Plumbing System Design
Subject guide — a code subject several of the state exam outlines declare.
Plumbing System Design
Reference text for the plumbing system design area. Every rule below is stated from a printed line of
the 2024 International Plumbing Code (IPC 2024) that carries it, or from a line of the Georgia rule
110-11-1-.26 that the state prints beside it, and the address of the line is given with the rule.
Numbers appear only where the printed line carries them.
This area is the selection and sizing side of the trade: choosing a fixture, a valve, a pump, a water
heater, an interceptor or a drain system, and fixing its size and capacity. The code answers it in the
tables it prints for each subject — a flow rate and a pressure for a fixture supply, a drainage fixture
unit value for a fixture, a maximum load for a pipe size, a flow rate for a leader, a capacity for a
sewage pump, a retention capacity for a grease interceptor — and Georgia replaces two of those printed
values and adds a table of its own for water heaters. Section 11 names the outline items the pieces
filed here do not carry.
1. Sizing the water distribution system
The water service pipe is sized for the system it serves (IPC 2024, 603.1), and the distribution system
is designed with pipe sizes selected so that under conditions of peak demand the capacities at the
fixture supply pipe outlets are not less than the code's printed table of flow rate and flow pressure
for each fixture supply outlet; a fixture or appliance not listed in that table takes the minimum flow
rate and flow pressure of its manufacturer's installation instructions (IPC 2024, 604.3). The maximum
flow rates and consumption of the fixtures and fixture fittings themselves come from a second printed
table (IPC 2024, 604.4), which Georgia replaces with the state's own: the revised table keeps the
published maximum flow rate or quantity for each fixture and fixture fitting and carries the state's
note pointing at its own waiver from the high-efficiency fixture requirement (GA-rule, l. 736, GA-rule,
l. 820). A fixture supply pipe has a minimum size taken from the code's third table on the subject, the
supply pipe terminating not more than 30 inches (762 mm) from the point of connection to the fixture, a
reduced-size flexible water connector being of an approved type, the supply pipe extending to the floor
or wall adjacent to the fixture, and the minimum size of individual distribution lines in a gridded or
parallel system also coming from that table (IPC 2024, 604.5). In a parallel or gridded system, the hot
and cold water manifolds are sized in accordance with the manifold sizing table, the total gallons per
minute being the demand of all outlets supplied (IPC 2024, 604.10.1).
Where the pressures vary, the code gives the designer a rule rather than a value. Variable street
pressures are accommodated by one of the means the section prints (IPC 2024, 604.6); where the water
pressure is insufficient, an approved booster pump, elevated tank or other approved device supplied or
approved by the serving water purveyor is installed (IPC 2024, 604.7); where the static pressure within
a building exceeds 80 psi (552 kPa), an approved water pressure-reducing valve or regulator with
strainer is installed to reduce the pressure in the building distribution piping to not greater than 80
psi (552 kPa) static, with an exception for service lines to sill cocks and outside hydrants and for
main supply risers where pressure from the mains is reduced to 80 psi or less at individual fixtures
(IPC 2024, 604.8); a water-hammer arrestor is installed where quick-closing valves are used (IPC 2024,
604.9); and individual pressure balancing in-line valves are installed in a configuration that will
accommodate an individual pressure balancing in-line valve for each fixture fitting (IPC 2024, 604.11).
2. Selecting and sizing the valves
A valve selected for a system is compatible with the piping material installed in that system, conforms
to one of the standards the code's valve table lists or is approved, and a valve intended to supply
drinking water meets the drinking water standard (IPC 2024, 605.7). Where full-open valves and shutoff
valves are required, the code fixes their locations: the full-open valves from the building water
service pipe near the curb through the entrance into the structure, the discharge side of every water
meter, the base of every riser and the top of every down-feed pipe to the water supply pipe of every
water heater (IPC 2024, 606.1), and the shutoff valve locations printed in the section beside it
(IPC 2024, 606.2), with Georgia adding one — access on the same floor as a refrigerator for the shutoff
valve serving its automatic icemaker (GA-rule, l. 855). Access is provided to all of them (IPC 2024,
606.3), and they are identified: service and hose bibb valves by identification, and other valves not
adjacent to the fixture or appliance they serve by an identification indicating what they serve
(IPC 2024, 606.4). A safety valve is selected to its duty: a storage water heater operating above
atmospheric pressure has an approved self-closing pressure relief valve and temperature relief valve or
a combination conforming to the printed standard, not used to control thermal expansion (IPC 2024,
504.4), and the valve's relieving capacity equals or exceeds the heat input to the heater or tank it
serves, with a temperature setting of not more than 210°F and a pressure setting not exceeding the
manufacturer's rated working pressure or 150 psi, whichever is less (IPC 2024, 504.5). A backflow
preventer is chosen by application: which assembly belongs on which connection, at which degree of
hazard, is a printed table the application must conform to (IPC 2024, 608.1), and the minimum air gap
between an opening or outlet and a fixture's flood level rim is likewise a printed table (IPC 2024,
608.16.1). A storm drainage system is provided with backwater valves as required for sanitary drainage
systems (IPC 2024, 1101.9), and the conditions that require one are printed in the sanitary drainage
chapter: fixtures below the elevation of the next upstream manhole cover of the public sewer are
protected by a backwater valve installed in the building drain or the horizontal branch serving them
(IPC 2024, 714.1).
3. Sizing the drainage system
Horizontal drainage piping is installed at the slope the code's slope table requires (IPC 2024, 704.1).
The load a pipe may carry is counted in drainage fixture units taken from the fixture-unit table, and a
fixture not listed there is given its value by the code official on the basis of the discharge it
delivers (IPC 2024, 709.1, IPC 2024, 709.2); where a discharge is known only in gallons per minute or
litres per second, the fixture unit value is computed on the printed basis that 1 gpm (0.06 L/s) of flow
is equivalent to two drainage fixture units (IPC 2024, 709.3). The maximum number of fixture units
connected to a given size of building sewer, building drain or horizontal branch is determined from the
code's table of building drains and sewers, and the maximum connected to a given size of horizontal
branch or vertical soil or waste stack from the table of horizontal branches and stacks (IPC 2024,
710.1). Horizontal and vertical stack offsets in buildings of five stories or more follow the offsets
chapter (IPC 2024, 711.1, IPC 2024, 711.2). A fixture trap is sized to drain the fixture rapidly and is
not less than the size the fixture-unit table indicates for that fixture, and a trap is not larger than
the drainage pipe into which it discharges (IPC 2024, 1002.5).
A designer who sizes a system by computation rather than by table follows the chapter the code prints
for it: the design of the drainage system is by the methods of that chapter (IPC 2024, 713.1), the load
on the drainage system is calculated from the fixture discharge profiles and the drainage fixture units
of the fixtures served (IPC 2024, 713.2, IPC 2024, 713.2.1), and pipe sizes are selected from the pipe
wall roughness of the material and the slope of the horizontal drainage piping so that the pipe is sized
to prevent full-bore flow (IPC 2024, 713.3, IPC 2024, 713.3.1, IPC 2024, 713.3.2).
4. Sizing the vents
The minimum required diameter of stack vents and vent stacks is determined from the developed length and
the total of drainage fixture units connected to them in accordance with the code's table of size and
developed length, and in no case is it less than one-half the diameter of the drain served or less than
1 1/4 inches (32 mm) (IPC 2024, 906.1). A vent system designed as an engineered system follows that
section's requirements (IPC 2024, 919.1), and one designed by computation where the code permits it
follows the computerized vent design section (IPC 2024, 920.1).
5. Sizing roof drains, leaders, gutters and storm drains
A roof drain is selected on its published flow rate, which is based on the head of water above the roof
drain, and that rate is what the storm drainage system is sized to; the flow rate used for sizing is
based on the maximum anticipated ponding at the roof drain (IPC 2024, 1105.2). Vertical and horizontal
storm drain piping is sized on the flow rate through the roof drain, calculated by the code's rainfall
rate conversion method and checked against the roof drain manufacturer's published flow rate for the
specific model and size to verify that the selected roof drain will handle the anticipated flow, and the
flow rate in the piping does not exceed that of the storm drain pipe sizing table (IPC 2024, 1106.2,
IPC 2024, 1106.2.1). Vertical leaders are sized on the flow rate from the horizontal gutters or the
maximum flow rate through the roof drains, within the limits of the vertical leader sizing table
(IPC 2024, 1106.3). Where a vertical wall or a parapet wall is drained, the sizing follows those
sections (IPC 2024, 1106.4, IPC 2024, 1106.5), and a horizontal gutter is sized in accordance with the
gutter sizing table (IPC 2024, 1106.6). A secondary or emergency roof drainage system is sized in
accordance with the storm drain sizing section on the rainfall rate for which the primary system is
sized, its scuppers sized to prevent ponding deeper than the roof was designed for, an opening dimension
of not less than 4 inches (102 mm) in height and an opening width equal to the circumference of the roof
drain required for the area served, and the flow through the primary system is not counted when the
secondary system is sized (IPC 2024, 1108.3). The number of roof drains is fixed by the code: not less
than two roof drains in roof areas of 10,000 square feet (929 m²) or less and not less than four in
roofs over that area (IPC 2024, 1110.4).
6. Selecting a sump, a pump and a sewage ejector
A sump's pump, pit and discharge piping are selected and installed under the sump design section
(IPC 2024, 712.3), whose own subsections fix the pump, the pit, the discharge pipe and its fittings,
their materials and ratings, the maximum effluent level and the pump connection to the drainage system
(IPC 2024, 712.3.1, IPC 2024, 712.3.2, IPC 2024, 712.3.3, IPC 2024, 712.3.4, IPC 2024, 712.3.5). A
sewage pump or sewage ejector automatically discharges the contents of the sump to the building drainage
system (IPC 2024, 712.4) and is selected with the capacity and head the application requires: a pump
receiving the discharge of water closets handles spherical solids up to and including 2 inches (51 mm)
in diameter and other pumps up to and including 1/2 inch (13 mm), and the capacity for a given discharge
pipe diameter is not less than the value of the minimum capacity table — 21 gallons per minute for a
2-inch discharge pipe, 30 for 2 1/2-inch and 46 for 3-inch — with the printed exceptions for grinder
pumps and for a macerating toilet assembly serving a single water closet (IPC 2024, 712.4.2). A storm
sump pump is selected on the same principle: it is of a capacity and head appropriate to the anticipated
use requirements (IPC 2024, 1113.1.1).
7. Selecting a water heater
The water heater chapter governs the materials, design and installation of water heaters and their
related safety devices and appurtenances (IPC 2024, 501.1), and the selection side of it is what this
area asks for. The heater is located and connected so as to provide access for observation, maintenance,
servicing and replacement (IPC 2024, 501.4) and with the service space the code prints for an appliance
(IPC 2024, 502.5). Water from a tankless heater is not hotter than 140°F where intended for domestic
use, which does not supersede the requirement for protective shower valves (IPC 2024, 501.6). Where
leakage would cause damage, the heater stands in a pan at least 1 1/2 inches deep and large enough for
all dripping or condensate, drained by an indirect waste pipe at least 3/4 inch in diameter (IPC 2024,
504.7, IPC 2024, 504.7.1).
Georgia sizes the residential water heater in a table of its own. Water heaters installed in residential
occupancies are sized in accordance with the state's minimum capacities table or the manufacturer's
recommendations, and the water heater must at a minimum meet the First Hour Rating requirements of that
table (GA-rule, l. 494); the table prints a first hour rating in gallons for a residence by number of
bedrooms and number of bathrooms — 40 gallons for a one-bath residence with one bedroom, 40 for two
bedrooms and 48 for three; 47 gallons for a residence with two to two and a half baths and two bedrooms,
60 for three, 62 for four and 70 for five; and 60 gallons for a residence with three to three and a half
baths and three bedrooms, 67 for four, 70 for five and 72 for six (GA-rule, l. 568, GA-rule, l. 624,
GA-rule, l. 688) — and a tankless water heater is sized and installed per the manufacturer's
recommendations (GA-rule, l. 720). Georgia also states where the water heater stops
being a plumbing selection: the State's minimum requirements for boilers and water heaters and for
pressure vessels over 200,000 Btu/h (58.61 kW), 210 degrees Fahrenheit or 120 gallons capacity are
established by O.C.G.A. Title 25, Chapter 15 and the rules and regulations of the Office of Insurance
and Safety Fire Commissioner (GA-rule, l. 460). And a storage water heater supplied with cold water
passing through a check valve, pressure reducing valve or backflow preventer has a thermal expansion
control device connected to its cold water supply pipe downstream of all check valves, pressure reducing
valves, backflow preventers and shutoff valves, the tank located at least 18 inches of developed length
from the cold water inlet fitting, sized in accordance with the tank manufacturer's instructions and so
that the system pressure does not exceed the code's limit (GA-rule, l. 872).
8. Selecting an interceptor or a separator
The fixture and the flow decide the interceptor. A grease interceptor has the grease retention capacity
indicated in the code's capacity table for the flow-through rates indicated (IPC 2024, 1003.3.5.1), and
where a hydromechanical interceptor is selected its rate of flow control is governed by the section
beside it (IPC 2024, 1003.3.5.2). An oil separator is listed and labelled, or designed in accordance
with the code's oil separator design sections (IPC 2024, 1003.4.2). A sand or similar interceptor for
heavy solids is designed and located so as to have ready access for cleaning and has a water seal of not
less than 6 inches (152 mm) (IPC 2024, 1003.5). A clothes washer discharges through an interceptor
provided with a wire basket or similar device, removable for cleaning, that prevents the passage into
the drainage system of solids 1/2 inch (12.7 mm) or larger, string, rags, buttons or other materials
detrimental to the public sewage system (IPC 2024, 1003.6). Whichever is selected, it is designed so as
not to become air bound and is vented in accordance with one of the venting methods of the vents
chapter (IPC 2024, 1003.9), and access is provided to each interceptor and separator for service and
maintenance (IPC 2024, 1003.10).
9. Selecting fixtures, and what the number of them comes from
How many fixtures a building needs is a table question before it is a design question: plumbing fixtures
are provided in the minimum number shown in the code's minimum plumbing facilities table, based on the
actual use of the building or space, a use not shown in the table being considered individually by the
code official, and the number of occupants being determined by the International Building Code
(IPC 2024, 403.1). The calculation is printed: the total occupant load is divided in half to determine
the occupant load of each sex, the fixture ratios of the table are applied to the occupant load of each
sex, fractional numbers are rounded up to the next whole number, and for multiple occupancies the
fractional numbers are first summed and then rounded up (IPC 2024, 403.1.1). Georgia changes that table
twice: the service sink requirements are deleted entirely and without substitution (GA-rule, l. 249),
and the residential lines gain one kitchen sink per dwelling unit, one automatic clothes washer
connection per twenty dwelling units in an apartment house or per dwelling unit in a one- or two-family
dwelling, and not less than two exterior hose bibs, sill cocks or outside hydrants with one located on
the side or rear of the structure for a detached single-family, duplex or multi-family dwelling three
stories or less in height (GA-rule, l. 339, GA-rule, l. 364). Separate facilities, employee and public
toilet facilities, signage and drinking fountain location are the sections beside it (IPC 2024, 403.2,
IPC 2024, 403.3, IPC 2024, 403.4, IPC 2024, 403.5), and the state raises the threshold below which
drinking fountains are not required to an occupant load of 25 or fewer (GA-rule, l. 392).
Accessibility is selected to a standard rather than to a size: accessible plumbing facilities and
fixtures are provided in accordance with the building code's accessibility chapter (IPC 2024, 404.1),
and the accessible fixtures themselves are installed in accordance with the printed accessibility
standard (IPC 2024, 404.2). A specialty fixture is selected by its application and its material:
materials for specialty fixtures not otherwise covered in the code are stainless steel, soapstone,
chemical stoneware or plastic, or are lined with lead, copper-base alloy, nickel-copper alloy,
corrosion-resistant steel or another material especially suited to the application for which the fixture
is intended (IPC 2024, 402.2). The hospital, medical and prison fixtures the outline names are reached
by the code's provisions for plumbing in mental health centers (IPC 2024, 405.7), and its specialty
fixture and whirlpool provisions print the requirements those installations are selected against
(IPC 2024, 423.1, IPC 2024, 426.1, IPC 2024, 426.2). An emergency shower or eyewash station conforms to
the printed standard, needs no waste connection, and where hot and cold water are supplied to it the
temperature is controlled only by a temperature-actuated mixing valve complying with the printed
standard, a water heater supplying it directly complying with another printed standard (IPC 2024, 411.1,
IPC 2024, 411.2, IPC 2024, 411.3). A shower floor or receptor is selected with its support and its
lining: floors under shower compartments other than prefabricated receptors are lined and made
watertight with a material complying with the lining sections, the liner turning up on all sides not
less than 2 inches (51 mm) above the finished threshold level (IPC 2024, 421.5.2), and the receptor is
supported as the section requires (IPC 2024, 421.5.1). A pan under a water heater is the other pan the
outline names, and its size and drain are printed: the pan is large enough for all dripping or
condensate and its drain terminates over an indirect waste receptor or floor drain or to the exterior
not less than 6 inches and not more than 24 inches above the adjacent ground surface (IPC 2024, 504.7.1,
IPC 2024, 504.7.2).
10. Selecting a specialty waste system
A special or indirect waste system is required for the applications the code lists: food-handling
equipment other than in dwelling units, clear-water waste, humidifiers, dishwashing machines and
utensils, pots, pans and dishwashing sinks discharge through an indirect waste pipe, and fixtures not
required by that section to be indirectly connected are directly connected to the plumbing system as
the drainage chapter requires (IPC 2024, 802.1). The connection is made by an air gap or an air break of
the printed type (IPC 2024, 802.3.1, IPC 2024, 802.3.2), the receptor receiving the discharge is sized
for the maximum discharge of all indirect waste pipes it serves and installed to prevent splashing or
flooding (IPC 2024, 802.4.1), and a standpipe is individually trapped, extends not less than 18 inches
(457 mm) and not more than 42 inches (1067 mm) above the trap weir, and has access provided for rodding
(IPC 2024, 802.4.3). Corrosive wastes are not discharged into the plumbing system without a selected
device: corrosive liquids, spent acids or other harmful chemicals that destroy or injure a drain, sewer,
soil or waste pipe or create noxious or toxic fumes or interfere with sewage treatment are not
discharged without being thoroughly diluted, neutralized or treated by passing through an approved
dilution or neutralizing device, automatically supplied with enough diluting water or neutralizing
medium to make the contents noninjurious before discharge, and the nature of the waste and its treatment
method are approved prior to installation (IPC 2024, 803.1). The on-site reuse systems of the code's
nonpotable chapter, where one is selected, have their own design section, and Georgia adds to the
chapter the uses reclaimed water from a permitted treatment facility may supply (GA-rule, l. 1006).
11. What these pieces do not carry
(GA-bulletin, l. 478). The plumbing code does not size a boiler: what it states about one is the
protection of the potable water that feeds it — the potable supply to a boiler is equipped with a
backflow preventer with an intermediate atmospheric vent complying with the printed standards, and
where conditioning chemicals are introduced into the system the potable water connection is protected
by an air gap or a reduced pressure principle backflow preventer complying with the printed standards
(IPC 2024, 608.17.2). Above the printed threshold, Georgia hands the subject to another authority: the
State's minimum requirements for boilers and water heaters and for pressure vessels over 200,000 Btu/h
(58.61 kW), 210 degrees Fahrenheit or 120 gallons capacity are established by O.C.G.A. Title 25,
Chapter 15 and the rules of the Office of Insurance and Safety Fire Commissioner (GA-rule, l. 460). No
boiler capacity, rating or sizing method is stated in this text.
and vacuum piping (GA-bulletin, l. 481). Gas piping is not a subject of this code: the code's scope
states that the installation of fuel gas distribution piping and equipment, fuel-gas-fired water
heaters and water heater venting systems is regulated by the International Fuel Gas Code (IPC 2024,
101.2), and Georgia's general applicability section repeats that sentence as the first sentence of its
scope (GA-rule, l. 151). No gas sizing method, table or pressure is stated here.
storage systems chapter, whose nonflammable medical gas provision is the printed line this text can
point at (IPC 2024, 1202.1); the design and installation of nonmedical oxygen systems are carried by
the printed NFPA standards rather than by this code (IPC 2024, 1203.1). Nothing further is asserted
about industrial or specialty piping here.
first-hour rating that governs a residential water heater in Georgia is printed by the state's rule
and not by the model code (GA-rule, l. 494); the high-efficiency fixture and faucet requirements that
the code's maximum-flow table refers to are the state's own additions (GA-rule, l. 170, GA-rule, l.
404); and the requirement to disinfect a new or repaired potable water system is the state's revised
wording of the code's disinfection section (GA-rule, l. 892). For a tankless water heater the code
states no rating at all: it states the temperature limit of the water delivered, not hotter than 140°F
where intended for domestic use (IPC 2024, 501.6).
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free