Drains and Sewers
Content area 5 of the Oklahoma master plumber exam.
Sanitary Drainage Systems
Reference text for the sanitary drainage area. Every rule below is written from the printed line of
the 2024 International Plumbing Code (IPC 2024) that carries it, and each rule names the section it
comes from. Where the printed line does not state a value, no value is stated here.
1. General
The chapter governs the materials, design, construction and installation of sanitary drainage systems
(IPC 2024, 701.1). Sanitary drainage piping from plumbing fixtures in buildings, and sanitary drainage
piping systems from premises, must be connected to a public sewer; where a public sewer is not
available they must be connected to a private sewage disposal system in compliance with state or local
requirements, and, where such requirements do not exist, to an approved private sewage disposal system
in accordance with the International Private Sewage Disposal Code (IPC 2024, 701.2). The exception
covers piping and systems that convey only the discharge from bathtubs, showers, lavatories, clothes
washers and laundry trays, provided they are connected to a system in accordance with Chapter 13 or 14
(IPC 2024, 701.2, Exception).
A building having plumbing fixtures installed and intended for human habitation, occupancy or use on
premises abutting on a street, alley or easement in which there is a public sewer must have a separate
connection with the sewer; where located on the same lot, multiple buildings may connect to a common
building sewer that connects to the public sewer (IPC 2024, 701.3). Sewage or other waste deleterious
to surface or subsurface waters must not be discharged into the ground or into any waterway unless
first rendered innocuous through an approved form of treatment (IPC 2024, 701.4), and waste
detrimental to the public sewer system or to the functioning of the sewage-treatment plant must be
treated and disposed of in accordance with Section 1003 as directed by the code official (IPC 2024,
701.5). The sanitary drainage system is tested in accordance with Section 312 (IPC 2024, 701.6), and
engineered sanitary drainage systems must conform to Sections 316 and 713 (IPC 2024, 701.7).
2. Materials and joints
Sections 702.1 (above-ground sanitary drainage and vent pipe), 702.2 (underground building sanitary
drainage and vent pipe), 702.3 (building sewer pipe) and 702.4 (fittings) publish the materials and
the standards for those applications. Where the wastewater temperature will be greater than 140°F
(60°C), the sanitary drainage piping material must be rated for the highest temperature of the
wastewater (IPC 2024, 702.5). Section 702.6 governs chemical waste systems and Section 702.7 lead
bends and traps.
Section 705 contains the provisions applicable to joints specific to sanitary drainage piping
(IPC 2024, 705.1): 705.2 ABS plastic, 705.3 cast iron, 705.4 concrete joints, 705.5 copper pipe,
705.6 copper tubing, 705.7 borosilicate glass joints, 705.8 steel, 705.9 lead, 705.10 PVC plastic,
705.11 vitrified clay, 705.12 polyethylene plastic pipe, 705.13 polyolefin plastic, 705.14
polyvinylidene fluoride plastic, 705.15 polypropylene plastic, 705.16 joints between different
materials, 705.17 drainage slip joints, 705.18 caulking ferrules, 705.19 soldering bushings and
705.20 stainless steel drainage systems. Prohibited joints and connections in
drainage piping are: cement or concrete joints; mastic or hot-pour bituminous joints; joints made
with fittings not approved for the specific installation; joints between different diameter pipes made
with elastomeric rolling O-rings; solvent-cement joints between different types of plastic pipe except
where provided for in Section 705.16.4; and saddle-type fittings (IPC 2024, 707.1).
3. Building sewer
The proximity of a sewer to a water service must comply with Section 603.2 (IPC 2024, 703.1). Where a
building sewer or building drain is installed on filled or unstable ground, the drainage pipe must
conform to one of the standards for ABS plastic pipe, cast-iron pipe, copper or copper-alloy tubing,
PVC plastic pipe or polypropylene plastic pipe indicated in Table 702.3 (IPC 2024, 703.2). Where
separate systems of sanitary drainage and storm drainage are installed in the same property, the
sanitary and storm building sewers or drains may be laid side by side in one trench (IPC 2024, 703.3).
Where the entire sanitary drainage system of an existing building is replaced, existing building
drains under concrete slabs and existing building sewers that will serve the new system must be
internally examined to verify that the piping is sloping in the correct direction, is not broken, is
not obstructed and is sized for the drainage load of the new plumbing drainage system to be installed
(IPC 2024, 703.4). Cleanouts on building sewers are located as indicated in Section 708 (IPC 2024,
703.5), and where the public sewer is a combined system for both sanitary and storm water the sanitary
sewer must be connected independently to the public sewer (IPC 2024, 703.6).
4. Drainage piping installation
4.1 Slope
Horizontal drainage piping must be installed in uniform alignment at uniform slopes. The slope must be
not less than Table 704.1 shows, except that where the drainage piping is upstream of a grease
interceptor the slope must be not less than 1/4 inch per foot (2 percent slope) (IPC 2024, 704.1).
| Size (inches) | Minimum slope (inch per foot) |
|---|---|
| 2 1/2 or less | 1/4 |
| 3 to 6 | 1/8 |
| 8 or larger | 1/16 |
For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.33 mm/m. Slopes for piping draining to a grease
interceptor comply with Section 704.1 (IPC 2024, Table 704.1, footnote a).
4.2 Size reduction, offsets and future fixtures
The size of the drainage piping must not be reduced in the direction of flow. The following are not
considered a reduction in size in the direction of flow: a 4-inch by 3-inch (102 mm by 76 mm) water
closet flange; a water closet bend fitting having a 4-inch (102 mm) inlet and a 3-inch (76 mm) outlet,
provided the 4-inch leg of the fitting is upright and below, but not necessarily directly connected
to, the water closet flange; and an offset closet flange (IPC 2024, 704.2).
Horizontal branches must connect to the bases of stacks at a point located not less than 10 times the
diameter of the drainage stack downstream from the stack, and must connect to horizontal stack offsets
at a point located not less than 10 times the diameter of the drainage stack downstream from the
upper stack (IPC 2024, 704.3). Drainage piping for future fixtures must terminate with an approved cap
or plug (IPC 2024, 704.4).
5. Connections and fittings
Connections and changes in direction of the sanitary drainage system must be made with approved
drainage fittings; connections between drainage piping and fixtures conform to Section 405 (IPC 2024,
706.1). Fittings must not have ledges, shoulders or reductions capable of retarding or obstructing
flow in the piping, and threaded drainage pipe fittings must be of the recessed drainage type; the
section does not apply to tubular waste fittings used to convey vertical flow upstream of the trap
seal liquid level of a fixture trap (IPC 2024, 706.2).
Fittings must be installed to guide sewage and waste in the direction of flow, and changes in
direction must be made by fittings installed in accordance with Table 706.3. Change in direction by
combination fittings, side inlets or increasers must be installed in accordance with Table 706.3 based
on the pattern of flow created by the fitting. Double sanitary tee patterns must not receive the
discharge of back-to-back water closets and fixtures or appliances with pumping action discharge;
back-to-back water closet connections to double sanitary tees are permitted where the horizontal
developed length between the outlet of the water closet and the connection to the double sanitary tee
pattern is 18 inches (457 mm) or greater (IPC 2024, 706.3 and Exception).
Table 706.3 — fittings for change in direction ("X" = permitted):
| Type of fitting pattern | Horizontal to vertical | Vertical to horizontal | Horizontal to horizontal |
|---|---|---|---|
| Sixteenth bend | X | X | X |
| Eighth bend | X | X | X |
| Sixth bend | X | X | X |
| Quarter bend | X | Xᵃ | Xᵃ |
| Short sweep | X | Xᵃ,ᵇ | Xᵃ |
| Long sweep | X | X | X |
| Sanitary tee | Xᶜ | — | — |
| Wye | X | X | X |
| Combination wye and eighth bend | X | X | X |
Fitting limitations, as the printed table carries them on the marked cells (IPC 2024,
Table 706.3, footnotes a, b and c): the fittings marked a are only permitted for a 2-inch or smaller
fixture drain; the cell marked b carries "three inches or larger"; and the double sanitary tee
limitation is Section 706.3.
Heel-inlet quarter bends are an acceptable means of connection except where the quarter bend serves a
water closet; a low-heel inlet must not be used as a wet-vented connection; side-inlet quarter bends
are an acceptable means of connection for drainage, wet venting and stack venting arrangements
(IPC 2024, 706.4).
6. Cleanouts
Cleanouts must be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.12
(IPC 2024, 708.1). The principal requirements:
100 feet (30 480 mm), and building drains must have cleanouts at intervals of not more than 100 feet
(30 480 mm) except where manholes are used instead of cleanouts, in which case the manholes must be
located at intervals of not more than 400 feet (122 m); the interval is measured from the cleanout
or manhole opening, along the developed length of the piping, to the next drainage fitting providing
access for cleaning, the end of the horizontal drain or the end of the building drain (IPC 2024,
708.1.1).
100 feet (30 480 mm); building sewers 8 inches (203 mm) and larger must have a manhole located not
more than 200 feet (60 960 mm) from the junction of the building drain and building sewer and at
intervals of not more than 400 feet (122 m) (IPC 2024, 708.1.2).
the junction or within 10 feet (3048 mm) of the developed length of piping upstream of the
junction; removal of the water closet must not be required to provide cleanout access (IPC 2024,
708.1.3).
direction greater than 45 degrees, a cleanout must be installed at the change of direction; where
more than one such change occurs within 40 feet (12 192 mm) of developed length, the cleanout
installed for the first change serves all changes in direction within that 40 feet (IPC 2024,
708.1.4).
4 inches (102 mm) need not be larger than 4 inches (102 mm); a removable P-trap with slip or ground
joint connections can serve as a cleanout for drain piping one size larger than the P-trap size;
cleanouts located on stacks can be one size smaller than the stack size; and the size of cleanouts
for cast-iron piping can be in accordance with the referenced standards for cast-iron fittings in
Table 702.4 (IPC 2024, 708.1.5 and Exceptions).
acceptable as a cleanout equivalent (IPC 2024, 708.1.6). Cleanout plugs must be of copper-alloy,
plastic or other approved materials (borosilicate glass for borosilicate glass piping systems),
copper-alloy plugs conforming to ASTM A74 and limited to metallic piping systems, plastic plugs
conforming to the referenced standards for plastic pipe fittings in Table 702.4, with a raised
square head, a countersunk square head or a countersunk slot head, and manufactured with a blind
end threaded hole where a trim cover screw will be installed (IPC 2024, 708.1.7).
must have gas-tight covers that require tools for removal (IPC 2024, 708.1.8). The installation
arrangement of a cleanout must enable cleaning of drainage piping only in the direction of drainage
flow, except for test tees serving as cleanouts and a two-way cleanout installation approved for
meeting Section 708.1.3 (IPC 2024, 708.1.9).
less than 18 inches (457 mm) from, and perpendicular to, the face of the opening to any
obstruction; cleanouts for 8-inch (203 mm) and larger piping must have a clearance of not less than
36 inches (914 mm) (IPC 2024, 708.1.10).
inside of plenums, within walls, within floor/ceiling assemblies, below grade and in crawl spaces
where the height from the crawl space floor to the nearest obstruction along the path from the
crawl space opening to the cleanout is less than 24 inches (610 mm). Cleanouts with openings at a
finished wall must have the face of the opening within 1 1/2 inches (38 mm) of the finished wall
surface; cleanouts located below grade must be extended to grade level so that the top of the
cleanout plug is at or above grade; and a cleanout installed in a floor or walkway without a trim
cover must have a countersunk plug installed so the top surface of the plug is flush with the
finished surface of the floor or walkway (IPC 2024, 708.1.11).
trim cover fasteners that thread into cleanout plugs must be corrosion resistant, and cleanout plugs
must not be covered with mortar, plaster or any other permanent material (IPC 2024, 708.1.11.1).
Cleanout assemblies in accordance with ASME A112.36.2M must be installed where it is necessary to
protect a cleanout plug from the loads of vehicular traffic (IPC 2024, 708.1.11.2).
where another cleanout of equal size is installed with the required access and clearance (IPC 2024,
708.1.12).
7. Fixture units
Drainage fixture unit values in Table 709.1 designate the relative load weight of different kinds of
fixtures, to be used in estimating the total load carried by a soil or waste pipe and in connection
with Tables 710.1(1) and 710.1(2) (IPC 2024, 709.1).
| Fixture type | Drainage fixture unit value | Minimum size of trap (inches) |
|---|---|---|
| Automatic clothes washers, commercial | 3 | 2 |
| Automatic clothes washers, residential | 2 | 2 |
| Bathroom group as defined in Section 202 (1.6 gpf water closet) | 5 | — |
| Bathroom group as defined in Section 202 (water closet flushing greater than 1.6 gpf) | 6 | — |
| Bathtub (with or without overhead shower or whirlpool attachments) | 2 | 1 1/2 |
| Bidet | 1 | 1 1/4 |
| Combination sink and tray | 2 | 1 1/2 |
| Dental lavatory | 1 | 1 1/4 |
| Dental unit or cuspidor | 1 | 1 1/4 |
| Dishwashing machine, domestic | 2 | 1 1/2 |
| Drinking fountain | 1/2 | 1 1/4 |
| Emergency floor drain | 0 | 2 |
| Floor drains | 2 | 2 |
| Floor sinks | Note h | 2 |
| Kitchen sink, domestic | 2 | 1 1/2 |
| Kitchen sink, domestic with food waste disposer, dishwasher or both | 2 | 1 1/2 |
| Laundry tray (1 or 2 compartments) | 2 | 1 1/2 |
| Lavatory | 1 | 1 1/4 |
| Service sink | 2 | 1 1/2 |
| Sink | 2 | 1 1/2 |
| Urinal | 4 | Note d |
| Urinal, 1 gallon per flush or less | 2 | Note d |
| Urinal, nonwater supplied | 1/2 | Note d |
| Wash sink (circular or multiple), each set of faucets | 2 | 1 1/2 |
| Water closet, flushometer tank, public or private | 4 | Note d |
| Water closet, private (1.6 gpf) | 3 | Note d |
| Water closet, private (flushing greater than 1.6 gpf) | 4 | Note d |
| Water closet, public (1.6 gpf) | 4 | Note d |
| Water closet, public (flushing greater than 1.6 gpf) | 6 | Note d |
Table notes that carry rules: a showerhead over a bathtub or whirlpool bathtub attachment does not
increase the drainage fixture unit value (footnote b); trap size must be consistent with the fixture
outlet size (footnote d); and for traps larger than 3 inches, Table 709.2 is used (footnote a).
Showers are rated on the total flow rate through showerheads and body sprays: 5.7 gpm or less = 2 dfu
with a 1 1/2-inch trap; greater than 5.7 gpm to 12.3 gpm = 3 dfu with a 2-inch trap; greater than
12.3 gpm to 25.8 gpm = 5 dfu with a 3-inch trap; greater than 25.8 gpm to 55.6 gpm = 6 dfu with a
4-inch trap (IPC 2024, Table 709.1).
Where discharges to a waste receptor or to a drainage system are known only in gallons per minute, the
drainage fixture unit values for those flows are computed on the basis that 1 gpm (0.06 L/s) of flow
is equivalent to two drainage fixture units (IPC 2024, 709.3). The drainage fixture unit load of an
indirect waste receptor receiving the discharge of indirectly connected fixtures is the sum of the
drainage fixture unit values of the fixtures that discharge to the receptor, but not less than the
value given for the indirect waste receptor in Table 709.1 or 709.2 (IPC 2024, 709.4). Waste receptors
such as floor drains, floor sinks and hub drains that receive only clear-water waste from display
cases, refrigerated display cases, ice bins, coolers and freezers have a drainage fixture unit value
of one-half (IPC 2024, 709.4.1).
8. Drainage system sizing
The maximum number of drainage fixture units connected to a given size of building sewer, building
drain or horizontal branch of the building drain is determined using Table 710.1(1), and the maximum
number connected to a given size of horizontal branch or vertical soil or waste stack is determined
using Table 710.1(2) (IPC 2024, 710.1).
Table 710.1(1) — building drains and sewers:
| Diameter of pipe (inches) | 1/16 inch slope | 1/8 inch slope | 1/4 inch slope | 1/2 inch slope |
|---|---|---|---|---|
| 1 1/4 | — | — | 1 | 1 |
| 1 1/2 | — | — | 3 | 3 |
| 2 | — | — | 21 | 26 |
| 2 1/2 | — | — | 24 | 31 |
| 3 | — | 36 | 42 | 50 |
| 4 | — | 180 | 216 | 250 |
| 5 | — | 390 | 480 | 575 |
| 6 | — | 700 | 840 | 1,000 |
| 8 | 1,400 | 1,600 | 1,920 | 2,300 |
| 10 | 2,500 | 2,900 | 3,500 | 4,200 |
| 12 | 3,900 | 4,600 | 5,600 | 6,700 |
| 15 | 7,000 | 8,300 | 10,000 | 12,000 |
The minimum size of any building drain serving a water closet is 3 inches (IPC 2024,
Table 710.1(1), footnote a).
9. Offsets in drainage piping in buildings of five stories or more
If a horizontal branch connects to the stack within 2 feet (610 mm) above or below a vertical stack
offset, and the offset is located more than four branch intervals below the top of the stack, the
offset must be vented in accordance with Section 907; those vents are not required where the stack and
its offset are sized as a building drain (IPC 2024, 711.1 and 711.1.1).
A stack with a horizontal offset located more than four branch intervals below the top of the stack
must be vented in accordance with Section 907 and sized as follows: the portion of the stack above
the offset is sized as for a vertical stack based on the total number of drainage fixture units above
the offset; the offset is sized in accordance with Section 710.1.1; and the portion of the stack below
the offset is sized as for the offset or based on the total number of drainage fixture units on the
entire stack, whichever is larger (IPC 2024, 711.2). Those vents are not required where the stack and
its offset are one pipe size larger than required for a building drain and the entire stack and offset
are not less in cross-sectional area than that required for a straight stack plus the area of an
offset vent as provided in Section 907 (IPC 2024, 711.2.1).
Where a vertical offset occurs in a soil or waste stack below the lowest horizontal branch, a change
in diameter of the stack because of the offset is not required; if a horizontal offset occurs below
the lowest horizontal branch, the required diameter of the offset and of the stack below it must be
determined as for a building drain in accordance with Table 710.1(1) (IPC 2024, 711.3).
10. Sumps and ejectors
Building subdrains that cannot be discharged to the sewer by gravity flow must be discharged into a
tightly covered and vented sump from which the liquid is lifted and discharged into the building
gravity drainage system by automatic pumping equipment or other approved method; in other than
existing structures, the sump must not receive drainage from any piping within the building capable of
being discharged by gravity to the building sewer (IPC 2024, 712.1). A check valve and a full-open
valve located on the discharge side of the check valve must be installed in the pump or ejector
discharge piping between the pump or ejector and the gravity drainage system, with access to such
valves; they must be located above the sump cover required by Section 712.1 or, where the discharge
pipe from the ejector is below grade, accessibly outside the sump below grade in an access pit with a
removable access cover (IPC 2024, 712.2).
The sump pit must be not less than 18 inches (457 mm) in diameter and not less than 24 inches (610 mm)
in depth unless otherwise approved, provided with access, located so that all drainage flows into the
pit by gravity, constructed of tile, concrete, steel, plastic or other approved materials, with a
solid bottom providing permanent support for the pump, and fitted with a gastight removable cover
installed not more than 2 inches (51 mm) below grade or floor level, adequate to support anticipated
loads; the sump pit is vented in accordance with Chapter 9 (IPC 2024, 712.3.2). The effluent level
control must be adjusted and maintained to at all times prevent the effluent in the sump from rising
to within 2 inches (51 mm) of the invert of the gravity drain inlet into the sump (IPC 2024, 712.3.4).
Discharge pipe and fittings must be constructed of copper or copper-alloy, CPVC, ductile iron, PE or
PVC, rated for the maximum system operating pressure and temperature, compatible with the pipe
material, and suitable for burial where buried in the earth (IPC 2024, 712.3.3.1 and 712.3.3.2).
Pumps connected to the drainage system must connect to a building sewer, building drain, soil stack,
waste stack or horizontal branch drain; where the discharge line connects into horizontal drainage
piping, the connection must be made through a wye fitting into the top of the drainage piping, and
that wye fitting must be located not less than 10 pipe diameters from the base of any soil stack,
waste stack or fixture drain (IPC 2024, 712.3.5).
A sewage pump or sewage ejector must automatically discharge the contents of the sump to the building
drainage system (IPC 2024, 712.4). Macerating toilet systems must comply with ASME A112.3.4/CSA B45.9
and be installed in accordance with the manufacturer's instructions (IPC 2024, 712.4.1). A sewage pump
or ejector must have the capacity and head for the application requirements: pumps or ejectors that
receive the discharge of water closets must be capable of handling spherical solids with a diameter of
up to and including 2 inches (51 mm), and other pumps or ejectors must be capable of handling
spherical solids up to and including 1/2 inch (13 mm). Capacity based on the diameter of the discharge
pipe must be not less than Table 712.4.2 shows; grinder pumps or grinder ejectors that receive the
discharge of water closets must have a discharge opening of not less than 1 1/4 inches (32 mm), and
macerating toilet assemblies that serve single water closets must have a discharge opening of not less
than 3/4 inch (19.1 mm) (IPC 2024, 712.4.2 and Exceptions).
| Diameter of the discharge pipe (inches) | Capacity of pump or ejector (gpm) |
|---|---|
| 2 | 21 |
| 2 1/2 | 30 |
| 3 | 46 |
11. Computerized drainage design, backwater valves and rehabilitation
The sizing, design and layout of the drainage system may be designed by approved computer design
methods; the load is computed from the simultaneous or sequential discharge conditions from fixtures,
appurtenances and appliances or the peak usage design condition; discharge profiles for flow rates
versus time follow the manufacturer's specifications; pipe must be sized to prevent full-bore flow;
pipe size calculations use the pipe wall roughness factor (ks) per the manufacturer's specifications
as modified for aging roughness factors with deposits and corrosion; and horizontal drainage piping
must be designed and installed at slopes in accordance with Table 704.1 (IPC 2024, 713.1, 713.2,
713.2.1, 713.3, 713.3.1 and 713.3.2).
Where plumbing fixtures are installed on a floor with a finished floor elevation below the elevation
of the manhole cover of the next upstream manhole in the public sewer, such fixtures must be protected
by a backwater valve installed in the building drain or horizontal branch serving such fixtures;
fixtures installed on a floor with a finished floor elevation above the elevation of that manhole
cover must not discharge through a backwater valve, except that in existing buildings fixtures above
that elevation are not prohibited from discharging through a backwater valve (IPC 2024, 714.1 and
Exception). Backwater valves must comply with ASME A112.14.1, CSA B181.1 or CSA B181.2 (IPC 2024,
714.2), and must be installed so that access is provided to the working parts (IPC 2024, 714.3).
Sections 715 through 718 govern vacuum drainage systems, replacement of underground building sewers
and building drains by pipe-bursting methods, relining of building sewers and building drains, and
rehabilitation of building sewers and building drains; vacuum drainage systems must be designed per
the manufacturer's instructions and the plans, specifications and other data submitted to the code
official for review and approval prior to installation (IPC 2024, 715.1, 715.2, 716.1, 717.1 and
718.1).
12. Testing the sanitary drainage system
Section 312 governs the tests (IPC 2024, 701.6):
openings in the piping tightly closed except the highest opening, the system filled with water to
the point of overflow; if tested in sections, each opening tightly plugged except the highest
openings of the section under test and each section filled with water, but no section tested with
less than a 10-foot (3048 mm) head of water; in testing successive sections, not less than the upper
10 feet of the next preceding section must be tested, so that no joint or pipe in the building,
except the uppermost 10 feet of the system, is submitted to a test of less than a 10-foot head of
water. The pressure must be held for not less than 15 minutes, and the system must then be tight at
all points (IPC 2024, 312.2).
forcing air into the system until there is a uniform gauge pressure of 5 psi (34.5 kPa) or enough
to balance a 10-inch (254 mm) column of mercury, held for not less than 15 minutes, with adjustments
for ambient temperature or gasket seating made before the test period begins (IPC 2024, 312.3).
uniform gauge pressure of negative 5 pounds per square inch or a negative 10 inches of mercury
column, held without removal of additional air for 15 minutes (IPC 2024, 312.4).
and in sufficient detail to determine compliance; where a smoke test is used it is made by filling
all traps with water and introducing into the entire system a pungent, thick smoke produced by one
or more smoke machines; when the smoke appears at stack openings on the roof, the stack openings
must be closed and a pressure equivalent to a 1-inch water column (248.8 Pa) held for a test period
of not less than 15 minutes (IPC 2024, 312.5).
Storm Drainage
Reference text for the storm drainage area. Every rule below is written from the printed line of the
2024 International Plumbing Code (IPC 2024) that carries it, and each rule names the section it comes
from. Where the printed line does not state a value, no value is stated here; where a sizing table is
printed under a number, the table is reproduced under that number with the values read from the print.
The whole of Chapter 11 of the code is read for this text, together with the sections it refers to.
1. General
The chapter governs the materials, design, construction and installation of storm drainage
(IPC 2024, 1101.1). Rainwater falling on roofs, and storm water from paved areas, yards, courts and
courtyards, must drain to an approved place of disposal; for one- and two-family dwellings, and where
the code official approves it, such water is permitted to discharge onto flat areas such as streets or
lawns as long as the flow is directed away from the building (IPC 2024, 1101.2). The purpose stated by
the code for the whole chapter: rainfall onto buildings must be removed and directed to a location
that can accommodate storm water, and the chapter fixes the design rainfall event for the geographic
area and the sizing methods for piping and gutter systems, together with the piping materials and the
subsoil drainage rules (IPC 2024, Chapter 11, About this chapter).
Storm water must not be drained into a sewer intended for sewage only (IPC 2024, 1101.3). That
prohibition is the mirror of the rule printed for sanitary drainage: where the public sewer is a
combined system carrying both sanitary sewage and storm water, the sanitary sewer is connected
independently to that public sewer (IPC 2024, 703.6), and the storm sewer is likewise connected
independently to it (IPC 2024, 1109.1).
The conductors and the building storm drain are tested in accordance with Section 312
(IPC 2024, 1101.4). The size of a drainage pipe in the storm system must not be reduced in the
direction of flow (IPC 2024, 1101.5). Connections and changes of direction in the storm drainage
system must be made with approved drainage-type fittings in accordance with Table 706.3, and those
fittings must not obstruct or retard the flow in the system (IPC 2024, 1101.6).
Roof design carries a structural rule: roofs must be designed for the maximum possible depth of water
that will pond on them, as determined by the relative levels of the roof deck and of the overflow
weirs, scuppers, edges or serviceable drains, combined with the deflected structural elements. In
fixing that maximum depth, all primary roof drainage means are assumed to be blocked, and the depth
must include the height of water required above the inlet of the secondary roof drainage means for
that secondary means to carry the design rainfall rate required by Section 1106 (IPC 2024, 1101.7).
Cleanouts must be installed in the storm drainage system and must comply with the provisions of the
code for sanitary drainage pipe cleanouts; the exception printed there is the subsurface drainage
system (IPC 2024, 1101.8 and Exception). Storm drainage systems must be provided with backwater
valves as required for sanitary drainage systems in accordance with Section 714 (IPC 2024, 1101.9).
2. Materials
The materials and methods used to construct and install storm drainage systems must comply with this
section and with the applicable provisions of Chapter 7 (IPC 2024, 1102.1).
Inside storm drainage conductors installed above ground conform to one of the standards listed in
Table 702.1 (IPC 2024, 1102.2). Underground building storm drain pipe conforms to one of the standards
listed in Table 702.2 (IPC 2024, 1102.3). Building storm sewer pipe conforms to one of the standards
listed in Table 1102.4 (IPC 2024, 1102.4).
TABLE 1102.4 BUILDING STORM SEWER PIPE
| Material | Standard |
|---|---|
| Acrylonitrile butadiene styrene (ABS) plastic pipe in IPS diameters, including Schedule 40, DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or composite wall | ASTM D2661; ASTM F628; ASTM F1488; CSA B181.1; CSA B182.1 |
| Cast-iron pipe | ASTM A74; ASTM A888; CISPI 301 |
| Concrete pipe | ASTM C14; ASTM C76; CSA A257.1; CSA A257.2 |
| Copper or copper-alloy tubing (Type K, L, M or DWV) | ASTM B75; ASTM B88; ASTM B251; ASTM B306 |
| Polyethylene (PE) plastic pipe | ASTM F667; ASTM F2306/F2306M; ASTM F2648/F2648M; ASTM F2763; ASTM F2947/F2947M; CSA B182.8 |
| Polypropylene (PP) pipe | ASTM F2764; ASTM F2881; CSA B182.13 |
| Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR26, SDR35, SDR41, PS50 or PS100) in IPS diameters, including Schedule 40, DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or composite wall | ASTM D2665; ASTM D3034; ASTM F891; ASTM F1488; CSA B181.2; CSA B182.2; CSA B182.4 |
| Stainless steel drainage systems, Type 316L | ASME A112.3.1 |
| Vitrified clay pipe | ASTM C4; ASTM C700 |
Subsoil drains are open-jointed, horizontally split or perforated pipe conforming to one of the
standards listed in Table 1102.5 (IPC 2024, 1102.5).
TABLE 1102.5 SUBSOIL DRAIN PIPE
| Material | Standard |
|---|---|
| Cast-iron pipe | ASTM A74; ASTM A888; CISPI 301 |
| Polyethylene (PE) plastic pipe | ASTM F667; CSA B182.1; CSA B182.6; CSA B182.8 |
| Polyvinyl chloride (PVC) plastic pipe (type sewer pipe, SDR35, PS25, PS50 or PS100) | ASTM D2729; ASTM D3034; ASTM F891; CSA B182.2; CSA B182.4 |
| Stainless steel drainage systems, Type 316L | ASME A112.3.1 |
| Vitrified clay pipe | ASTM C4; ASTM C700 |
Roof drains conform to ASME A112.3.1 or ASME A112.6.4; roof drains other than siphonic roof drains
are tested and rated in accordance with ASME A112.6.4 or ASPE/IAPMO Z1034 (IPC 2024, 1102.6).
Pipe fittings must be approved for installation with the piping material installed and must conform
to the respective pipe standards or to one of the standards listed in Table 1102.7. The fittings must
not have ledges, shoulders or reductions capable of retarding or obstructing the flow in the piping,
and threaded drainage pipe fittings must be of the recessed drainage type (IPC 2024, 1102.7).
TABLE 1102.7 PIPE FITTINGS
| Material | Standard |
|---|---|
| Acrylonitrile butadiene styrene (ABS) plastic | ASTM D2661; ASTM D3311; CSA B181.1 |
| Cast iron | ASME B16.4; ASME B16.12; ASTM A74; ASTM A888; CISPI 301 |
| Coextruded composite ABS and drain DR-PS in PS35, PS50, PS100, PS140, PS200 | ASTM D2751 |
| Coextruded composite ABS DWV Schedule 40 IPS pipe (solid or cellular core) | ASTM D2661; ASTM D3311; ASTM F628 |
| Coextruded composite PVC DWV Schedule 40 IPS-DR, PS140, PS200 (solid or cellular core) | ASTM D2665; ASTM D3311; ASTM F891 |
| Coextruded composite PVC sewer and drain DR-PS in PS35, PS50, PS100, PS140, PS200 | ASTM D3034 |
| Copper or copper alloy | ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.23; ASME B16.26; ASME B16.29 |
| Gray iron and ductile iron | AWWA C110/A21.10 |
| Malleable iron | ASME B16.3 |
| Plastic, general | ASTM F409 |
| Polyethylene (PE) plastic pipe | ASTM F667/F667M; ASTM F2306/F2306M; ASTM F2763; ASTM F2947/F2947M |
| Polypropylene (PP) plastic pipe | ASTM F2764; ASTM F2881/F2881M |
| Polyvinyl chloride (PVC) plastic | ASTM D2665; ASTM D3311; ASTM F1866; ASTM F3202 |
| Stainless steel drainage systems, Type 316L | ASME A112.3.1 |
| Steel | ASME B16.9; ASME B16.11; ASME B16.28 |
3. Traps
Leaders and storm drains that connect to a combined sewer must be trapped. The trap is installed
either individually, on the storm water drain branch serving each conductor, or as a single trap in
the main storm drain immediately before its connection with the combined building sewer or with the
public sewer. Leaders and storm drains that connect to a building storm sewer are not required to be
trapped (IPC 2024, 1103.1). A storm water trap must be of the same material as the piping system it
is attached to (IPC 2024, 1103.2), and the trap for an individual conductor must be the same size as
the horizontal drain it is connected to (IPC 2024, 1103.3). A cleanout is installed on the building
side of the trap and is provided with access (IPC 2024, 1103.4).
4. Conductors and connections
Conductor pipes must not be used as soil, waste or vent pipes, and soil, waste or vent pipes must not
be used as conductors (IPC 2024, 1104.1). Floor drains must not be connected to a storm drain
(IPC 2024, 1104.2).
5. Roof drains
Roof drains are installed in accordance with the manufacturer's instructions, and the inside opening
of the roof drain must not be obstructed by the roofing membrane material (IPC 2024, 1105.1). The
published flow rate of the roof drain, based on the head of water above the drain, is the figure used
to size the storm drainage system in accordance with Section 1106; the flow rate used for sizing the
storm drainage piping is based on the maximum anticipated ponding at the roof drain
(IPC 2024, 1105.2).
6. Size of conductors, leaders and storm drains
6.1 Design rainfall
The size of vertical conductors and leaders, of building storm drains and building storm sewers, and
of any horizontal branches of such drains or sewers, is based on the 100-year hourly rainfall rate of
the geographic area as mapped in the figures published with the section, or on other rainfall rates
determined from approved local weather data (IPC 2024, 1106.1).
6.2 Storm drain piping
Vertical and horizontal storm drain piping is sized on the flow rate through the roof drain. That
flow rate is calculated in accordance with Section 1106.2.1 and is then checked against the roof
drain manufacturer's published flow rate for the specific model and size of the drain selected, to
verify that the drain will handle the anticipated flow. The flow rate in storm drain piping must not
exceed the values printed in Table 1106.2 (IPC 2024, 1106.2).
TABLE 1106.2 STORM DRAIN PIPE SIZING
| Pipe size (inches) | Capacity (gpm), vertical drain | Capacity (gpm), horizontal drain at 1/16 inch per foot | at 1/8 inch per foot | at 1/4 inch per foot | at 1/2 inch per foot |
|---|---|---|---|---|---|
| 2 | 34 | 15 | 22 | 31 | 44 |
| 3 | 87 | 39 | 55 | 79 | 111 |
| 4 | 180 | 81 | 115 | 163 | 231 |
| 5 | 311 | 117 | 165 | 234 | 331 |
| 6 | 538 | 243 | 344 | 487 | 689 |
| 8 | 1,117 | 505 | 714 | 1,010 | 1,429 |
| 10 | 2,050 | 927 | 1,311 | 1,855 | 2,623 |
| 12 | 3,272 | 1,480 | 2,093 | 2,960 | 4,187 |
| 15 | 5,543 | 2,508 | 3,546 | 5,016 | 7,093 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m
(IPC 2024, Table 1106.2).
6.3 Rainfall rate converted to a flow rate
The rainfall rate falling on a roof surface is converted to a gallon-per-minute flow rate by
Equation 11-1: the flow rate equals the rainfall intensity in inches per hour, multiplied by the roof
area in square feet, multiplied by 0.0104 (IPC 2024, 1106.2.1).
6.4 Vertical leaders
Vertical leaders are sized on the flow rate delivered from horizontal gutters or on the maximum flow
rate through the roof drains. The flow rate through vertical leaders must not exceed the values of
Table 1106.3 (IPC 2024, 1106.3).
TABLE 1106.3 VERTICAL LEADER SIZING
| Size of leader (inches) | Capacity (gpm) |
|---|---|
| 2 | 30 |
| 2 × 2 | 30 |
| 1 1/2 × 2 1/2 | 30 |
| 2 1/2 | 54 |
| 2 1/2 × 2 1/2 | 54 |
| 3 | 92 |
| 2 × 4 | 92 |
| 2 1/2 × 3 | 92 |
| 4 | 192 |
| 3 × 4 1/4 | 192 |
| 3 1/2 × 4 | 192 |
| 5 | 360 |
| 4 × 5 | 360 |
| 4 1/2 × 4 1/2 | 360 |
| 6 | 563 |
| 5 × 6 | 563 |
| 5 1/2 × 5 1/2 | 563 |
| 8 | 1208 |
| 6 × 8 | 1208 |
For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m (IPC 2024, Table 1106.3).
6.5 Vertical walls
When roof drains and storm drainage piping are sized, one-half of the area of any vertical wall that
diverts rainwater onto the roof is added to the projected roof area, and that combined area is the
area used in calculating the required size of the vertical conductors, the leaders and the horizontal
storm drainage piping (IPC 2024, 1106.4).
6.6 Parapet wall scuppers
Where scuppers serve as primary roof drainage, as secondary (emergency overflow) roof drainage, or as
both, their quantity, size, location and inlet elevation are chosen so that the depth of ponding
water on the roof does not exceed the maximum water depth for which the roof was designed as
determined by the International Building Code. Scupper openings are not less than 4 inches (102 mm)
in height and have a width equal to or greater than the circumference of a roof drain sized for the
same roof area. The flow through the primary system is not counted when the secondary scuppers are
located and sized (IPC 2024, 1106.5).
6.7 Roof gutters
Horizontal gutters are sized on the flow rate from the roof surface, and the flow rate in horizontal
gutters must not exceed the values of Table 1106.6 (IPC 2024, 1106.6).
TABLE 1106.6 HORIZONTAL GUTTER SIZING
| Gutter dimensions (inches) | Slope (inch per foot) | Capacity (gpm) |
|---|---|---|
| 1 1/2 × 2 1/2 | 1/4 | 26 |
| 1 1/2 × 2 1/2 | 1/2 | 40 |
| 4 | 1/8 | 39 |
| 2 1/4 × 3 | 1/4 | 55 |
| 2 1/4 × 3 | 1/2 | 87 |
| 5 | 1/8 | 74 |
| 4 × 2 1/2 | 1/4 | 106 |
| 3 × 3 1/2 | 1/2 | 156 |
| 6 | 1/8 | 110 |
| 3 × 5 | 1/4 | 157 |
| 3 × 5 | 1/2 | 225 |
| 8 | 1/16 | 172 |
| 8 | 1/8 | 247 |
| 4 1/2 × 6 | 1/4 | 348 |
| 4 1/2 × 6 | 1/2 | 494 |
| 10 | 1/16 | 331 |
| 10 | 1/8 | 472 |
| 5 × 8 | 1/4 | 651 |
| 4 × 10 | 1/2 | 1055 |
Footnote a of the table: dimensions are width by depth for rectangular shapes, and a single dimension
is the diameter of a semicircle. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute =
3.785 L/m, 1 inch per foot = 83.3 mm/m (IPC 2024, Table 1106.6).
7. Siphonic roof drainage systems
Siphonic roof drains and siphonic drainage systems are designed in accordance with ASME A112.6.9 and
ASPE 45 (IPC 2024, 1107.1).
8. Secondary (emergency) roof drains
Where roof drains are required, secondary (emergency overflow) roof drains or scuppers are provided
where the roof perimeter construction extends above the roof in a manner that would entrap water if
the primary drains allow a buildup of water for any reason. Where primary and secondary roof drains
are manufactured as a single assembly, the inlet and the outlet of each drain are independent
(IPC 2024, 1108.1).
The secondary roof drain system discharges at an end point separate from the primary system, above
grade, at a location normally observed by the building occupants or by maintenance personnel
(IPC 2024, 1108.2).
Secondary (emergency) roof drain systems are sized in accordance with Section 1106, on the rainfall
rate for which the primary system is sized. Scuppers are sized so that the depth of ponding water does
not exceed the depth for which the roof was designed as determined by Section 1101.7; a scupper has
an opening dimension of not less than 4 inches (102 mm) in height, and an opening width equal to the
circumference of the roof drain required for the area served. The flow through the primary system is
not counted when the secondary roof drain system is sized (IPC 2024, 1108.3).
The section on secondary roof drains carries no sizing table of its own in the print read for this
document; the sizing of secondary drains is by reference to Section 1106 (IPC 2024, 1108.3), and the
only sizing tables printed in Chapter 11 are Table 1106.2, Table 1106.3 and Table 1106.6
(IPC 2024, Table 1106.2, Table 1106.3, Table 1106.6).
9. Combined sanitary and storm public sewer
Where the public sewer is a combined system serving both sanitary sewage and storm water, the storm
sewer is connected independently to that public sewer (IPC 2024, 1109.1).
10. Controlled flow roof drain systems
Where the storm drainage system is engineered for controlled flow, the roof of the structure is
designed for the storage of water. The controlled flow roof drain system is an engineered system
under this section and under the design, submittal, approval, inspection and testing requirements of
Section 316.1, and it is designed on the required rainfall rate of Section 1106.1 (IPC 2024, 1110.1).
The control devices are installed so that the discharge rate of water per minute does not exceed the
values for continuous flow indicated in Section 1110.1 (IPC 2024, 1110.2). Runoff control is by those
control devices, and the control devices are protected by strainers (IPC 2024, 1110.3). The minimum
number of roof drains in such a roof is fixed: not fewer than two roof drains in roof areas of
10,000 square feet (929 m²) or less, and not fewer than four roof drains in roofs of more than
10,000 square feet (929 m²) (IPC 2024, 1110.4).
11. Subsoil drains
Subsoil drains are open-jointed, horizontally split or perforated pipe conforming to one of the
standards listed in Table 1102.5, and they are not less than 4 inches (102 mm) in diameter. Where the
building is subject to backwater, the subsoil drain is protected by a backwater valve located with
access. Subsoil drains discharge to a trapped area drain, to a sump, to a dry well or to an approved
location above ground. A subsoil sump is not required to have a gastight cover or a vent, and the sump
and the pumping system comply with Section 1113.1 (IPC 2024, 1111.1).
12. Building subdrains
Building subdrains located below the level of the public sewer discharge into a sump or a receiving
tank whose contents are lifted automatically and discharged into the drainage system as required for
building sumps; the sump and the pumping equipment comply with Section 1113.1 (IPC 2024, 1112.1).
13. Sumps and pumping systems
The sump pump, the pit and the discharge piping conform to Sections 1113.1.1 through 1113.1.4
(IPC 2024, 1113.1).
The sump pump is of a capacity and a head appropriate to the anticipated use requirements
(IPC 2024, 1113.1.1). The sump pit is not less than 18 inches (457 mm) in diameter and not less than
24 inches (610 mm) in depth, unless otherwise approved; it is provided with access and is located so
that all drainage flows into the pit by gravity. The pit is constructed of tile, steel, plastic, cast
iron, concrete or another approved material, with a removable cover adequate to support the
anticipated loads in the area of use, and the pit floor is solid and provides permanent support for
the pump (IPC 2024, 1113.1.2). Electrical service outlets, where they are required, meet the
requirements of NFPA 70 (IPC 2024, 1113.1.3).
The discharge piping meets the requirements of Section 1102.2, 1102.3 or 1102.4 and includes a gate
valve and a full flow check valve; the pipe and the fittings are the same size as, or larger than,
the pump discharge tapping (IPC 2024, 1113.1.4). The exception printed with that rule: in one- and
two-family dwellings only a check valve is required, located on the discharge piping from the pump or
the ejector (IPC 2024, 1113.1.4 and Exception).
14. Where the rules of the chapter meet the other chapters
Storm drainage borrows from the rest of the code by printed reference, and those references fix what
the storm installer shares with the sanitary installer: the tests of Section 312 (IPC 2024, 1101.4),
the drainage-type fittings and changes of direction of Table 706.3 (IPC 2024, 1101.6), the pipe
cleanout provisions of Chapter 7 through Section 1101.8 (IPC 2024, 1101.8), the backwater valves of
Section 714 (IPC 2024, 1101.9), the materials of Chapter 7 through Section 1102.1 (IPC 2024, 1102.1),
and the above-ground conductor materials of Table 702.1 and the underground building drain materials
of Table 702.2 (IPC 2024, 1102.2 and 1102.3). The combination of storm and sanitary flow in one
building drain does not merge the two systems: each is connected independently to a combined public
sewer (IPC 2024, 703.6 and 1109.1).
Cleanouts
Reference text for the cleanouts area. Every rule below is written from the printed line of the 2024
International Plumbing Code (IPC 2024) that carries it, and each rule names the section it comes
from. Where the printed line does not state a value, no value is stated here. The subject of this
text is Section 708 in full: where a cleanout is required, how far apart cleanouts may be, how big
they are, what they are made of, where they must not be installed, and how much room a person has to
work in front of the opening.
1. The duty, and where it sits in the chapter
Cleanouts must be provided for drainage piping as Sections 708.1.1 through 708.1.12 direct (IPC 2024,
708.1). A cleanout is therefore not an optional convenience added when a drain is hard to reach: it
is a required element of the drainage system, sized, spaced, located and left accessible according to
the rules that follow. Chapter 7 as a whole governs the materials, design, construction and
installation of sanitary drainage systems (IPC 2024, 701.1), and the cleanout rules sit inside that
chapter because access for cleaning is part of how the system is designed, not something added
afterwards.
The sections divide the work along the parts of the system: the horizontal drain inside the building,
the building drain, the building sewer, the junction between the last two, the changes of direction
in each of them, and the cleanout itself as a piece of hardware.
2. Horizontal drains and building drains
Horizontal drainage pipes in buildings must have cleanouts located at intervals of not more than 100
feet (30 480 mm). Building drains must have cleanouts at intervals of not more than 100 feet
(30 480 mm) as well, except that where manholes are used instead of cleanouts the manholes are
located at intervals of not more than 400 feet (122 m) (IPC 2024, 708.1.1).
The measuring rule is part of the same provision and is what a layout is checked against: the
interval length is measured from the cleanout or manhole opening, along the developed length of the
piping, to the next drainage fitting that provides access for cleaning, to the end of the horizontal
drain, or to the end of the building drain (IPC 2024, 708.1.1). Developed length — not the straight
line across the plan — is what counts, so the total of the run a cable or a snake has to travel
between two access points is the number being held to 100 feet.
One exception narrows the requirement: horizontal fixture drain piping serving a nonremovable trap
does not need a cleanout for the section of piping between the trap and the vent connection for that
trap (IPC 2024, 708.1.1). The exception is drawn around the trap-to-vent piece only; it does not
excuse the drain from cleanouts elsewhere along its run.
3. Building sewers
The building sewer is treated according to its size. A building sewer smaller than 8 inches (203 mm)
must have cleanouts located at intervals of not more than 100 feet (30 480 mm). A building sewer
8 inches (203 mm) and larger must have a manhole located not more than 200 feet (60 960 mm) from the
junction of the building drain and the building sewer, and manholes at intervals of not more than
400 feet (122 m) (IPC 2024, 708.1.2).
The interval is again measured along the developed length of the piping, from the cleanout or manhole
opening to the next drainage fitting providing access for cleaning, to a manhole, or to the end of the
building sewer (IPC 2024, 708.1.2). The change from cleanouts to manholes at 8 inches and larger is a
size threshold, and it moves the interval from 100 feet to 400 feet at the same time.
4. The junction of the building drain and the building sewer
The junction of the building drain and the building sewer must be served by a cleanout located at the
junction, or within 10 feet (3048 mm) of the developed length of piping upstream of the junction
(IPC 2024, 708.1.3). Upstream is where the cleanout sits if it is not right at the junction: the
access is placed on the building drain side, within 10 feet of developed length of the point where the
two pipes meet.
The same provision settles a practical conflict that shows up on remodels: for the purpose of this
section, the removal of the water closet is not required in order to provide cleanout access
(IPC 2024, 708.1.3). A layout that would only reach the junction through a pull-out fixture is not
the layout the section asks for.
5. Changes of direction
Where a horizontal drainage pipe, a building drain or a building sewer changes horizontal direction
by more than 45 degrees (0.79 rad), a cleanout must be installed at the change of direction. Where
more than one change of horizontal direction greater than 45 degrees occurs within 40 feet (12 192 mm)
of developed length of piping, the cleanout installed for the first change of direction serves as the
cleanout for all the changes in direction within that 40 feet of developed length (IPC 2024, 708.1.4).
The rule has an angle threshold and a distance threshold, and both have to be read before a cleanout
can be dropped. Offsets under the threshold do not call for a cleanout at all; offsets over it do,
unless the changes are close enough together in developed length that one cleanout covers the group.
6. Size of the cleanout
A cleanout must be the same size as the piping it serves, except that cleanouts for piping larger than
4 inches (102 mm) need not be larger than 4 inches (102 mm) (IPC 2024, 708.1.5). The size of the
opening is thus tied to the pipe below the threshold, and capped at 4 inches above it.
Three exceptions complete the sizing rule (IPC 2024, 708.1.5):
that is one size larger than the P-trap size.
fittings as indicated in Table 702.4.
7. A trap as a cleanout: the cleanout equivalent
A fixture trap, or a fixture with an integral trap, that can be removed without altering concealed
piping is acceptable as a cleanout equivalent (IPC 2024, 708.1.6). The condition in the sentence is
the whole content of the rule: removable, and removable without disturbing concealed piping. A trap
that can only be reached by opening a finished surface is not that.
8. Plugs, heads and trim covers
Cleanout plugs must be of copper-alloy, plastic or other approved materials, and cleanout plugs for
borosilicate glass piping systems must be of borosilicate glass. Copper-alloy cleanout plugs must
conform to ASTM A74 and are limited to use on metallic piping systems, while plastic cleanout plugs
must conform to the referenced standards for plastic pipe fittings as indicated in Table 702.4
(IPC 2024, 708.1.7).
The head of the plug must be one of three forms: a raised square head, a countersunk square head or a
countersunk slot head. Where a cleanout plug will have a trim cover screw installed into it, the plug
must be manufactured with a blind end threaded hole for that purpose (IPC 2024, 708.1.7).
Trim covers and access doors for cleanout plugs must be designed for that purpose and be approved, and
the fasteners that thread into the cleanout plugs must be corrosion resistant. A cleanout plug may not
be covered with mortar, plaster or any other permanent material (IPC 2024, 708.1.11.1). The plug is
meant to be opened later; a wall finish that seals it permanently is prohibited for that reason.
9. Manholes
Manholes and manhole covers must be of an approved type, and manholes located inside a building must
have gas-tight covers that require tools for removal (IPC 2024, 708.1.8). The interior manhole is
therefore closed against sewer gas and is not openable by hand.
10. Arrangement and clearance
Cleanouts must be arranged so that cleaning can only take place in the direction of drainage flow
(IPC 2024, 708.1.9). Two arrangements are excepted from that limitation: test tees serving as
cleanouts, and a two-way cleanout installation approved for meeting the requirement that the junction
of building drain and building sewer be served by a cleanout (IPC 2024, 708.1.9).
Clearance in front of the opening is measured as a fixed distance, perpendicular to the face of the
opening, to any obstruction: cleanouts for 6-inch (153 mm) and smaller piping must have a clearance of
not less than 18 inches (457 mm), and cleanouts for 8-inch (203 mm) and larger piping a clearance of
not less than 36 inches (914 mm) (IPC 2024, 708.1.10). Both numbers are measured from, and
perpendicular to, the face of the opening — the working room belongs to the face of the cleanout, not
to the room in general in which the cleanout happens to sit.
11. Access
Required cleanouts may not be installed in concealed locations. For this section, concealed locations
include, but are not limited to, the inside of plenums, within walls, within floor/ceiling
assemblies, below grade, and in crawl spaces where the height from the crawl space floor to the
nearest obstruction along the path from the crawl space opening to the cleanout location is less than
24 inches (610 mm) (IPC 2024, 708.1.11).
Where the cleanout opens at a finished wall, the face of the opening must be located within 1 1/2
inches (38 mm) of the finished wall surface. Where the cleanout is located below grade, it must be
extended to grade level so that the top of the cleanout plug is at or above grade. Where a cleanout is
installed in a floor or walkway that will not have a trim cover installed, it must have a countersunk
plug installed so that the top surface of the plug is flush with the finished surface of the floor or
walkway (IPC 2024, 708.1.11).
A cleanout plug that would be exposed to the loads of vehicular traffic is protected by installing a
cleanout assembly in accordance with ASME A112.36.2M (IPC 2024, 708.1.11.2).
12. Prohibited use
A threaded cleanout opening may not be used to add a fixture or to extend piping, except where another
cleanout of equal size is installed with the required access and clearance (IPC 2024, 708.1.12). The
opening that exists to let a drain be cleaned may only be converted into a connection if the drain
keeps an equivalent cleanout, installed with the access and the clearance the section requires.
13. The numbers of the area, as printed
| Rule | What it fixes |
|---|---|
| Horizontal drains and building drains | Cleanouts at intervals of not more than 100 feet; manholes instead of cleanouts at intervals of not more than 400 feet (IPC 2024, 708.1.1) |
| Building sewers smaller than 8 inches | Cleanouts at intervals of not more than 100 feet (IPC 2024, 708.1.2) |
| Building sewers 8 inches and larger | Manhole not more than 200 feet from the junction of building drain and building sewer, and manholes at intervals of not more than 400 feet (IPC 2024, 708.1.2) |
| Building drain and building sewer junction | Cleanout at the junction or within 10 feet of developed length upstream (IPC 2024, 708.1.3) |
| Changes of horizontal direction over 45 degrees | Cleanout at the change; one cleanout serves all such changes within 40 feet of developed length (IPC 2024, 708.1.4) |
| Cleanout size | Same size as the piping served; need not be larger than 4 inches for piping larger than 4 inches (IPC 2024, 708.1.5) |
| Required clearance | 18 inches for piping 6 inches and smaller; 36 inches for piping 8 inches and larger (IPC 2024, 708.1.10) |
| Face at a finished wall | Within 1 1/2 inches of the finished wall surface (IPC 2024, 708.1.11) |
| Crawl space access | Height from crawl space floor to nearest obstruction along the path from the opening to the cleanout not less than 24 inches (IPC 2024, 708.1.11) |
14. Reading a layout against the section
The provisions are easier to apply in sequence than all at once, because each one answers a different
question about the same run:
choice between cleanout and manhole follow from that answer (IPC 2024, 708.1.1 and 708.1.2).
length upstream of that junction (IPC 2024, 708.1.3)?
within 40 feet of developed length, which single cleanout covers the group (IPC 2024, 708.1.4)?
or a shallow crawl space; at the finished wall face; extended to grade where it was built below
grade; flush where it sits in a floor or walkway (IPC 2024, 708.1.11)?
and head form, manhole gas-tight where it is inside a building (IPC 2024, 708.1.5, 708.1.7 and
708.1.8)?
piping without an equal cleanout taking its place (IPC 2024, 708.1.12)?
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free