Chapter V

Drains and Sewers

Content area 5 of the Oklahoma master plumber exam.

Sanitary Drainage Systems

Reference text for the sanitary drainage area. Every rule below is written from the printed line of

the 2024 International Plumbing Code (IPC 2024) that carries it, and each rule names the section it

comes from. Where the printed line does not state a value, no value is stated here.

1. General

The chapter governs the materials, design, construction and installation of sanitary drainage systems

(IPC 2024, 701.1). Sanitary drainage piping from plumbing fixtures in buildings, and sanitary drainage

piping systems from premises, must be connected to a public sewer; where a public sewer is not

available they must be connected to a private sewage disposal system in compliance with state or local

requirements, and, where such requirements do not exist, to an approved private sewage disposal system

in accordance with the International Private Sewage Disposal Code (IPC 2024, 701.2). The exception

covers piping and systems that convey only the discharge from bathtubs, showers, lavatories, clothes

washers and laundry trays, provided they are connected to a system in accordance with Chapter 13 or 14

(IPC 2024, 701.2, Exception).

A building having plumbing fixtures installed and intended for human habitation, occupancy or use on

premises abutting on a street, alley or easement in which there is a public sewer must have a separate

connection with the sewer; where located on the same lot, multiple buildings may connect to a common

building sewer that connects to the public sewer (IPC 2024, 701.3). Sewage or other waste deleterious

to surface or subsurface waters must not be discharged into the ground or into any waterway unless

first rendered innocuous through an approved form of treatment (IPC 2024, 701.4), and waste

detrimental to the public sewer system or to the functioning of the sewage-treatment plant must be

treated and disposed of in accordance with Section 1003 as directed by the code official (IPC 2024,

701.5). The sanitary drainage system is tested in accordance with Section 312 (IPC 2024, 701.6), and

engineered sanitary drainage systems must conform to Sections 316 and 713 (IPC 2024, 701.7).

2. Materials and joints

Sections 702.1 (above-ground sanitary drainage and vent pipe), 702.2 (underground building sanitary

drainage and vent pipe), 702.3 (building sewer pipe) and 702.4 (fittings) publish the materials and

the standards for those applications. Where the wastewater temperature will be greater than 140°F

(60°C), the sanitary drainage piping material must be rated for the highest temperature of the

wastewater (IPC 2024, 702.5). Section 702.6 governs chemical waste systems and Section 702.7 lead

bends and traps.

Section 705 contains the provisions applicable to joints specific to sanitary drainage piping

(IPC 2024, 705.1): 705.2 ABS plastic, 705.3 cast iron, 705.4 concrete joints, 705.5 copper pipe,

705.6 copper tubing, 705.7 borosilicate glass joints, 705.8 steel, 705.9 lead, 705.10 PVC plastic,

705.11 vitrified clay, 705.12 polyethylene plastic pipe, 705.13 polyolefin plastic, 705.14

polyvinylidene fluoride plastic, 705.15 polypropylene plastic, 705.16 joints between different

materials, 705.17 drainage slip joints, 705.18 caulking ferrules, 705.19 soldering bushings and

705.20 stainless steel drainage systems. Prohibited joints and connections in

drainage piping are: cement or concrete joints; mastic or hot-pour bituminous joints; joints made

with fittings not approved for the specific installation; joints between different diameter pipes made

with elastomeric rolling O-rings; solvent-cement joints between different types of plastic pipe except

where provided for in Section 705.16.4; and saddle-type fittings (IPC 2024, 707.1).

3. Building sewer

The proximity of a sewer to a water service must comply with Section 603.2 (IPC 2024, 703.1). Where a

building sewer or building drain is installed on filled or unstable ground, the drainage pipe must

conform to one of the standards for ABS plastic pipe, cast-iron pipe, copper or copper-alloy tubing,

PVC plastic pipe or polypropylene plastic pipe indicated in Table 702.3 (IPC 2024, 703.2). Where

separate systems of sanitary drainage and storm drainage are installed in the same property, the

sanitary and storm building sewers or drains may be laid side by side in one trench (IPC 2024, 703.3).

Where the entire sanitary drainage system of an existing building is replaced, existing building

drains under concrete slabs and existing building sewers that will serve the new system must be

internally examined to verify that the piping is sloping in the correct direction, is not broken, is

not obstructed and is sized for the drainage load of the new plumbing drainage system to be installed

(IPC 2024, 703.4). Cleanouts on building sewers are located as indicated in Section 708 (IPC 2024,

703.5), and where the public sewer is a combined system for both sanitary and storm water the sanitary

sewer must be connected independently to the public sewer (IPC 2024, 703.6).

4. Drainage piping installation

4.1 Slope

Horizontal drainage piping must be installed in uniform alignment at uniform slopes. The slope must be

not less than Table 704.1 shows, except that where the drainage piping is upstream of a grease

interceptor the slope must be not less than 1/4 inch per foot (2 percent slope) (IPC 2024, 704.1).

Size (inches)Minimum slope (inch per foot)
2 1/2 or less1/4
3 to 61/8
8 or larger1/16

For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.33 mm/m. Slopes for piping draining to a grease

interceptor comply with Section 704.1 (IPC 2024, Table 704.1, footnote a).

4.2 Size reduction, offsets and future fixtures

The size of the drainage piping must not be reduced in the direction of flow. The following are not

considered a reduction in size in the direction of flow: a 4-inch by 3-inch (102 mm by 76 mm) water

closet flange; a water closet bend fitting having a 4-inch (102 mm) inlet and a 3-inch (76 mm) outlet,

provided the 4-inch leg of the fitting is upright and below, but not necessarily directly connected

to, the water closet flange; and an offset closet flange (IPC 2024, 704.2).

Horizontal branches must connect to the bases of stacks at a point located not less than 10 times the

diameter of the drainage stack downstream from the stack, and must connect to horizontal stack offsets

at a point located not less than 10 times the diameter of the drainage stack downstream from the

upper stack (IPC 2024, 704.3). Drainage piping for future fixtures must terminate with an approved cap

or plug (IPC 2024, 704.4).

5. Connections and fittings

Connections and changes in direction of the sanitary drainage system must be made with approved

drainage fittings; connections between drainage piping and fixtures conform to Section 405 (IPC 2024,

706.1). Fittings must not have ledges, shoulders or reductions capable of retarding or obstructing

flow in the piping, and threaded drainage pipe fittings must be of the recessed drainage type; the

section does not apply to tubular waste fittings used to convey vertical flow upstream of the trap

seal liquid level of a fixture trap (IPC 2024, 706.2).

Fittings must be installed to guide sewage and waste in the direction of flow, and changes in

direction must be made by fittings installed in accordance with Table 706.3. Change in direction by

combination fittings, side inlets or increasers must be installed in accordance with Table 706.3 based

on the pattern of flow created by the fitting. Double sanitary tee patterns must not receive the

discharge of back-to-back water closets and fixtures or appliances with pumping action discharge;

back-to-back water closet connections to double sanitary tees are permitted where the horizontal

developed length between the outlet of the water closet and the connection to the double sanitary tee

pattern is 18 inches (457 mm) or greater (IPC 2024, 706.3 and Exception).

Table 706.3 — fittings for change in direction ("X" = permitted):

Type of fitting patternHorizontal to verticalVertical to horizontalHorizontal to horizontal
Sixteenth bendXXX
Eighth bendXXX
Sixth bendXXX
Quarter bendXXᵃXᵃ
Short sweepXXᵃ,ᵇXᵃ
Long sweepXXX
Sanitary teeXᶜ——
WyeXXX
Combination wye and eighth bendXXX

Fitting limitations, as the printed table carries them on the marked cells (IPC 2024,

Table 706.3, footnotes a, b and c): the fittings marked a are only permitted for a 2-inch or smaller

fixture drain; the cell marked b carries "three inches or larger"; and the double sanitary tee

limitation is Section 706.3.

Heel-inlet quarter bends are an acceptable means of connection except where the quarter bend serves a

water closet; a low-heel inlet must not be used as a wet-vented connection; side-inlet quarter bends

are an acceptable means of connection for drainage, wet venting and stack venting arrangements

(IPC 2024, 706.4).

6. Cleanouts

Cleanouts must be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.12

(IPC 2024, 708.1). The principal requirements:

Horizontal drainage pipes in buildings must have cleanouts located at intervals of not more than

100 feet (30 480 mm), and building drains must have cleanouts at intervals of not more than 100 feet

(30 480 mm) except where manholes are used instead of cleanouts, in which case the manholes must be

located at intervals of not more than 400 feet (122 m); the interval is measured from the cleanout

or manhole opening, along the developed length of the piping, to the next drainage fitting providing

access for cleaning, the end of the horizontal drain or the end of the building drain (IPC 2024,

708.1.1).

Building sewers smaller than 8 inches (203 mm) must have cleanouts at intervals of not more than

100 feet (30 480 mm); building sewers 8 inches (203 mm) and larger must have a manhole located not

more than 200 feet (60 960 mm) from the junction of the building drain and building sewer and at

intervals of not more than 400 feet (122 m) (IPC 2024, 708.1.2).

The junction of the building drain and the building sewer must be served by a cleanout located at

the junction or within 10 feet (3048 mm) of the developed length of piping upstream of the

junction; removal of the water closet must not be required to provide cleanout access (IPC 2024,

708.1.3).

Where a horizontal drainage pipe, a building drain or a building sewer has a change of horizontal

direction greater than 45 degrees, a cleanout must be installed at the change of direction; where

more than one such change occurs within 40 feet (12 192 mm) of developed length, the cleanout

installed for the first change serves all changes in direction within that 40 feet (IPC 2024,

708.1.4).

Cleanouts must be the same size as the piping served, except that cleanouts for piping larger than

4 inches (102 mm) need not be larger than 4 inches (102 mm); a removable P-trap with slip or ground

joint connections can serve as a cleanout for drain piping one size larger than the P-trap size;

cleanouts located on stacks can be one size smaller than the stack size; and the size of cleanouts

for cast-iron piping can be in accordance with the referenced standards for cast-iron fittings in

Table 702.4 (IPC 2024, 708.1.5 and Exceptions).

A fixture trap, or a fixture with integral trap, removable without altering concealed piping, is

acceptable as a cleanout equivalent (IPC 2024, 708.1.6). Cleanout plugs must be of copper-alloy,

plastic or other approved materials (borosilicate glass for borosilicate glass piping systems),

copper-alloy plugs conforming to ASTM A74 and limited to metallic piping systems, plastic plugs

conforming to the referenced standards for plastic pipe fittings in Table 702.4, with a raised

square head, a countersunk square head or a countersunk slot head, and manufactured with a blind

end threaded hole where a trim cover screw will be installed (IPC 2024, 708.1.7).

Manholes and manhole covers must be of an approved type, and manholes located inside a building

must have gas-tight covers that require tools for removal (IPC 2024, 708.1.8). The installation

arrangement of a cleanout must enable cleaning of drainage piping only in the direction of drainage

flow, except for test tees serving as cleanouts and a two-way cleanout installation approved for

meeting Section 708.1.3 (IPC 2024, 708.1.9).

Required clearance: cleanouts for 6-inch (153 mm) and smaller piping must have a clearance of not

less than 18 inches (457 mm) from, and perpendicular to, the face of the opening to any

obstruction; cleanouts for 8-inch (203 mm) and larger piping must have a clearance of not less than

36 inches (914 mm) (IPC 2024, 708.1.10).

Required cleanouts must not be installed in concealed locations; concealed locations include the

inside of plenums, within walls, within floor/ceiling assemblies, below grade and in crawl spaces

where the height from the crawl space floor to the nearest obstruction along the path from the

crawl space opening to the cleanout is less than 24 inches (610 mm). Cleanouts with openings at a

finished wall must have the face of the opening within 1 1/2 inches (38 mm) of the finished wall

surface; cleanouts located below grade must be extended to grade level so that the top of the

cleanout plug is at or above grade; and a cleanout installed in a floor or walkway without a trim

cover must have a countersunk plug installed so the top surface of the plug is flush with the

finished surface of the floor or walkway (IPC 2024, 708.1.11).

Trim covers and access doors for cleanout plugs must be designed for such purposes and approved;

trim cover fasteners that thread into cleanout plugs must be corrosion resistant, and cleanout plugs

must not be covered with mortar, plaster or any other permanent material (IPC 2024, 708.1.11.1).

Cleanout assemblies in accordance with ASME A112.36.2M must be installed where it is necessary to

protect a cleanout plug from the loads of vehicular traffic (IPC 2024, 708.1.11.2).

The use of a threaded cleanout opening to add a fixture or to extend piping is prohibited except

where another cleanout of equal size is installed with the required access and clearance (IPC 2024,

708.1.12).

7. Fixture units

Drainage fixture unit values in Table 709.1 designate the relative load weight of different kinds of

fixtures, to be used in estimating the total load carried by a soil or waste pipe and in connection

with Tables 710.1(1) and 710.1(2) (IPC 2024, 709.1).

Fixture typeDrainage fixture unit valueMinimum size of trap (inches)
Automatic clothes washers, commercial32
Automatic clothes washers, residential22
Bathroom group as defined in Section 202 (1.6 gpf water closet)5—
Bathroom group as defined in Section 202 (water closet flushing greater than 1.6 gpf)6—
Bathtub (with or without overhead shower or whirlpool attachments)21 1/2
Bidet11 1/4
Combination sink and tray21 1/2
Dental lavatory11 1/4
Dental unit or cuspidor11 1/4
Dishwashing machine, domestic21 1/2
Drinking fountain1/21 1/4
Emergency floor drain02
Floor drains22
Floor sinksNote h2
Kitchen sink, domestic21 1/2
Kitchen sink, domestic with food waste disposer, dishwasher or both21 1/2
Laundry tray (1 or 2 compartments)21 1/2
Lavatory11 1/4
Service sink21 1/2
Sink21 1/2
Urinal4Note d
Urinal, 1 gallon per flush or less2Note d
Urinal, nonwater supplied1/2Note d
Wash sink (circular or multiple), each set of faucets21 1/2
Water closet, flushometer tank, public or private4Note d
Water closet, private (1.6 gpf)3Note d
Water closet, private (flushing greater than 1.6 gpf)4Note d
Water closet, public (1.6 gpf)4Note d
Water closet, public (flushing greater than 1.6 gpf)6Note d

Table notes that carry rules: a showerhead over a bathtub or whirlpool bathtub attachment does not

increase the drainage fixture unit value (footnote b); trap size must be consistent with the fixture

outlet size (footnote d); and for traps larger than 3 inches, Table 709.2 is used (footnote a).

Showers are rated on the total flow rate through showerheads and body sprays: 5.7 gpm or less = 2 dfu

with a 1 1/2-inch trap; greater than 5.7 gpm to 12.3 gpm = 3 dfu with a 2-inch trap; greater than

12.3 gpm to 25.8 gpm = 5 dfu with a 3-inch trap; greater than 25.8 gpm to 55.6 gpm = 6 dfu with a

4-inch trap (IPC 2024, Table 709.1).

Where discharges to a waste receptor or to a drainage system are known only in gallons per minute, the

drainage fixture unit values for those flows are computed on the basis that 1 gpm (0.06 L/s) of flow

is equivalent to two drainage fixture units (IPC 2024, 709.3). The drainage fixture unit load of an

indirect waste receptor receiving the discharge of indirectly connected fixtures is the sum of the

drainage fixture unit values of the fixtures that discharge to the receptor, but not less than the

value given for the indirect waste receptor in Table 709.1 or 709.2 (IPC 2024, 709.4). Waste receptors

such as floor drains, floor sinks and hub drains that receive only clear-water waste from display

cases, refrigerated display cases, ice bins, coolers and freezers have a drainage fixture unit value

of one-half (IPC 2024, 709.4.1).

8. Drainage system sizing

The maximum number of drainage fixture units connected to a given size of building sewer, building

drain or horizontal branch of the building drain is determined using Table 710.1(1), and the maximum

number connected to a given size of horizontal branch or vertical soil or waste stack is determined

using Table 710.1(2) (IPC 2024, 710.1).

Table 710.1(1) — building drains and sewers:

Diameter of pipe (inches)1/16 inch slope1/8 inch slope1/4 inch slope1/2 inch slope
1 1/4——11
1 1/2——33
2——2126
2 1/2——2431
3—364250
4—180216250
5—390480575
6—7008401,000
81,4001,6001,9202,300
102,5002,9003,5004,200
123,9004,6005,6006,700
157,0008,30010,00012,000

The minimum size of any building drain serving a water closet is 3 inches (IPC 2024,

Table 710.1(1), footnote a).

9. Offsets in drainage piping in buildings of five stories or more

If a horizontal branch connects to the stack within 2 feet (610 mm) above or below a vertical stack

offset, and the offset is located more than four branch intervals below the top of the stack, the

offset must be vented in accordance with Section 907; those vents are not required where the stack and

its offset are sized as a building drain (IPC 2024, 711.1 and 711.1.1).

A stack with a horizontal offset located more than four branch intervals below the top of the stack

must be vented in accordance with Section 907 and sized as follows: the portion of the stack above

the offset is sized as for a vertical stack based on the total number of drainage fixture units above

the offset; the offset is sized in accordance with Section 710.1.1; and the portion of the stack below

the offset is sized as for the offset or based on the total number of drainage fixture units on the

entire stack, whichever is larger (IPC 2024, 711.2). Those vents are not required where the stack and

its offset are one pipe size larger than required for a building drain and the entire stack and offset

are not less in cross-sectional area than that required for a straight stack plus the area of an

offset vent as provided in Section 907 (IPC 2024, 711.2.1).

Where a vertical offset occurs in a soil or waste stack below the lowest horizontal branch, a change

in diameter of the stack because of the offset is not required; if a horizontal offset occurs below

the lowest horizontal branch, the required diameter of the offset and of the stack below it must be

determined as for a building drain in accordance with Table 710.1(1) (IPC 2024, 711.3).

10. Sumps and ejectors

Building subdrains that cannot be discharged to the sewer by gravity flow must be discharged into a

tightly covered and vented sump from which the liquid is lifted and discharged into the building

gravity drainage system by automatic pumping equipment or other approved method; in other than

existing structures, the sump must not receive drainage from any piping within the building capable of

being discharged by gravity to the building sewer (IPC 2024, 712.1). A check valve and a full-open

valve located on the discharge side of the check valve must be installed in the pump or ejector

discharge piping between the pump or ejector and the gravity drainage system, with access to such

valves; they must be located above the sump cover required by Section 712.1 or, where the discharge

pipe from the ejector is below grade, accessibly outside the sump below grade in an access pit with a

removable access cover (IPC 2024, 712.2).

The sump pit must be not less than 18 inches (457 mm) in diameter and not less than 24 inches (610 mm)

in depth unless otherwise approved, provided with access, located so that all drainage flows into the

pit by gravity, constructed of tile, concrete, steel, plastic or other approved materials, with a

solid bottom providing permanent support for the pump, and fitted with a gastight removable cover

installed not more than 2 inches (51 mm) below grade or floor level, adequate to support anticipated

loads; the sump pit is vented in accordance with Chapter 9 (IPC 2024, 712.3.2). The effluent level

control must be adjusted and maintained to at all times prevent the effluent in the sump from rising

to within 2 inches (51 mm) of the invert of the gravity drain inlet into the sump (IPC 2024, 712.3.4).

Discharge pipe and fittings must be constructed of copper or copper-alloy, CPVC, ductile iron, PE or

PVC, rated for the maximum system operating pressure and temperature, compatible with the pipe

material, and suitable for burial where buried in the earth (IPC 2024, 712.3.3.1 and 712.3.3.2).

Pumps connected to the drainage system must connect to a building sewer, building drain, soil stack,

waste stack or horizontal branch drain; where the discharge line connects into horizontal drainage

piping, the connection must be made through a wye fitting into the top of the drainage piping, and

that wye fitting must be located not less than 10 pipe diameters from the base of any soil stack,

waste stack or fixture drain (IPC 2024, 712.3.5).

A sewage pump or sewage ejector must automatically discharge the contents of the sump to the building

drainage system (IPC 2024, 712.4). Macerating toilet systems must comply with ASME A112.3.4/CSA B45.9

and be installed in accordance with the manufacturer's instructions (IPC 2024, 712.4.1). A sewage pump

or ejector must have the capacity and head for the application requirements: pumps or ejectors that

receive the discharge of water closets must be capable of handling spherical solids with a diameter of

up to and including 2 inches (51 mm), and other pumps or ejectors must be capable of handling

spherical solids up to and including 1/2 inch (13 mm). Capacity based on the diameter of the discharge

pipe must be not less than Table 712.4.2 shows; grinder pumps or grinder ejectors that receive the

discharge of water closets must have a discharge opening of not less than 1 1/4 inches (32 mm), and

macerating toilet assemblies that serve single water closets must have a discharge opening of not less

than 3/4 inch (19.1 mm) (IPC 2024, 712.4.2 and Exceptions).

Diameter of the discharge pipe (inches)Capacity of pump or ejector (gpm)
221
2 1/230
346

11. Computerized drainage design, backwater valves and rehabilitation

The sizing, design and layout of the drainage system may be designed by approved computer design

methods; the load is computed from the simultaneous or sequential discharge conditions from fixtures,

appurtenances and appliances or the peak usage design condition; discharge profiles for flow rates

versus time follow the manufacturer's specifications; pipe must be sized to prevent full-bore flow;

pipe size calculations use the pipe wall roughness factor (ks) per the manufacturer's specifications

as modified for aging roughness factors with deposits and corrosion; and horizontal drainage piping

must be designed and installed at slopes in accordance with Table 704.1 (IPC 2024, 713.1, 713.2,

713.2.1, 713.3, 713.3.1 and 713.3.2).

Where plumbing fixtures are installed on a floor with a finished floor elevation below the elevation

of the manhole cover of the next upstream manhole in the public sewer, such fixtures must be protected

by a backwater valve installed in the building drain or horizontal branch serving such fixtures;

fixtures installed on a floor with a finished floor elevation above the elevation of that manhole

cover must not discharge through a backwater valve, except that in existing buildings fixtures above

that elevation are not prohibited from discharging through a backwater valve (IPC 2024, 714.1 and

Exception). Backwater valves must comply with ASME A112.14.1, CSA B181.1 or CSA B181.2 (IPC 2024,

714.2), and must be installed so that access is provided to the working parts (IPC 2024, 714.3).

Sections 715 through 718 govern vacuum drainage systems, replacement of underground building sewers

and building drains by pipe-bursting methods, relining of building sewers and building drains, and

rehabilitation of building sewers and building drains; vacuum drainage systems must be designed per

the manufacturer's instructions and the plans, specifications and other data submitted to the code

official for review and approval prior to installation (IPC 2024, 715.1, 715.2, 716.1, 717.1 and

718.1).

12. Testing the sanitary drainage system

Section 312 governs the tests (IPC 2024, 701.6):

Drainage and vent water test: the water test is applied to the whole system or in sections, all

openings in the piping tightly closed except the highest opening, the system filled with water to

the point of overflow; if tested in sections, each opening tightly plugged except the highest

openings of the section under test and each section filled with water, but no section tested with

less than a 10-foot (3048 mm) head of water; in testing successive sections, not less than the upper

10 feet of the next preceding section must be tested, so that no joint or pipe in the building,

except the uppermost 10 feet of the system, is submitted to a test of less than a 10-foot head of

water. The pressure must be held for not less than 15 minutes, and the system must then be tight at

all points (IPC 2024, 312.2).

Drainage and vent air test: plastic piping must not be tested using air; an air test is made by

forcing air into the system until there is a uniform gauge pressure of 5 psi (34.5 kPa) or enough

to balance a 10-inch (254 mm) column of mercury, held for not less than 15 minutes, with adjustments

for ambient temperature or gasket seating made before the test period begins (IPC 2024, 312.3).

Drainage and vent vacuum test: the portion under test is evacuated of air by a vacuum-type pump to a

uniform gauge pressure of negative 5 pounds per square inch or a negative 10 inches of mercury

column, held without removal of additional air for 15 minutes (IPC 2024, 312.4).

Drainage and vent final test: the final test of the completed drainage and vent systems is visual

and in sufficient detail to determine compliance; where a smoke test is used it is made by filling

all traps with water and introducing into the entire system a pungent, thick smoke produced by one

or more smoke machines; when the smoke appears at stack openings on the roof, the stack openings

must be closed and a pressure equivalent to a 1-inch water column (248.8 Pa) held for a test period

of not less than 15 minutes (IPC 2024, 312.5).

Storm Drainage

Reference text for the storm drainage area. Every rule below is written from the printed line of the

2024 International Plumbing Code (IPC 2024) that carries it, and each rule names the section it comes

from. Where the printed line does not state a value, no value is stated here; where a sizing table is

printed under a number, the table is reproduced under that number with the values read from the print.

The whole of Chapter 11 of the code is read for this text, together with the sections it refers to.

1. General

The chapter governs the materials, design, construction and installation of storm drainage

(IPC 2024, 1101.1). Rainwater falling on roofs, and storm water from paved areas, yards, courts and

courtyards, must drain to an approved place of disposal; for one- and two-family dwellings, and where

the code official approves it, such water is permitted to discharge onto flat areas such as streets or

lawns as long as the flow is directed away from the building (IPC 2024, 1101.2). The purpose stated by

the code for the whole chapter: rainfall onto buildings must be removed and directed to a location

that can accommodate storm water, and the chapter fixes the design rainfall event for the geographic

area and the sizing methods for piping and gutter systems, together with the piping materials and the

subsoil drainage rules (IPC 2024, Chapter 11, About this chapter).

Storm water must not be drained into a sewer intended for sewage only (IPC 2024, 1101.3). That

prohibition is the mirror of the rule printed for sanitary drainage: where the public sewer is a

combined system carrying both sanitary sewage and storm water, the sanitary sewer is connected

independently to that public sewer (IPC 2024, 703.6), and the storm sewer is likewise connected

independently to it (IPC 2024, 1109.1).

The conductors and the building storm drain are tested in accordance with Section 312

(IPC 2024, 1101.4). The size of a drainage pipe in the storm system must not be reduced in the

direction of flow (IPC 2024, 1101.5). Connections and changes of direction in the storm drainage

system must be made with approved drainage-type fittings in accordance with Table 706.3, and those

fittings must not obstruct or retard the flow in the system (IPC 2024, 1101.6).

Roof design carries a structural rule: roofs must be designed for the maximum possible depth of water

that will pond on them, as determined by the relative levels of the roof deck and of the overflow

weirs, scuppers, edges or serviceable drains, combined with the deflected structural elements. In

fixing that maximum depth, all primary roof drainage means are assumed to be blocked, and the depth

must include the height of water required above the inlet of the secondary roof drainage means for

that secondary means to carry the design rainfall rate required by Section 1106 (IPC 2024, 1101.7).

Cleanouts must be installed in the storm drainage system and must comply with the provisions of the

code for sanitary drainage pipe cleanouts; the exception printed there is the subsurface drainage

system (IPC 2024, 1101.8 and Exception). Storm drainage systems must be provided with backwater

valves as required for sanitary drainage systems in accordance with Section 714 (IPC 2024, 1101.9).

2. Materials

The materials and methods used to construct and install storm drainage systems must comply with this

section and with the applicable provisions of Chapter 7 (IPC 2024, 1102.1).

Inside storm drainage conductors installed above ground conform to one of the standards listed in

Table 702.1 (IPC 2024, 1102.2). Underground building storm drain pipe conforms to one of the standards

listed in Table 702.2 (IPC 2024, 1102.3). Building storm sewer pipe conforms to one of the standards

listed in Table 1102.4 (IPC 2024, 1102.4).

TABLE 1102.4 BUILDING STORM SEWER PIPE

MaterialStandard
Acrylonitrile butadiene styrene (ABS) plastic pipe in IPS diameters, including Schedule 40, DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or composite wallASTM D2661; ASTM F628; ASTM F1488; CSA B181.1; CSA B182.1
Cast-iron pipeASTM A74; ASTM A888; CISPI 301
Concrete pipeASTM C14; ASTM C76; CSA A257.1; CSA A257.2
Copper or copper-alloy tubing (Type K, L, M or DWV)ASTM B75; ASTM B88; ASTM B251; ASTM B306
Polyethylene (PE) plastic pipeASTM F667; ASTM F2306/F2306M; ASTM F2648/F2648M; ASTM F2763; ASTM F2947/F2947M; CSA B182.8
Polypropylene (PP) pipeASTM F2764; ASTM F2881; CSA B182.13
Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR26, SDR35, SDR41, PS50 or PS100) in IPS diameters, including Schedule 40, DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or composite wallASTM D2665; ASTM D3034; ASTM F891; ASTM F1488; CSA B181.2; CSA B182.2; CSA B182.4
Stainless steel drainage systems, Type 316LASME A112.3.1
Vitrified clay pipeASTM C4; ASTM C700

Subsoil drains are open-jointed, horizontally split or perforated pipe conforming to one of the

standards listed in Table 1102.5 (IPC 2024, 1102.5).

TABLE 1102.5 SUBSOIL DRAIN PIPE

MaterialStandard
Cast-iron pipeASTM A74; ASTM A888; CISPI 301
Polyethylene (PE) plastic pipeASTM F667; CSA B182.1; CSA B182.6; CSA B182.8
Polyvinyl chloride (PVC) plastic pipe (type sewer pipe, SDR35, PS25, PS50 or PS100)ASTM D2729; ASTM D3034; ASTM F891; CSA B182.2; CSA B182.4
Stainless steel drainage systems, Type 316LASME A112.3.1
Vitrified clay pipeASTM C4; ASTM C700

Roof drains conform to ASME A112.3.1 or ASME A112.6.4; roof drains other than siphonic roof drains

are tested and rated in accordance with ASME A112.6.4 or ASPE/IAPMO Z1034 (IPC 2024, 1102.6).

Pipe fittings must be approved for installation with the piping material installed and must conform

to the respective pipe standards or to one of the standards listed in Table 1102.7. The fittings must

not have ledges, shoulders or reductions capable of retarding or obstructing the flow in the piping,

and threaded drainage pipe fittings must be of the recessed drainage type (IPC 2024, 1102.7).

TABLE 1102.7 PIPE FITTINGS

MaterialStandard
Acrylonitrile butadiene styrene (ABS) plasticASTM D2661; ASTM D3311; CSA B181.1
Cast ironASME B16.4; ASME B16.12; ASTM A74; ASTM A888; CISPI 301
Coextruded composite ABS and drain DR-PS in PS35, PS50, PS100, PS140, PS200ASTM D2751
Coextruded composite ABS DWV Schedule 40 IPS pipe (solid or cellular core)ASTM D2661; ASTM D3311; ASTM F628
Coextruded composite PVC DWV Schedule 40 IPS-DR, PS140, PS200 (solid or cellular core)ASTM D2665; ASTM D3311; ASTM F891
Coextruded composite PVC sewer and drain DR-PS in PS35, PS50, PS100, PS140, PS200ASTM D3034
Copper or copper alloyASME B16.15; ASME B16.18; ASME B16.22; ASME B16.23; ASME B16.26; ASME B16.29
Gray iron and ductile ironAWWA C110/A21.10
Malleable ironASME B16.3
Plastic, generalASTM F409
Polyethylene (PE) plastic pipeASTM F667/F667M; ASTM F2306/F2306M; ASTM F2763; ASTM F2947/F2947M
Polypropylene (PP) plastic pipeASTM F2764; ASTM F2881/F2881M
Polyvinyl chloride (PVC) plasticASTM D2665; ASTM D3311; ASTM F1866; ASTM F3202
Stainless steel drainage systems, Type 316LASME A112.3.1
SteelASME B16.9; ASME B16.11; ASME B16.28

3. Traps

Leaders and storm drains that connect to a combined sewer must be trapped. The trap is installed

either individually, on the storm water drain branch serving each conductor, or as a single trap in

the main storm drain immediately before its connection with the combined building sewer or with the

public sewer. Leaders and storm drains that connect to a building storm sewer are not required to be

trapped (IPC 2024, 1103.1). A storm water trap must be of the same material as the piping system it

is attached to (IPC 2024, 1103.2), and the trap for an individual conductor must be the same size as

the horizontal drain it is connected to (IPC 2024, 1103.3). A cleanout is installed on the building

side of the trap and is provided with access (IPC 2024, 1103.4).

4. Conductors and connections

Conductor pipes must not be used as soil, waste or vent pipes, and soil, waste or vent pipes must not

be used as conductors (IPC 2024, 1104.1). Floor drains must not be connected to a storm drain

(IPC 2024, 1104.2).

5. Roof drains

Roof drains are installed in accordance with the manufacturer's instructions, and the inside opening

of the roof drain must not be obstructed by the roofing membrane material (IPC 2024, 1105.1). The

published flow rate of the roof drain, based on the head of water above the drain, is the figure used

to size the storm drainage system in accordance with Section 1106; the flow rate used for sizing the

storm drainage piping is based on the maximum anticipated ponding at the roof drain

(IPC 2024, 1105.2).

6. Size of conductors, leaders and storm drains

6.1 Design rainfall

The size of vertical conductors and leaders, of building storm drains and building storm sewers, and

of any horizontal branches of such drains or sewers, is based on the 100-year hourly rainfall rate of

the geographic area as mapped in the figures published with the section, or on other rainfall rates

determined from approved local weather data (IPC 2024, 1106.1).

6.2 Storm drain piping

Vertical and horizontal storm drain piping is sized on the flow rate through the roof drain. That

flow rate is calculated in accordance with Section 1106.2.1 and is then checked against the roof

drain manufacturer's published flow rate for the specific model and size of the drain selected, to

verify that the drain will handle the anticipated flow. The flow rate in storm drain piping must not

exceed the values printed in Table 1106.2 (IPC 2024, 1106.2).

TABLE 1106.2 STORM DRAIN PIPE SIZING

Pipe size (inches)Capacity (gpm), vertical drainCapacity (gpm), horizontal drain at 1/16 inch per footat 1/8 inch per footat 1/4 inch per footat 1/2 inch per foot
23415223144
387395579111
418081115163231
5311117165234331
6538243344487689
81,1175057141,0101,429
102,0509271,3111,8552,623
123,2721,4802,0932,9604,187
155,5432,5083,5465,0167,093

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m

(IPC 2024, Table 1106.2).

6.3 Rainfall rate converted to a flow rate

The rainfall rate falling on a roof surface is converted to a gallon-per-minute flow rate by

Equation 11-1: the flow rate equals the rainfall intensity in inches per hour, multiplied by the roof

area in square feet, multiplied by 0.0104 (IPC 2024, 1106.2.1).

6.4 Vertical leaders

Vertical leaders are sized on the flow rate delivered from horizontal gutters or on the maximum flow

rate through the roof drains. The flow rate through vertical leaders must not exceed the values of

Table 1106.3 (IPC 2024, 1106.3).

TABLE 1106.3 VERTICAL LEADER SIZING

Size of leader (inches)Capacity (gpm)
230
2 × 230
1 1/2 × 2 1/230
2 1/254
2 1/2 × 2 1/254
392
2 × 492
2 1/2 × 392
4192
3 × 4 1/4192
3 1/2 × 4192
5360
4 × 5360
4 1/2 × 4 1/2360
6563
5 × 6563
5 1/2 × 5 1/2563
81208
6 × 81208

For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m (IPC 2024, Table 1106.3).

6.5 Vertical walls

When roof drains and storm drainage piping are sized, one-half of the area of any vertical wall that

diverts rainwater onto the roof is added to the projected roof area, and that combined area is the

area used in calculating the required size of the vertical conductors, the leaders and the horizontal

storm drainage piping (IPC 2024, 1106.4).

6.6 Parapet wall scuppers

Where scuppers serve as primary roof drainage, as secondary (emergency overflow) roof drainage, or as

both, their quantity, size, location and inlet elevation are chosen so that the depth of ponding

water on the roof does not exceed the maximum water depth for which the roof was designed as

determined by the International Building Code. Scupper openings are not less than 4 inches (102 mm)

in height and have a width equal to or greater than the circumference of a roof drain sized for the

same roof area. The flow through the primary system is not counted when the secondary scuppers are

located and sized (IPC 2024, 1106.5).

6.7 Roof gutters

Horizontal gutters are sized on the flow rate from the roof surface, and the flow rate in horizontal

gutters must not exceed the values of Table 1106.6 (IPC 2024, 1106.6).

TABLE 1106.6 HORIZONTAL GUTTER SIZING

Gutter dimensions (inches)Slope (inch per foot)Capacity (gpm)
1 1/2 × 2 1/21/426
1 1/2 × 2 1/21/240
41/839
2 1/4 × 31/455
2 1/4 × 31/287
51/874
4 × 2 1/21/4106
3 × 3 1/21/2156
61/8110
3 × 51/4157
3 × 51/2225
81/16172
81/8247
4 1/2 × 61/4348
4 1/2 × 61/2494
101/16331
101/8472
5 × 81/4651
4 × 101/21055

Footnote a of the table: dimensions are width by depth for rectangular shapes, and a single dimension

is the diameter of a semicircle. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute =

3.785 L/m, 1 inch per foot = 83.3 mm/m (IPC 2024, Table 1106.6).

7. Siphonic roof drainage systems

Siphonic roof drains and siphonic drainage systems are designed in accordance with ASME A112.6.9 and

ASPE 45 (IPC 2024, 1107.1).

8. Secondary (emergency) roof drains

Where roof drains are required, secondary (emergency overflow) roof drains or scuppers are provided

where the roof perimeter construction extends above the roof in a manner that would entrap water if

the primary drains allow a buildup of water for any reason. Where primary and secondary roof drains

are manufactured as a single assembly, the inlet and the outlet of each drain are independent

(IPC 2024, 1108.1).

The secondary roof drain system discharges at an end point separate from the primary system, above

grade, at a location normally observed by the building occupants or by maintenance personnel

(IPC 2024, 1108.2).

Secondary (emergency) roof drain systems are sized in accordance with Section 1106, on the rainfall

rate for which the primary system is sized. Scuppers are sized so that the depth of ponding water does

not exceed the depth for which the roof was designed as determined by Section 1101.7; a scupper has

an opening dimension of not less than 4 inches (102 mm) in height, and an opening width equal to the

circumference of the roof drain required for the area served. The flow through the primary system is

not counted when the secondary roof drain system is sized (IPC 2024, 1108.3).

The section on secondary roof drains carries no sizing table of its own in the print read for this

document; the sizing of secondary drains is by reference to Section 1106 (IPC 2024, 1108.3), and the

only sizing tables printed in Chapter 11 are Table 1106.2, Table 1106.3 and Table 1106.6

(IPC 2024, Table 1106.2, Table 1106.3, Table 1106.6).

9. Combined sanitary and storm public sewer

Where the public sewer is a combined system serving both sanitary sewage and storm water, the storm

sewer is connected independently to that public sewer (IPC 2024, 1109.1).

10. Controlled flow roof drain systems

Where the storm drainage system is engineered for controlled flow, the roof of the structure is

designed for the storage of water. The controlled flow roof drain system is an engineered system

under this section and under the design, submittal, approval, inspection and testing requirements of

Section 316.1, and it is designed on the required rainfall rate of Section 1106.1 (IPC 2024, 1110.1).

The control devices are installed so that the discharge rate of water per minute does not exceed the

values for continuous flow indicated in Section 1110.1 (IPC 2024, 1110.2). Runoff control is by those

control devices, and the control devices are protected by strainers (IPC 2024, 1110.3). The minimum

number of roof drains in such a roof is fixed: not fewer than two roof drains in roof areas of

10,000 square feet (929 m²) or less, and not fewer than four roof drains in roofs of more than

10,000 square feet (929 m²) (IPC 2024, 1110.4).

11. Subsoil drains

Subsoil drains are open-jointed, horizontally split or perforated pipe conforming to one of the

standards listed in Table 1102.5, and they are not less than 4 inches (102 mm) in diameter. Where the

building is subject to backwater, the subsoil drain is protected by a backwater valve located with

access. Subsoil drains discharge to a trapped area drain, to a sump, to a dry well or to an approved

location above ground. A subsoil sump is not required to have a gastight cover or a vent, and the sump

and the pumping system comply with Section 1113.1 (IPC 2024, 1111.1).

12. Building subdrains

Building subdrains located below the level of the public sewer discharge into a sump or a receiving

tank whose contents are lifted automatically and discharged into the drainage system as required for

building sumps; the sump and the pumping equipment comply with Section 1113.1 (IPC 2024, 1112.1).

13. Sumps and pumping systems

The sump pump, the pit and the discharge piping conform to Sections 1113.1.1 through 1113.1.4

(IPC 2024, 1113.1).

The sump pump is of a capacity and a head appropriate to the anticipated use requirements

(IPC 2024, 1113.1.1). The sump pit is not less than 18 inches (457 mm) in diameter and not less than

24 inches (610 mm) in depth, unless otherwise approved; it is provided with access and is located so

that all drainage flows into the pit by gravity. The pit is constructed of tile, steel, plastic, cast

iron, concrete or another approved material, with a removable cover adequate to support the

anticipated loads in the area of use, and the pit floor is solid and provides permanent support for

the pump (IPC 2024, 1113.1.2). Electrical service outlets, where they are required, meet the

requirements of NFPA 70 (IPC 2024, 1113.1.3).

The discharge piping meets the requirements of Section 1102.2, 1102.3 or 1102.4 and includes a gate

valve and a full flow check valve; the pipe and the fittings are the same size as, or larger than,

the pump discharge tapping (IPC 2024, 1113.1.4). The exception printed with that rule: in one- and

two-family dwellings only a check valve is required, located on the discharge piping from the pump or

the ejector (IPC 2024, 1113.1.4 and Exception).

14. Where the rules of the chapter meet the other chapters

Storm drainage borrows from the rest of the code by printed reference, and those references fix what

the storm installer shares with the sanitary installer: the tests of Section 312 (IPC 2024, 1101.4),

the drainage-type fittings and changes of direction of Table 706.3 (IPC 2024, 1101.6), the pipe

cleanout provisions of Chapter 7 through Section 1101.8 (IPC 2024, 1101.8), the backwater valves of

Section 714 (IPC 2024, 1101.9), the materials of Chapter 7 through Section 1102.1 (IPC 2024, 1102.1),

and the above-ground conductor materials of Table 702.1 and the underground building drain materials

of Table 702.2 (IPC 2024, 1102.2 and 1102.3). The combination of storm and sanitary flow in one

building drain does not merge the two systems: each is connected independently to a combined public

sewer (IPC 2024, 703.6 and 1109.1).

Cleanouts

Reference text for the cleanouts area. Every rule below is written from the printed line of the 2024

International Plumbing Code (IPC 2024) that carries it, and each rule names the section it comes

from. Where the printed line does not state a value, no value is stated here. The subject of this

text is Section 708 in full: where a cleanout is required, how far apart cleanouts may be, how big

they are, what they are made of, where they must not be installed, and how much room a person has to

work in front of the opening.

1. The duty, and where it sits in the chapter

Cleanouts must be provided for drainage piping as Sections 708.1.1 through 708.1.12 direct (IPC 2024,

708.1). A cleanout is therefore not an optional convenience added when a drain is hard to reach: it

is a required element of the drainage system, sized, spaced, located and left accessible according to

the rules that follow. Chapter 7 as a whole governs the materials, design, construction and

installation of sanitary drainage systems (IPC 2024, 701.1), and the cleanout rules sit inside that

chapter because access for cleaning is part of how the system is designed, not something added

afterwards.

The sections divide the work along the parts of the system: the horizontal drain inside the building,

the building drain, the building sewer, the junction between the last two, the changes of direction

in each of them, and the cleanout itself as a piece of hardware.

2. Horizontal drains and building drains

Horizontal drainage pipes in buildings must have cleanouts located at intervals of not more than 100

feet (30 480 mm). Building drains must have cleanouts at intervals of not more than 100 feet

(30 480 mm) as well, except that where manholes are used instead of cleanouts the manholes are

located at intervals of not more than 400 feet (122 m) (IPC 2024, 708.1.1).

The measuring rule is part of the same provision and is what a layout is checked against: the

interval length is measured from the cleanout or manhole opening, along the developed length of the

piping, to the next drainage fitting that provides access for cleaning, to the end of the horizontal

drain, or to the end of the building drain (IPC 2024, 708.1.1). Developed length — not the straight

line across the plan — is what counts, so the total of the run a cable or a snake has to travel

between two access points is the number being held to 100 feet.

One exception narrows the requirement: horizontal fixture drain piping serving a nonremovable trap

does not need a cleanout for the section of piping between the trap and the vent connection for that

trap (IPC 2024, 708.1.1). The exception is drawn around the trap-to-vent piece only; it does not

excuse the drain from cleanouts elsewhere along its run.

3. Building sewers

The building sewer is treated according to its size. A building sewer smaller than 8 inches (203 mm)

must have cleanouts located at intervals of not more than 100 feet (30 480 mm). A building sewer

8 inches (203 mm) and larger must have a manhole located not more than 200 feet (60 960 mm) from the

junction of the building drain and the building sewer, and manholes at intervals of not more than

400 feet (122 m) (IPC 2024, 708.1.2).

The interval is again measured along the developed length of the piping, from the cleanout or manhole

opening to the next drainage fitting providing access for cleaning, to a manhole, or to the end of the

building sewer (IPC 2024, 708.1.2). The change from cleanouts to manholes at 8 inches and larger is a

size threshold, and it moves the interval from 100 feet to 400 feet at the same time.

4. The junction of the building drain and the building sewer

The junction of the building drain and the building sewer must be served by a cleanout located at the

junction, or within 10 feet (3048 mm) of the developed length of piping upstream of the junction

(IPC 2024, 708.1.3). Upstream is where the cleanout sits if it is not right at the junction: the

access is placed on the building drain side, within 10 feet of developed length of the point where the

two pipes meet.

The same provision settles a practical conflict that shows up on remodels: for the purpose of this

section, the removal of the water closet is not required in order to provide cleanout access

(IPC 2024, 708.1.3). A layout that would only reach the junction through a pull-out fixture is not

the layout the section asks for.

5. Changes of direction

Where a horizontal drainage pipe, a building drain or a building sewer changes horizontal direction

by more than 45 degrees (0.79 rad), a cleanout must be installed at the change of direction. Where

more than one change of horizontal direction greater than 45 degrees occurs within 40 feet (12 192 mm)

of developed length of piping, the cleanout installed for the first change of direction serves as the

cleanout for all the changes in direction within that 40 feet of developed length (IPC 2024, 708.1.4).

The rule has an angle threshold and a distance threshold, and both have to be read before a cleanout

can be dropped. Offsets under the threshold do not call for a cleanout at all; offsets over it do,

unless the changes are close enough together in developed length that one cleanout covers the group.

6. Size of the cleanout

A cleanout must be the same size as the piping it serves, except that cleanouts for piping larger than

4 inches (102 mm) need not be larger than 4 inches (102 mm) (IPC 2024, 708.1.5). The size of the

opening is thus tied to the pipe below the threshold, and capped at 4 inches above it.

Three exceptions complete the sizing rule (IPC 2024, 708.1.5):

562.A removable P-trap with slip or ground joint connections can serve as a cleanout for drain piping

that is one size larger than the P-trap size.

564.Cleanouts located on stacks can be one size smaller than the stack size.
565.The size of cleanouts for cast-iron piping can follow the referenced standards for cast-iron

fittings as indicated in Table 702.4.

7. A trap as a cleanout: the cleanout equivalent

A fixture trap, or a fixture with an integral trap, that can be removed without altering concealed

piping is acceptable as a cleanout equivalent (IPC 2024, 708.1.6). The condition in the sentence is

the whole content of the rule: removable, and removable without disturbing concealed piping. A trap

that can only be reached by opening a finished surface is not that.

8. Plugs, heads and trim covers

Cleanout plugs must be of copper-alloy, plastic or other approved materials, and cleanout plugs for

borosilicate glass piping systems must be of borosilicate glass. Copper-alloy cleanout plugs must

conform to ASTM A74 and are limited to use on metallic piping systems, while plastic cleanout plugs

must conform to the referenced standards for plastic pipe fittings as indicated in Table 702.4

(IPC 2024, 708.1.7).

The head of the plug must be one of three forms: a raised square head, a countersunk square head or a

countersunk slot head. Where a cleanout plug will have a trim cover screw installed into it, the plug

must be manufactured with a blind end threaded hole for that purpose (IPC 2024, 708.1.7).

Trim covers and access doors for cleanout plugs must be designed for that purpose and be approved, and

the fasteners that thread into the cleanout plugs must be corrosion resistant. A cleanout plug may not

be covered with mortar, plaster or any other permanent material (IPC 2024, 708.1.11.1). The plug is

meant to be opened later; a wall finish that seals it permanently is prohibited for that reason.

9. Manholes

Manholes and manhole covers must be of an approved type, and manholes located inside a building must

have gas-tight covers that require tools for removal (IPC 2024, 708.1.8). The interior manhole is

therefore closed against sewer gas and is not openable by hand.

10. Arrangement and clearance

Cleanouts must be arranged so that cleaning can only take place in the direction of drainage flow

(IPC 2024, 708.1.9). Two arrangements are excepted from that limitation: test tees serving as

cleanouts, and a two-way cleanout installation approved for meeting the requirement that the junction

of building drain and building sewer be served by a cleanout (IPC 2024, 708.1.9).

Clearance in front of the opening is measured as a fixed distance, perpendicular to the face of the

opening, to any obstruction: cleanouts for 6-inch (153 mm) and smaller piping must have a clearance of

not less than 18 inches (457 mm), and cleanouts for 8-inch (203 mm) and larger piping a clearance of

not less than 36 inches (914 mm) (IPC 2024, 708.1.10). Both numbers are measured from, and

perpendicular to, the face of the opening — the working room belongs to the face of the cleanout, not

to the room in general in which the cleanout happens to sit.

11. Access

Required cleanouts may not be installed in concealed locations. For this section, concealed locations

include, but are not limited to, the inside of plenums, within walls, within floor/ceiling

assemblies, below grade, and in crawl spaces where the height from the crawl space floor to the

nearest obstruction along the path from the crawl space opening to the cleanout location is less than

24 inches (610 mm) (IPC 2024, 708.1.11).

Where the cleanout opens at a finished wall, the face of the opening must be located within 1 1/2

inches (38 mm) of the finished wall surface. Where the cleanout is located below grade, it must be

extended to grade level so that the top of the cleanout plug is at or above grade. Where a cleanout is

installed in a floor or walkway that will not have a trim cover installed, it must have a countersunk

plug installed so that the top surface of the plug is flush with the finished surface of the floor or

walkway (IPC 2024, 708.1.11).

A cleanout plug that would be exposed to the loads of vehicular traffic is protected by installing a

cleanout assembly in accordance with ASME A112.36.2M (IPC 2024, 708.1.11.2).

12. Prohibited use

A threaded cleanout opening may not be used to add a fixture or to extend piping, except where another

cleanout of equal size is installed with the required access and clearance (IPC 2024, 708.1.12). The

opening that exists to let a drain be cleaned may only be converted into a connection if the drain

keeps an equivalent cleanout, installed with the access and the clearance the section requires.

13. The numbers of the area, as printed

RuleWhat it fixes
Horizontal drains and building drainsCleanouts at intervals of not more than 100 feet; manholes instead of cleanouts at intervals of not more than 400 feet (IPC 2024, 708.1.1)
Building sewers smaller than 8 inchesCleanouts at intervals of not more than 100 feet (IPC 2024, 708.1.2)
Building sewers 8 inches and largerManhole not more than 200 feet from the junction of building drain and building sewer, and manholes at intervals of not more than 400 feet (IPC 2024, 708.1.2)
Building drain and building sewer junctionCleanout at the junction or within 10 feet of developed length upstream (IPC 2024, 708.1.3)
Changes of horizontal direction over 45 degreesCleanout at the change; one cleanout serves all such changes within 40 feet of developed length (IPC 2024, 708.1.4)
Cleanout sizeSame size as the piping served; need not be larger than 4 inches for piping larger than 4 inches (IPC 2024, 708.1.5)
Required clearance18 inches for piping 6 inches and smaller; 36 inches for piping 8 inches and larger (IPC 2024, 708.1.10)
Face at a finished wallWithin 1 1/2 inches of the finished wall surface (IPC 2024, 708.1.11)
Crawl space accessHeight from crawl space floor to nearest obstruction along the path from the opening to the cleanout not less than 24 inches (IPC 2024, 708.1.11)

14. Reading a layout against the section

The provisions are easier to apply in sequence than all at once, because each one answers a different

question about the same run:

624.Is this piping a horizontal drain, a building drain, or a building sewer? The interval and the

choice between cleanout and manhole follow from that answer (IPC 2024, 708.1.1 and 708.1.2).

626.Where does this run meet the building sewer, and is there access at or within 10 feet of developed

length upstream of that junction (IPC 2024, 708.1.3)?

628.Does the run change horizontal direction by more than 45 degrees, and if it does so more than once

within 40 feet of developed length, which single cleanout covers the group (IPC 2024, 708.1.4)?

630.Is each access point actually reachable — not inside a wall, a floor/ceiling assembly, a plenum,

or a shallow crawl space; at the finished wall face; extended to grade where it was built below

grade; flush where it sits in a floor or walkway (IPC 2024, 708.1.11)?

633.Is the cleanout the right size for the pipe it serves, and is it the right hardware — plug material

and head form, manhole gas-tight where it is inside a building (IPC 2024, 708.1.5, 708.1.7 and

708.1.8)?

636.Is the opening still being used as a cleanout, or is it being used to add a fixture or extend

piping without an equal cleanout taking its place (IPC 2024, 708.1.12)?

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free