Water Supply
Content area 4 of the Oklahoma master plumber exam.
Water Supply and Distribution
Reference text for the water supply area. Every rule below is written from the printed line of the
2024 International Plumbing Code (IPC 2024) that carries it, and each rule names the section it comes
from. Where the printed line does not state a value, no value is stated here.
1. Scope and required water
Chapter 6 governs the materials, design and installation of water supply systems, both hot and cold,
for utilization in connection with human occupancy and habitation, and governs the installation of
individual water supply systems (IPC 2024, 601.1).
Structures equipped with plumbing fixtures and used for human occupancy or habitation must be
provided with a potable supply of water in the amounts and at the pressures specified in the chapter
(IPC 2024, 602.1). Only potable water may be supplied to plumbing fixtures that provide water for
drinking, bathing or culinary purposes, or for the processing of food, medical or pharmaceutical
products; unless the code provides otherwise, potable water must be supplied to all plumbing fixtures
(IPC 2024, 602.2).
Solar energy systems used for heating potable water, or using an independent medium for heating
potable water, must comply with the applicable requirements of the code, and their use must not
compromise the cross-connection or potable-supply protection requirements (IPC 2024, 601.2).
Existing metallic water service piping used for electrical grounding must not be replaced with
nonmetallic pipe or tubing until other approved means of grounding is provided (IPC 2024, 601.3).
The potable water distribution system is tested in accordance with Section 312.6 (IPC 2024, 601.4),
and pressure piping systems rehabilitated with an epoxy lining system must use a lining system
complying with ASTM F2831 (IPC 2024, 601.5).
2. Individual water supply
Where a potable public water supply is not available, individual sources of potable water supply must
be used (IPC 2024, 602.3). The recognized types of individual supply — depending on geological and
soil conditions and the amount of rainfall — are the drilled well, driven well, dug well, bored well,
spring, stream or cistern. Surface bodies of water and land cisterns are not acceptable sources unless
properly treated by approved means to prevent contamination; individual supplies must be constructed
and installed in accordance with applicable state and local laws, and, where those laws do not address
all the requirements of NGWA-01, must comply with NGWA-01 for the requirements those laws do not
address (IPC 2024, 602.3.1).
The combined capacity of source and storage must supply the fixtures with water at the rates and
pressures the chapter requires (IPC 2024, 602.3.2). Water from an individual supply must be approved as
potable by the authority having jurisdiction before connection to the plumbing system (IPC 2024,
602.3.3), and after construction the system must be purged of deleterious matter and disinfected in
accordance with Section 610 (IPC 2024, 602.3.4).
Pumps must be rated for the transport of potable water, be built and installed to prevent
contamination entering the potable supply through the pump units, conform to NSF 61 where they supply
drinking water, be sealed to the well casing or covered with a watertight seal, be designed to
maintain a prime, and be installed with ready access to the pump parts of the entire assembly for
repairs (IPC 2024, 602.3.5). The pump room or enclosure around a well pump must be drained and
protected from freezing by heating or other approved means; pumps installed in basements must be
mounted on a block or shelf not less than 18 inches (457 mm) above the basement floor, and well pits
are prohibited (IPC 2024, 602.3.5.1).
3. Water service
The water service pipe must be sized to supply the structure in the quantities and at the pressures
the code requires, and must be not less than 3/4 inch (19.1 mm) in diameter (IPC 2024, 603.1).
Separation from the building sewer, where the water service is in the same trench: if the building
sewer is not constructed of a material listed in Table 702.2, water service pipe and building sewer
must be horizontally separated by not less than 5 feet (1524 mm) of undisturbed or compacted earth.
That separation does not apply where the water service crosses a sewer pipe, provided the water
service is sleeved to a point not less than 5 feet (1524 mm) horizontally from the sewer pipe
centerline on both sides of the crossing; the sleeve must be of pipe materials listed in Table 605.3,
702.2 or 702.3. It also does not apply where the bottom of the water service pipe, within 5 feet
(1524 mm) of the sewer, is not less than 12 inches (305 mm) above the highest point of the top of the
building sewer (IPC 2024, 603.2). Potable water service pipes must not be located in, under or above
cesspools, septic tanks, septic tank drainage fields or seepage pits; where soil or ground water
creates contaminated conditions for piping, analysis is required in accordance with Section 605.1
(IPC 2024, 603.2.1).
Pipe selection. Water service pipe must conform to NSF 61 and to one of the standards listed in
Table 605.3. Water service pipe or tubing installed underground and outside the structure must have a
working pressure rating of not less than 160 psi (1100 kPa) at 73.4°F (23°C); where the water pressure
exceeds 160 psi (1100 kPa), the piping material must have a working pressure rating not less than the
highest available pressure. Water service piping materials that are not third-party certified for
water distribution must terminate at or before the full-open valve located at the entrance to the
structure, and ductile iron water service piping must be cement mortar lined in accordance with
AWWA C104/A21.4 (IPC 2024, 605.3). Dual check-valve-type backflow preventers installed on the water
supply system must comply with ASSE 1024 or CSA B64.6 (IPC 2024, 605.3.1).
Water distribution pipe and tubing must conform to NSF 61 and to one of the standards listed in
Table 605.4, and hot water distribution pipe and tubing must have a pressure rating of not less than
100 psi (690 kPa) at 180°F (82°C) (IPC 2024, 605.4).
| Table 605.3 — water service pipe (material → standards) |
|---|
| ABS plastic pipe — ASTM D1527; ASTM D2282 |
| CPVC plastic pipe — ASTM D2846; ASTM F441; ASTM F442; CSA B137.6 |
| CPVC/AL/CPVC — ASTM F2855 |
| Copper or copper-alloy pipe — ASTM B42; ASTM B43; ASTM B302 |
| Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM) — ASTM B75; ASTM B88; ASTM B251; ASTM B447 |
| PEX plastic pipe and tubing — ASTM F876; AWWA C904; CSA B137.5 |
| PEX-AL-PEX pipe — ASTM F1281; ASTM F2262; CSA B137.10 |
| PEX-AL-HDPE — ASTM F1986 |
| Ductile iron water pipe — AWWA C115/A21.15; AWWA C151/A21.51 |
| Galvanized steel pipe — ASTM A53 |
| PE plastic pipe — ASTM D2239; ASTM D3035; AWWA C901; CSA B137.1 |
| PE plastic tubing — ASTM D2737; AWWA C901; CSA B137.1 |
| PE-AL-PE pipe — ASTM F1282; CSA B137.9 |
| PE-RT plastic tubing — ASTM F2769; CSA B137.18 |
| Polypropylene (PP) plastic pipe or tubing — ASTM F2389; CSA B137.11 |
| PVC plastic pipe — ASTM D1785; ASTM D2241; ASTM D2672; CSA B137.3 |
| Stainless steel pipe and tubing, Type 304/304L and Type 316/316L — ASTM A269/A269M; ASTM A312; ASTM A778 |
Water distribution is served by a shorter list: CPVC, CPVC/AL/CPVC, copper or copper-alloy pipe and
tubing, PEX, PEX-AL-PEX, PEX-AL-HDPE, ductile iron, galvanized steel, PE-AL-PE composite, PE-RT,
polypropylene, and stainless steel pipe and tubing of Type 304/304L and 316/316L (IPC 2024,
Table 605.4).
4. Design of the building water distribution system
The design must conform to accepted engineering practice, and the methods used to determine pipe sizes
must be approved (IPC 2024, 604.1). At the points of interconnection between the hot and cold water
supply piping systems and the individual fixtures, appliances or devices, provisions must be made to
prevent flow between those piping systems (IPC 2024, 604.2).
4.1 Required capacity at fixture supply outlets (Table 604.3)
Under conditions of peak demand, the capacities at the fixture supply pipe outlets must be not less
than the values of Table 604.3; for fixtures and appliances not listed there, the minimum flow rate
and flow pressure follow the manufacturer's installation instructions (IPC 2024, 604.3).
| Fixture supply outlet serving | Flow rate (gpm) | Flow pressure (psi) |
|---|---|---|
| Bathtub, balanced-pressure, thermostatic or combination balanced-pressure/thermostatic mixing valve | 4 | 20 |
| Bidet, thermostatic mixing valve | 2 | 20 |
| Combination fixture | 4 | 8 |
| Dishwasher, residential | 2.75 | 8 |
| Drinking fountain | 0.75 | 8 |
| Laundry tray | 4 | 8 |
| Lavatory, private | 0.8 | 8 |
| Lavatory, private, mixing valve | 0.8 | 8 |
| Lavatory, public | 0.4 | 8 |
| Shower | 2.5 | 8 |
| Shower, balanced-pressure, thermostatic or combination balanced-pressure/thermostatic mixing valve | 2.5 | 20 |
| Sill cock, hose bibb | 5 | 8 |
| Sink, residential | 1.75 | 8 |
| Sink, service | 3 | 8 |
| Urinal, valve | 12 | 25 |
| Water closet, blow out, flushometer valve | 25 | 45 |
| Water closet, flushometer tank | 1.6 | 20 |
| Water closet, siphonic, flushometer valve | 25 | 35 |
| Water closet, tank, close coupled | 3 | 20 |
| Water closet, tank, one piece | 6 | 20 |
For SI: 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 3.785 L/m. Where the shower mixing
valve manufacturer indicates a lower flow rating for the mixing valve, the lower value applies
(IPC 2024, Table 604.3, footnote b).
4.2 Maximum flow and water consumption (Table 604.4)
Maximum water consumption flow rates and quantities for all plumbing fixtures and fixture fittings
follow Table 604.4 (IPC 2024, 604.4).
| Plumbing fixture or fixture fitting | Maximum flow rate or quantity |
|---|---|
| Lavatory, private | 2.2 gpm at 60 psi |
| Lavatory, public (metering) | 0.25 gallon per metering cycle |
| Lavatory, public (other than metering) | 0.5 gpm at 60 psi |
| Shower head | 2.0 gpm at 80 psi |
| Sink faucet | 2.2 gpm at 60 psi |
| Urinal | 1.0 gallon per flushing cycle |
| Water closet | 1.6 gallons per flushing cycle |
A hand-held shower spray is a shower head, and shower heads must comply with all requirements for
high-efficiency showerheads in ASME A112.18.1-2020/CSA B125.1 (IPC 2024, Table 604.4, footnotes a
and c). The exceptions to Section 604.4 are blowout design water closets having a water consumption
not greater than 3 1/2 gallons (13 L) per flushing cycle, vegetable sprays, clinical sinks having a
water consumption not greater than 4 1/2 gallons (17 L) per flushing cycle, service sinks and
emergency showers.
4.3 Size of fixture supply (Table 604.5)
The minimum size of a fixture supply pipe follows Table 604.5. The fixture supply pipe must terminate
not more than 30 inches (762 mm) from the point of connection to the fixture; a reduced-size flexible
water connector installed between the supply pipe and the fixture must be of an approved type, and the
supply pipe must extend to the floor or wall adjacent to the fixture. The minimum size of individual
distribution lines used in gridded or parallel water distribution systems also follows Table 604.5
(IPC 2024, 604.5).
| Fixture | Minimum pipe size (inch) |
|---|---|
| Bathtubs (60" × 32" and smaller) | 1/2 |
| Bathtubs (larger than 60" × 32") | 1/2 |
| Bidet | 3/8 |
| Combination sink and tray | 1/2 |
| Dishwasher, domestic | 1/2 |
| Drinking fountain | 3/8 |
| Hose bibbs | 1/2 |
| Kitchen sink | 1/2 |
| Laundry, 1, 2 or 3 compartments | 1/2 |
| Lavatory | 3/8 |
| Shower, single head | 1/2 |
| Sinks, flushing rim | 3/4 |
| Sinks, service | 1/2 |
| Urinal, flush tank | 1/2 |
| Urinal, flushometer valve | 3/4 |
| Wall hydrant | 1/2 |
| Water closet, flush tank | 3/8 |
| Water closet, flushometer tank | 3/8 |
| Water closet, flushometer valve | 1 |
| Water closet, one piece | 1/2 |
Where the developed length of the distribution line is 50 feet or less and the available pressure at
the meter is 35 psi or greater, the minimum size of an individual distribution line supplied from a
manifold and installed as part of a parallel water distribution system may be one nominal tube size
smaller than the sizes indicated (IPC 2024, Table 604.5, footnote a).
4.4 Pressure, flow control and manifolds
Where street water main pressures fluctuate, the building water distribution system must be designed
for the minimum pressure available (IPC 2024, 604.6). Wherever the pressure from the street main or
other source is insufficient to provide the flow pressures at fixture outlets required by Table 604.3,
a water pressure booster system conforming to Section 606.5 must be installed on the building water
supply system (IPC 2024, 604.7).
Where water pressure within a building exceeds 80 psi (552 kPa) static, an approved water
pressure-reducing valve conforming to ASSE 1003 or CSA B356 with strainer must be installed to reduce
the pressure in the building water distribution piping to not greater than 80 psi (552 kPa) static.
The exception covers service lines to sill cocks and outside hydrants, and main supply risers where
pressure from the mains is reduced to 80 psi (552 kPa) or less at individual fixtures (IPC 2024,
604.8). The valve must be designed to remain open to permit uninterrupted water flow in case of valve
failure (IPC 2024, 604.8.1), and valves, regulators and strainers must be constructed and installed so
that parts can be repaired or removed without breaking a pipeline or removing the valve and strainer
from the pipeline (IPC 2024, 604.8.2).
The flow velocity of the distribution system must be controlled to reduce the possibility of water
hammer; a water-hammer arrestor must be installed where quick-closing valves are used, installed in
accordance with the manufacturer's instructions, and must conform to ASSE 1010 (IPC 2024, 604.9).
Hot and cold water manifolds installed with gridded or parallel connected individual distribution
lines to each fixture or fixture fitting must be sized in accordance with Table 604.10.1, where the
total gallons per minute is the demand of all outlets supplied (IPC 2024, 604.10.1).
| Nominal size internal diameter (inches) | Maximum demand (gpm), velocity at 4 feet per second | Maximum demand (gpm), velocity at 8 feet per second |
|---|---|---|
| 1/2 | 2 | 5 |
| 3/4 | 6 | 11 |
| 1 | 10 | 20 |
| 1 1/4 | 15 | 31 |
| 1 1/2 | 22 | 44 |
Individual fixture shutoff valves installed at the manifold must be identified as to the fixture
being supplied (IPC 2024, 604.10.2), and access must be provided to manifolds with integral factory-
or field-installed valves (IPC 2024, 604.10.3). Individual pressure balancing in-line valves for
individual fixture fittings must comply with ASSE 1066, must be installed in a location with access,
and must not be used alone as a substitute for the balanced pressure, thermostatic or combination
shower valves required in Section 412.3 (IPC 2024, 604.11).
5. Materials, joints and valves
Installation of a water service or water distribution pipe is prohibited in soil and ground water
contaminated with solvents, fuels, organic compounds or other detrimental materials causing
permeation, corrosion, degradation or structural failure of the piping material; where detrimental
conditions are suspected, a chemical analysis of the soil and ground water is required, and where
detrimental conditions exist, approved alternative materials or routing are required (IPC 2024,
605.1).
Pipe and pipe fittings, including valves and faucets, used in the water supply system must have not
more than 8 percent lead content (IPC 2024, 605.2). Pipe, fittings, joints, valves, faucets and
fixture fittings used to supply water for drinking or cooking purposes must comply with NSF 372 and
must have a weighted average lead content of 0.25 percent or less (IPC 2024, 605.2.1).
Fittings must be approved for installation with the piping material installed and comply with the
applicable standards listed in Table 605.5; fittings used in water supply systems must also comply
with NSF 61, and ductile and gray iron pipe and fittings used in water service piping systems must be
cement mortar lined in accordance with AWWA C104/A21.4 (IPC 2024, 605.5). Flexible water connectors
exposed to continuous pressure must conform to ASME A112.18.6/CSA B125.6, and access must be provided
to all flexible water connectors (IPC 2024, 605.6). Valves must be compatible with the type of piping
material installed in the system, conform to one of the standards listed in Table 605.7 or be
approved, and, where intended to supply drinking water, meet NSF 61 (IPC 2024, 605.7). Manufactured
pipe nipples must conform to one of the standards listed in Table 605.8 (copper, copper alloy and
chromium-plated: ASTM B687; steel: ASTM A733) (IPC 2024, 605.8).
Prohibited joints and connections in the water supply system are: cement or concrete joints; joints
made with fittings not approved for the specific installation; solvent-cement joints between
different types of plastic pipe; and saddle-type fittings (IPC 2024, 605.9).
6. Installation: valves, boosters, tanks and testing
Full-open valves must be installed in these locations (IPC 2024, 606.1):
buildings three stories or less in height where a common water supply piping system supplies other
than one- and two-family dwellings, a main shutoff valve must be provided for each tenant.
occupancies that are two stories or less in height and in one- and two-family residential
occupancies.
occupancies.
fixture equipped with individual stops.
Shutoff valves must be installed on the fixture supply to each plumbing fixture other than bathtubs
and showers in one- and two-family residential occupancies and other than in individual dwelling or
sleeping units that are provided with unit shutoff valves in hotels, motels, boarding houses and
similar occupancies; on the water supply pipe to each sill cock; and on the water supply pipe to each
appliance or mechanical equipment (IPC 2024, 606.2). Access must be provided to all full-open valves
and shutoff valves (IPC 2024, 606.3). Service and hose bibb valves must be identified, and other
valves installed in locations that are not adjacent to the fixture or appliance must be identified
as to the fixture or appliance served (IPC 2024, 606.4).
Where the water pressure in the public water main or individual water supply system is insufficient
to supply the minimum pressures and quantities specified in the code, the supply must be supplemented
by an elevated water tank, a hydropneumatic pressure booster system or a water pressure booster pump
installed in accordance with Section 606.5.5 (IPC 2024, 606.5.1). Within a booster system: a
low-pressure cutoff must be installed on all booster pumps to prevent creation of a vacuum or negative
pressure on the suction side of the pump when a positive pressure of 10 psi (68.94 kPa) or less occurs
on the suction side (IPC 2024, 606.5.5); potable water inlets to gravity tanks must be controlled by a
fill valve or other automatic supply valve installed so as to prevent the tank from overflowing, with
the inlet terminated to provide an air gap not less than 4 inches (102 mm) above the overflow
(IPC 2024, 606.5.6); and every pressure tank in a hydropneumatic pressure booster system must be
protected with a pressure relief valve set at a maximum pressure equal to the rating of the tank,
installed on the supply pipe to the tank or on the tank, discharging by gravity to a safe place of
disposal (IPC 2024, 606.5.10).
Water supply tanks must be covered to keep out unauthorized persons, dirt and vermin; the covers of
gravity tanks must be vented with a return bend vent pipe with an area not less than the area of the
down-feed riser pipe, screened with a corrosion-resistant screen of not less than 16 by 20 mesh per
inch (IPC 2024, 606.5.3). A gravity or suction water supply tank must have an overflow sized by
Table 606.5.4, discharging not less than 6 inches (152 mm) above the roof or roof drain, floor or
floor drain, or over an open water-supplied fixture, and covered with a corrosion-resistant screen of
not less than 16 by 20 mesh per inch and by 1/4-inch (6.4 mm) hardware cloth or terminating in a
horizontal angle seat check valve (IPC 2024, 606.5.4).
| Maximum capacity of water supply line to tank (gpm) | Diameter of overflow pipe (inches) |
|---|---|
| 0 – 50 | 2 |
| 50 – 150 | 2 1/2 |
| 150 – 200 | 3 |
| 200 – 400 | 4 |
| 400 – 700 | 5 |
| 700 – 1,000 | 6 |
| Over 1,000 | 8 |
A drain pipe with a valve must be provided at the lowest point of each tank to permit emptying, must
discharge as required for overflow pipes, and must be not smaller than Table 606.5.7 (IPC 2024,
606.5.7).
| Tank capacity (gallons) | Drain pipe (inches) |
|---|---|
| Up to 750 | 1 |
| 751 to 1,500 | 1 1/2 |
| 1,501 to 3,000 | 2 |
| 3,001 to 5,000 | 2 1/2 |
| 5,000 to 7,500 | 3 |
| Over 7,500 | 4 |
Potable water gravity tanks or manholes of potable water pressure tanks must not be located directly
under any soil or waste piping or any source of contamination (IPC 2024, 606.5.8). Water pressure
tanks must be provided with a vacuum relief valve at the top of the tank operating up to a maximum
water pressure of 200 psi (1380 kPa) and up to a maximum temperature of 200°F (93°C), not less than
1/2 inch (12.7 mm) in size; the section does not apply to pressurized captive air
diaphragm/bladder tanks (IPC 2024, 606.5.9).
Testing: upon completion of a section of or the entire water supply system, the system or portion
completed must be tested in accordance with Section 312 (IPC 2024, 606.6). Section 312.6 requires the
system to be tested and proved tight under a water pressure not less than the working pressure of the
system, or — for piping systems other than plastic — by an air test of not less than 50 psi
(344 kPa), with the pressure held for not less than 15 minutes, and the water used for tests obtained
from a potable source (IPC 2024, 312.6).
7. Hot water supply system
In residential occupancies, hot water must be supplied to plumbing fixtures and equipment used for
bathing, washing, culinary purposes, cleansing, laundry or building maintenance; in nonresidential
occupancies, hot water must be supplied for culinary, cleansing, laundry or building maintenance
purposes, and hot water or tempered water must be supplied for bathing and washing purposes
(IPC 2024, 607.1). A thermostat control for a water heater serves as the temperature limiting means
only where the water heater complies with ASSE 1082 or ASSE 1085 (IPC 2024, 607.1.1). Tempered water
must be controlled by a limiting device conforming to ASSE 1070/ASME A112.1070/CSA B125.70 and set to
not greater than 110°F (43°C), by a thermostatic mixing valve conforming to ASSE 1017, by a water
heater conforming to ASSE 1082, or by a water heater conforming to ASSE 1084; this does not supersede
the requirement for protective shower valves in accordance with Section 412.3 (IPC 2024, 607.1.2).
The developed length of hot or tempered water piping, from the source of hot water to the fixtures
that require hot or tempered water, must not exceed 50 feet (15 240 mm); recirculating system piping
and heat-traced piping are considered sources of hot or tempered water (IPC 2024, 607.2). Where a
storage water heater is supplied with cold water that passes through a check valve, pressure reducing
valve or backflow preventer, a thermal expansion control device must be connected to the water heater
cold water supply pipe at a point downstream of all check valves, pressure reducing valves and
backflow preventers; thermal expansion tanks must be sized per the tank manufacturer's instructions
and such that the pressure in the water distribution system does not exceed that required by
Section 604.8 (IPC 2024, 607.3). Fixture fittings, faucets and diverters must be installed and adjusted
so that the flow of hot water from the fittings corresponds to the left-hand side of the fixture
fitting, with an exception for shower and tub/shower mixing valves conforming to
ASSE 1016/ASME A112.1016/CSA B125.16 or ASME A112.18.1/CSA B125.1 where the flow of hot water
corresponds to the markings on the device (IPC 2024, 607.4).
8. Protection of the potable water supply
A potable water supply system must be designed, installed and maintained so as to prevent
contamination from nonpotable liquids, solids or gases being introduced into the potable water supply
through cross connections or any other piping connections to the system; backflow preventer
applications must conform to Table 608.1, except as specifically stated in Sections 608.2 through
608.17.10 (IPC 2024, 608.1).
Table 608.1 (application of backflow preventers) — selected devices, degree of hazard, application and
standard:
| Device | Degree of hazard | Application | Applicable standards |
|---|---|---|---|
| Double check backflow prevention assembly | Low hazard | Backpressure or backsiphonage, sizes 1/4"–16" | ASSE 1015; AWWA C510; CSA B64.5; CSA B64.5.1 |
| Double check detector fire protection backflow prevention assembly | Low hazard | Backpressure or backsiphonage, sizes 1"–16" | ASSE 1048 |
| Pressure vacuum breaker assembly | High or low hazard | Backsiphonage only, sizes 1/2"–2" | ASSE 1020; CSA B64.1.2 |
| Reduced pressure principle backflow prevention assembly | High or low hazard | Backpressure or backsiphonage, sizes 1/4"–16" | ASSE 1013; AWWA C511; CSA B64.4; CSA B64.4.1 |
| Reduced pressure detector fire protection backflow prevention assembly | High or low hazard | Backsiphonage or backpressure (automatic sprinkler systems) | ASSE 1047 |
| Spill-resistant vacuum breaker assembly | High or low hazard | Backsiphonage only, sizes 1/4"–2" | ASSE 1056; CSA B64.1.3 |
| Antisiphon-type fill valve for gravity water closet flush tank | High hazard | Backsiphonage only | ASSE 1002/ASME A112.1002/CSA B125.12; CSA B125.3 |
| Backflow preventer for carbonated beverage machines | Low hazard | Backpressure or backsiphonage, sizes 1/4"–1/2" | ASSE 1022 |
| Backflow preventer with intermediate atmospheric vent | Low hazard | Backpressure or backsiphonage, sizes 1/4"–3/4" | ASSE 1012; CSA B64.3 |
| Dual-check-valve-type backflow preventer | Low hazard | Backpressure or backsiphonage, sizes 1/4"–2" | ASSE 1024; CSA B64.6 |
| Hose connection backflow preventer | High or low hazard | Low head backpressure, rated working pressure, backpressure or backsiphonage, sizes 1/2"–1" | ASME A112.21.3; ASSE 1052; CSA B64.2.1.1 |
| Hose connection vacuum breaker | High or low hazard | Low head backpressure or backsiphonage, sizes 1/2", 3/4", 1" | ASME A112.21.3; ASSE 1011; CSA B64.2; CSA B64.2.1 |
| Laboratory faucet backflow preventer | High or low hazard | Low head backpressure and backsiphonage | ASSE 1035; CSA B64.7 |
| Pipe-applied atmospheric-type vacuum breaker | High or low hazard | Backsiphonage only, sizes 1/8"–8" | ASSE 1001; CSA B64.1.1 |
| Vacuum breaker wall hydrant, frost-resistant, automatic-draining type | High or low hazard | Low head backpressure or backsiphonage, sizes 3/4", 1" | ASME A112.21.3; ASSE 1019; CSA B64.2.2 |
| Air gap | High or low hazard | Backsiphonage or backpressure | ASME A112.1.2 |
| Air gap fittings for plumbing fixtures, appliances and appurtenances | High or low hazard | Backsiphonage or backpressure | ASME A112.1.3 |
| Barometric loop | High or low hazard | Backsiphonage only | See Section 608.14.4 |
In Table 608.1, "low hazard" is pollution and "high hazard" is contamination, both as defined in
Section 202 (IPC 2024, Table 608.1, footnotes a and b).
8.1 Means of protection
The minimum required air gap is measured vertically from the lowest end of a potable water outlet to
the flood level rim of the fixture or receptacle into which the outlet discharges; air gaps must
comply with ASME A112.1.2 and air gap fittings with ASME A112.1.3, and products listed and labeled to
those standards are considered in compliance (IPC 2024, 608.14.1).
Reduced pressure principle backflow prevention assemblies must conform to ASSE 1013, AWWA C511,
CSA B64.4 or CSA B64.4.1, and reduced pressure detector assembly backflow preventers to ASSE 1047;
they may be installed where subject to continuous pressure, and the relief opening must discharge by
air gap and be prevented from being submerged (IPC 2024, 608.14.2). Backflow preventers with
intermediate atmospheric vents must conform to ASSE 1012, ASSE 1081 or CSA B64.3, may be installed
under continuous pressure, and their relief opening must discharge by air gap and be prevented from
being submerged (IPC 2024, 608.14.3). Barometric loops must precede the point of connection and extend
vertically to a height of 35 feet (10 668 mm), and may be used only as an atmospheric-type or
pressure-type vacuum breaker (IPC 2024, 608.14.4). Pressure vacuum breaker assemblies must comply with
ASSE 1020 or CSA B64.1.2, spill-resistant vacuum breaker assemblies with ASSE 1056 or CSA B64.1.3, and
these assemblies must be installed with the critical level located not less than 12 inches (305 mm)
above all downstream piping and outlets; pressure vacuum breaker assemblies must not be installed
where spillage could cause damage to the structure (IPC 2024, 608.14.5). Double check backflow
prevention assemblies must conform to ASSE 1015, CSA B64.5, CSA B64.5.1 or AWWA C510, double check
detector fire protection assemblies to ASSE 1048, and these assemblies must be capable of operating
under continuous pressure conditions (IPC 2024, 608.14.7). Dual check backflow preventers must comply
with ASSE 1024 or CSA B64.6 (IPC 2024, 608.14.9), and backflow devices for chemical dispensers must
comply with ASSE 1055 or be equipped with an air gap fitting (IPC 2024, 608.14.8).
Access must be provided to backflow preventers as specified by the manufacturer's instructions
(IPC 2024, 608.15). They must not be located in areas subject to freezing except where they can be
removed by means of unions or are protected from freezing by heat, insulation or both (IPC 2024,
608.15.2), and the termination of piping from the relief port or air gap fitting must discharge to an
approved indirect waste receptor or to the outdoors where it will not cause damage or create a
nuisance, with the receptor and drainage piping sized to drain the maximum discharge flow rate from
the relief port as published by the manufacturer (IPC 2024, 608.15.2.1).
8.2 Protection of potable water outlets
Openings and outlets must be protected by an air gap between the opening and the fixture flood level
rim as specified in Table 608.16.1; openings and outlets equipped for hose connection must be
protected by means other than an air gap (IPC 2024, 608.16.1).
| Fixture | Minimum air gap, away from a wall (inches) | Minimum air gap, close to a wall (inches) |
|---|---|---|
| Lavatories and other fixtures with effective openings not greater than 1/2 inch in diameter | 1 | 1 1/2 |
| Sinks, laundry trays, gooseneck back faucets and other fixtures with effective openings not greater than 3/4 inch in diameter | 1 1/2 | 2 1/2 |
| Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch in diameter | 2 | 3 |
| Drinking water fountains, single orifice not greater than 7/16 inch in diameter, or multiple orifices with a total area of 0.150 square inch | 1 | 1 1/2 |
| Effective openings greater than 1 inch | Two times the diameter of the effective opening | Three times the diameter of the effective opening |
The "away from a wall" column applies where walls or obstructions are spaced from the nearest
inside-edge of the spout opening a distance greater than three times the diameter of the effective
opening for a single wall, or greater than four times the diameter of the effective opening for two
intersecting walls (IPC 2024, Table 608.16.1, footnote a).
Where openings and outlets are protected by vacuum breakers, the critical level of the vacuum breaker
must be set not less than 6 inches (152 mm) above the flood level rim of the fixture or device; fill
valves must be set in accordance with Section 415.3.1; vacuum breakers must not be installed under
exhaust hoods or similar locations that will contain toxic fumes or vapors; and pipe-applied vacuum
breakers must be installed not less than 6 inches (152 mm) above the flood level rim of the fixture,
receptor or device served (IPC 2024, 608.16.4). Approved deck-mounted or equipment-mounted vacuum
breakers, and faucets with integral atmospheric vacuum breakers or spill-resistant vacuum breaker
assemblies, must be installed in accordance with the manufacturer's instructions and the requirements
for labeling, with the critical level not less than 1 inch (25 mm) above the flood level rim
(IPC 2024, 608.16.4.1). Sill cocks, hose bibbs, wall hydrants and other openings with a hose
connection must be protected by an atmospheric-type or pressure-type vacuum breaker or a permanently
attached hose connection vacuum breaker, except for water heater and boiler drain valves with hose
connection threads intended only for tank or vessel draining, and water supply valves intended for
connection of clothes washing machines where backflow prevention is otherwise provided or integral
with the machine (IPC 2024, 608.16.4.2).
8.3 Health care plumbing (highlights)
Health care plumbing systems must conform to Section 609 in addition to the other requirements of the
code, and the provisions apply to Group I-1, Group I-2, ambulatory care facilities, medical offices,
research and testing laboratories, and Group F facilities manufacturing pharmaceutical drugs and
medicines (IPC 2024, 609.1). Group I-2, Condition 2 facilities must have not fewer than two water
service pipes sized so that, with the loss of the largest service pipe, the remaining service pipes
meet the water demand for the entire facility, each service with a shutoff valve in the building and a
shutoff valve at the utility-provided point of connection (IPC 2024, 609.2). Vacuum breakers in health
care plumbing must be installed not less than 6 inches (152 mm) above the flood level rim of the
fixture or device in accordance with Section 608, and the flood level rim of hose connections is the
maximum height at which any hose is utilized (IPC 2024, 609.4).
9. Disinfection and treatment
New potable water systems must be purged of deleterious matter and disinfected prior to utilization.
The method is that prescribed by the health authority or water purveyor having jurisdiction or, in the
absence of a prescribed method, the procedure described in AWWA C651 or AWWA C652 or in Section 610;
the requirement applies to on-site or in-plant fabrication of a system or of a modular portion of a
system (IPC 2024, 610.1). The procedure published in the section is: flush the pipe system with clean,
potable water until dirty water does not appear at the points of outlet; fill the system or part with
a water/chlorine solution containing not less than 50 parts per million (50 mg/L) of chlorine, valve
it off and let it stand for 24 hours, or fill with a solution containing not less than 200 parts per
million (200 mg/L) of chlorine and let it stand for 3 hours; then flush with clean potable water until
the chlorine is purged; and repeat the procedure where a bacteriological examination shows
contamination remains (IPC 2024, 610.1, items 1 through 4).
Point-of-use reverse osmosis drinking water treatment units must comply with CSA B483.1 or NSF 58, and
drinking water treatment units must meet CSA B483.1, NSF 42, NSF 44, NSF 53 or NSF 62 (IPC 2024,
611.1). The discharge from a reverse osmosis drinking water treatment unit must enter the drainage
system through an air gap or an air gap device meeting CSA B483.1 or NSF 58 (IPC 2024, 611.2), and
tubing to and from drinking water treatment units must be of a size and material recommended by the
manufacturer and comply with NSF 14, NSF 42, NSF 44, NSF 53, NSF 58 or NSF 61 (IPC 2024, 611.3).
Solar systems for domestic hot water heating and similar uses must be constructed and installed in
accordance with the International Mechanical Code (IPC 2024, 612.1). Temperature-actuated mixing
valves installed to reduce water temperatures to defined limits must comply with ASSE 1017 and be
installed at the hot water source (IPC 2024, 613.1).
Protection of the Potable Water Supply (Backflow Prevention)
Reference text for the backflow prevention area. Every rule below is written from the printed line of
the 2024 International Plumbing Code (IPC 2024) that carries it, and each rule names the section it
comes from. Where the printed line does not state a value, no value is stated here. The degree of
hazard a device may be used on, the applications it may serve and the sizes it is made in are the
values carried by Table 608.1; they are reproduced here as that table prints them.
1. The duty this area carries
A potable water supply system must be designed, installed and maintained in a way that prevents
contamination from nonpotable liquids, solids or gases being introduced into the potable supply
through cross connections or through any other piping connection to the system. The applications of
backflow preventers follow Table 608.1, except where Sections 608.2 through 608.17.10 state the
protection specifically (IPC 2024, 608.1). That whole-chapter duty is what the rest of this text
unpacks: the table is the default answer, and the numbered sections are the particular answers that
override it.
Cross connections are prohibited outright, and the only way to keep one is to install approved
backflow prevention assemblies, backflow prevention devices, or other approved means or methods that
protect the potable supply (IPC 2024, 608.7). Where a private water supply exists alongside a potable
public supply, a cross connection between the two is prohibited without qualification (IPC 2024,
608.7.1).
2. Where the plumbing system may not go at all
Service utilities are held back until the code official authorizes them: a person may not connect a
utility, source of energy, fuel, power, water system or sewer system to a building or system
regulated by the code and requiring a permit until that authorization exists (IPC 2024, 109.1).
The code official may authorize a temporary connection of the building or system to the utility,
source of energy, fuel, power, water system or sewer system for testing plumbing systems or for use
under a temporary approval (IPC 2024, 109.2), and may authorize disconnection of utility service to a
building, structure or system regulated by the code and the referenced codes and standards in an
emergency where disconnection is necessary to eliminate an immediate hazard to life or property, or
where the utility connection was made without the approval Sections 109.1 and 109.2 require (IPC 2024,
109.3). Where the disconnection decision is made, the code official must notify the serving utility
and, wherever possible, the owner, the owner's authorized agent and the occupant before acting; where
that was not possible beforehand, the notice must be given in writing as soon as is practical
afterward (IPC 2024, 109.3).
Plumbing systems may not be located in an elevator shaft or in an elevator equipment room. Floor
drains, sumps and sump pumps are permitted at the base of the shaft, but only where they are
indirectly connected to the plumbing system and comply with Section 1003.4 (IPC 2024, 301.6).
Together those two provisions decide where a potable supply may be brought in and where it may be
left: a plumbing system is not permitted inside the shaft, and the drainage that is permitted at the
base of the shaft is kept at arm's length from the supply by the indirect connection.
3. The device table: hazard, application and sizes (Table 608.1)
Table 608.1 sorts the available protections into backflow prevention assemblies, backflow preventer
plumbing devices, and other means or methods, and for each one prints the degree of hazard it may
serve, the application (backsiphonage only, backpressure, or both) and the sizes or standards that
apply.
| Device | Degree of hazard | Application | Applicable standards |
|---|---|---|---|
| Double check backflow prevention assembly | Low hazard | Backpressure or backsiphonage; sizes 1/4"–16" | ASSE 1015; AWWA C510; CSA B64.5; CSA B64.5.1 |
| Double check detector fire protection backflow prevention assembly | Low hazard | Backpressure or backsiphonage; sizes 1"–16" | ASSE 1048 |
| Pressure vacuum breaker assembly | High or low hazard | Backsiphonage only; sizes 1/2"–2" | ASSE 1020; CSA B64.1.2 |
| Reduced pressure principle backflow prevention assembly | High or low hazard | Backpressure or backsiphonage; sizes 1/4"–16" | ASSE 1013; AWWA C511; CSA B64.4; CSA B64.4.1 |
| Reduced pressure detector fire protection backflow prevention assembly | High or low hazard | Backsiphonage or backpressure (automatic sprinkler systems) | ASSE 1047 |
| Spill-resistant vacuum breaker assembly | High or low hazard | Backsiphonage only; sizes 1/4"–2" | ASSE 1056; CSA B64.1.3 |
| Antisiphon-type fill valves for gravity water closet flush tanks | High hazard | Backsiphonage only | ASSE 1002/ASME A112.1002/CSA B125.12; CSA B125.3 |
| Backflow preventer for carbonated beverage machines | Low hazard | Backpressure or backsiphonage; sizes 1/4"–1/2" | ASSE 1022 |
| Backflow preventer with intermediate atmospheric vent | Low hazard | Backpressure or backsiphonage; sizes 1/4"–3/4" | ASSE 1012; CSA B64.3 |
| Backflow preventer with intermediate atmospheric vent and pressure-reducing valve | Low hazard | Backpressure or backsiphonage; sizes 1/2"–3/4" | ASSE 1081 |
| Dual-check-valve-type backflow preventer | Low hazard | Backpressure or backsiphonage; sizes 1/4"–2" | ASSE 1024; CSA B64.6 |
| Hose connection backflow preventer | High or low hazard | Low head backpressure, rated working pressure, backpressure or backsiphonage; sizes 1/2"–1" | ASME A112.21.3; ASSE 1052; CSA B64.2.1.1 |
| Hose connection vacuum breaker | High or low hazard | Low head backpressure or backsiphonage; sizes 1/2", 3/4", 1" | ASME A112.21.3; ASSE 1011; CSA B64.2; CSA B64.2.1 |
| Laboratory faucet backflow preventer | High or low hazard | Low head backpressure and backsiphonage | ASSE 1035; CSA B64.7 |
| Pipe-applied atmospheric-type vacuum breaker | High or low hazard | Backsiphonage only; sizes 1/8"–8" | ASSE 1001; CSA B64.1.1 |
| Vacuum breaker wall hydrants, frost-resistant, automatic-draining-type | High or low hazard | Low head backpressure or backsiphonage; sizes 3/4", 1" | ASME A112.21.3; ASSE 1019; CSA B64.2.2 |
| Air gap | High or low hazard | Backsiphonage or backpressure | ASME A112.1.2 |
| Air gap fittings for use with plumbing fixtures, appliances and appurtenances | High or low hazard | Backsiphonage or backpressure | ASME A112.1.3 |
| Barometric loop | High or low hazard | Backsiphonage only | See Section 608.14.4 |
The table's footnotes tie the two words "low hazard" and "high hazard" back to the definitions of
pollution and contamination in the code's definition chapter, and the application column's "low head
backpressure" and "backsiphonage" to the definitions of backflow in the same place (IPC 2024, Table
608.1). Reading the table therefore means reading those definitions first: a device is not selected
because the pipe is small, but because the hazard on the other side of the connection is a pollution
or a contamination and because the driving force is backpressure or backsiphonage.
4. What the assembly has to be, and where it may sit
The means of protection are given standards, and those standards are what an installer orders against
and what an inspector reads off the device.
water outlet to the flood level rim of the fixture or receptacle the outlet discharges into. Air
gaps must comply with ASME A112.1.2 and air gap fittings with ASME A112.1.3; a product listed and
labeled to either standard is treated as complying (IPC 2024, 608.14.1).
CSA B64.4.1, and reduced pressure detector assemblies to ASSE 1047. They may be installed where the
device is subject to continuous pressure conditions, and the relief opening must discharge by air
gap and must be kept from being submerged (IPC 2024, 608.14.2).
1081 or CSA B64.3, may be installed under continuous pressure conditions, and their relief opening
must discharge by air gap and must not be submerged (IPC 2024, 608.14.3).
height of 35 feet (10 668 mm). It may only be used as an atmospheric-type or pressure-type vacuum
breaker (IPC 2024, 608.14.4).
spill-resistant vacuum breaker assemblies with ASSE 1056 or CSA B64.1.3. The critical level of the
assembly must sit not less than 12 inches (305 mm) above all downstream piping and outlets, and a
pressure vacuum breaker assembly may not be installed where spillage could damage the structure
(IPC 2024, 608.14.5).
ASSE 1001 or CSA B64.1.1; hose-connection vacuum breakers to ASME A112.21.3, ASSE 1011, ASSE 1019,
ASSE 1035, ASSE 1052, CSA B64.2, CSA B64.2.1, CSA B64.2.1.1, CSA B64.2.2 or CSA B64.7. They operate
under normal atmospheric pressure when the critical level is installed at the required height
(IPC 2024, 608.14.6).
double check detector fire protection assemblies to ASSE 1048. They must be capable of operating
under continuous pressure conditions (IPC 2024, 608.14.7).
1055 or be equipped with an air gap fitting (IPC 2024, 608.14.8).
Access must be provided to backflow preventers as the manufacturer's instructions specify (IPC 2024,
608.15), and outdoor enclosures for backflow prevention devices must comply with ASSE 1060 (IPC 2024,
608.15.1).
Placement is a rule of its own: a backflow preventer may not be located in an area subject to
freezing, unless it can be removed by means of unions or is protected from freezing by heat,
insulation, or both (IPC 2024, 608.15.2). Where the piping from the relief port or air gap fitting of
a backflow preventer terminates, it must discharge to an approved indirect waste receptor or to the
outdoors where it will not cause damage or create a nuisance, and both the waste receptor and the
drainage piping must be sized to drain the maximum discharge flow rate from the relief port as the
backflow preventer manufacturer publishes it (IPC 2024, 608.15.2.1). A discharge that is merely
"allowed to drip somewhere" is not the rule: the receiving pipe has to be able to take the device's
own published maximum flow.
5. Protection of openings and outlets (608.16)
Potable water openings and outlets are protected under one of six provisions — air gap, reduced
pressure principle assembly, backflow preventer with intermediate atmospheric vent, or one of the
three vacuum breaker provisions (IPC 2024, 608.16).
Protection by air gap means an air gap between the opening and the fixture flood level rim as Table
608.16.1 specifies. An opening or outlet equipped for hose connection must be protected by means
other than an air gap (IPC 2024, 608.16.1).
TABLE 608.16.1 MINIMUM REQUIRED AIR GAPS
| Fixture | Away from a wall (inches) | Close to a wall (inches) |
|---|---|---|
| Lavatories and other fixtures with effective openings not greater than 1/2 inch in diameter | 1 | 1 1/2 |
| Sinks, laundry trays, gooseneck back faucets and other fixtures with effective openings not greater than 3/4 inch in diameter | 1 1/2 | 2 1/2 |
| Over-rim bath fillers and other fixtures with effective openings not greater than 1 inch in diameter | 2 | 3 |
| Drinking water fountains, single orifice not greater than 7/16 inch in diameter, or multiple orifices with a total area of 0.150 square inch | 1 | 1 1/2 |
| Effective openings greater than 1 inch | Two times the diameter of the effective opening | Three times the diameter of the effective opening |
For that table, "away from a wall" applies where walls or obstructions are spaced from the nearest
inside edge of the spout opening by more than three times the diameter of the effective opening for a
single wall, or more than four times that diameter for two intersecting walls (IPC 2024, Table
608.16.1).
The other routes to protecting an opening or outlet are: a reduced pressure principle backflow
prevention assembly, or a reduced pressure principle fire protection backflow prevention assembly, on
potable water supplies (IPC 2024, 608.16.2); a backflow preventer with an intermediate atmospheric
vent (IPC 2024, 608.16.3); or a vacuum breaker (IPC 2024, 608.16.4).
The vacuum breaker provision carries the heights and the prohibitions an installer works to. The
critical level of the vacuum breaker must be set not less than 6 inches (152 mm) above the flood level
rim of the fixture or device, fill valves are set as the code's fill valve section directs, vacuum
breakers may not be installed under exhaust hoods or in similar locations that will contain toxic
fumes or vapors, and a pipe-applied vacuum breaker must be installed not less than 6 inches (152 mm)
above the flood level rim of the fixture, receptor or device served (IPC 2024, 608.16.4).
Deck-mounted and integral vacuum breakers have a shorter height of their own: approved deck-mounted or
equipment-mounted vacuum breakers, and faucets with integral atmospheric vacuum breakers or
spill-resistant vacuum breaker assemblies, are installed per the manufacturer's instructions and per
the labeling requirements, with the critical level not less than 1 inch (25 mm) above the flood level
rim (IPC 2024, 608.16.4.1).
Hose connections — sill cocks, hose bibbs, wall hydrants and other openings with a hose connection —
are protected by an atmospheric-type or pressure-type vacuum breaker, or by a permanently attached
hose connection vacuum breaker. Two connections are carved out of that rule: water heater and boiler
drain valves with hose connection threads that are intended only for tank or vessel draining, and
water supply valves intended for connecting clothes washing machines where backflow prevention is
otherwise provided or is integral with the machine (IPC 2024, 608.16.4.2).
6. Connections to the potable system, appliance by appliance (608.17)
The chapter then names the equipment that commonly gets connected to potable water and fixes the
protection for each:
A carbonated beverage dispenser is protected by a backflow preventer conforming to ASSE 1022 or by
an air gap, and no part of the device downstream from its second check valve, nor the piping
downstream of that, may be affected by carbon dioxide gas (IPC 2024, 608.17.1.1). Coffee machines
and noncarbonated drink dispensers are protected by a backflow preventer conforming to ASSE 1022,
ASSE 1024 or ASSE 1032, or by an air gap (IPC 2024, 608.17.1.2).
atmospheric vent complying with ASSE 1012, ASSE 1081 or CSA B64.3; where conditioning chemicals are
put into the system, the potable connection is protected by an air gap or a reduced pressure
principle backflow preventer complying with ASSE 1013, AWWA C511 or CSA B64.4 (IPC 2024, 608.17.2).
potable water by double-wall construction, with an air gap open to the atmosphere between the two
walls; an essentially nontoxic transfer fluid permits single-wall construction (IPC 2024, 608.17.3).
backflow prevention assembly, a double check fire protection backflow prevention assembly, or a
reduced pressure principle fire protection backflow prevention assembly. Isolation of the water
supply system is not required where the systems are installed as part of the water distribution
system under the code and have no fire department connection, and isolation is not required for
deluge, preaction or dry pipe systems (IPC 2024, 608.17.4).
continuous pressure and contains chemical additives or antifreeze, or is connected to a nonpotable
secondary water supply, the potable supply is protected by a reduced pressure principle backflow
prevention assembly or a reduced pressure principle fire protection backflow prevention assembly;
where additives or antifreeze are added to only part of the system, that assembly may be located so
as to isolate that part. Where the system is not under continuous pressure, the protection is an
air gap or an atmospheric vacuum breaker conforming to ASSE 1001 or CSA B64.1.1 (IPC 2024,
608.17.4.1).
pressure vacuum breaker assembly or a reduced pressure principle backflow prevention assembly. No
valve may be installed downstream from an atmospheric vacuum breaker. Where chemicals are put into
the system, the protection must be a reduced pressure principle backflow prevention assembly
(IPC 2024, 608.17.5).
fixture, tank, vat, pump or other equipment subject to high-hazard backpressure, the connection is
protected by a reduced pressure principle backflow prevention assembly (IPC 2024, 608.17.6).
the means listed for it: for chemical dispensers, the air gap, the reduced pressure principle
assembly, the pressure vacuum breaker assembly, the atmospheric-type vacuum breaker or the chemical
dispenser backflow device (IPC 2024, 608.17.7); for portable cleaning equipment, the air gap, the
reduced pressure principle assembly, the backflow preventer with intermediate atmospheric vent, the
double check assembly or the chemical dispenser backflow device (IPC 2024, 608.17.8); for dental
pumping equipment, the air gap, the reduced pressure principle assembly, the pressure vacuum
breaker assembly, the atmospheric-type vacuum breaker or the chemical dispenser backflow device
(IPC 2024, 608.17.9).
backflow preventer conforming to ASSE 1012 or by an air gap (IPC 2024, 608.17.10).
7. Fixtures, equipment and the water that serves them (608.2 through 608.13)
Plumbing fixtures. The supply lines and fittings for plumbing fixtures are installed so as to prevent
backflow, and plumbing fixture fittings provide backflow protection in accordance with ASME
A112.18.1/CSA B125.1 (IPC 2024, 608.2).
Devices, appurtenances, appliances and apparatus. Equipment intended to serve a special function —
sterilization, distillation, processing, cooling, or the storage of ice or foods — that connects to
the water supply system must be provided with protection against backflow and contamination of the
water supply system (IPC 2024, 608.3). For hospital fixtures the water supply is protected by a
reduced pressure principle backflow prevention assembly, an atmospheric or spill-resistant vacuum
breaker assembly, or an air gap; vacuum breakers for bedpan washer hoses must be not less than 5 feet
(1524 mm) above the floor, and vacuum breakers for hose connections in health care or laboratory areas
not less than 6 feet (1829 mm) above the floor (IPC 2024, 608.3.1).
Potable water handling and treatment equipment. Water pumps, filters, softeners, tanks and other
appliances and devices that handle or treat potable water for the potable distribution system must be
located so that contamination cannot enter them, and the overflow, relief valve and waste discharge
pipes from them must terminate through an air gap (IPC 2024, 608.4). More generally, water pumps,
filters, softeners, tanks and other devices handling or treating potable water must be protected
against contamination (IPC 2024, 608.13).
Water service piping is protected under the code's water service provisions (IPC 2024, 608.5).
Chemicals. Chemicals and other substances that would produce toxic conditions, taste, odor or
discoloration in a potable water system may not be introduced into or used in such systems (IPC 2024,
608.6).
Reuse and reutilization. Water used to heat or cool equipment or for other processes may not be
returned to the potable water system; it must be discharged into a drainage system through an air gap
or used for nonpotable purposes (IPC 2024, 608.10). Piping that has conveyed anything other than
potable water may not be used to convey potable water (IPC 2024, 608.11).
Tanks. Where a water tank, its interior coating or its liner is in contact with potable water intended
for drinking, those materials must conform to NSF 61, and the interior surface of the tank may not be
lined, painted or repaired with any material that changes the taste, odor, color or potability of the
water supply when the tank is placed in, or returned to, service (IPC 2024, 608.12).
Valves and outlets below grade. Potable water outlets and combination stop-and-waste valves may not be
installed underground or below grade, and a freezeproof yard hydrant that drains the riser into the
ground is treated as having a stop-and-waste valve below grade. Such a hydrant is permitted where the
potable supply to it is protected under the backflow provisions for reduced pressure principle
assemblies or pressure vacuum breaker assemblies, and the hydrants and the piping from the backflow
preventer to the hydrant are identified as the code's identification section requires (IPC 2024,
608.8).
8. Identifying what is not potable (608.9)
Where nonpotable water systems are installed, the piping conveying the nonpotable water must be
identified by color marking, metal tags or tape (IPC 2024, 608.9).
Signage. Nonpotable water outlets such as hose connections, open-ended pipes and faucets must carry
signage reading "Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER – DO
NOT DRINK." The words must be legibly and indelibly printed on a tag or sign of corrosion-resistant
waterproof material, or indelibly printed on the fixture; the letters must be not less than 0.5 inch
(12.7 mm) in height and in colors contrasting with their background, and the required pictograph must
appear on the signage in addition to the wordage (IPC 2024, 608.9.1).
Pipe labeling. Nonpotable distribution piping must be purple and embossed, integrally stamped or
marked with "CAUTION: NONPOTABLE WATER – DO NOT DRINK", or installed with a purple identification tape
or wrap. The identification must carry the contents of the system and an arrow indicating direction of
flow, and hazardous systems must also state the nature of the hazard. The identification must be
repeated at intervals not exceeding 25 feet (7620 mm) and at every point where the piping passes
through a wall, floor or roof, and the lettering must be readily observable within the room or space
where the piping is located (IPC 2024, 608.9.2).
The color must be discernible and consistent throughout the building, and purple is the color for
reclaimed, rain and graywater distribution systems (IPC 2024, 608.9.2.1). The size of the background
color field and of the lettering follows Table 608.9.2.2 (IPC 2024, 608.9.2.2):
TABLE 608.9.2.2 SIZE OF PIPE IDENTIFICATION
| Pipe diameter (inches) | Length of background color field (inches) | Size of letters (inches) |
|---|---|---|
| 3/4 to 1 1/4 | 8 | 0.5 |
| 1 1/2 to 2 | 8 | 0.75 |
| 2 1/2 to 6 | 12 | 1.25 |
| 8 to 10 | 24 | 2.5 |
| over 10 | 32 | 3.5 |
Where identification tape is used, it must be not less than 3 inches (76 mm) wide, with white or
black lettering on a purple field stating "CAUTION: NONPOTABLE WATER – DO NOT DRINK". The tape is
installed on top of nonpotable rainwater distribution pipes, fastened not less than every 10 feet
(3048 mm) to each pipe length and run continuously along the entire length of the pipe (IPC 2024,
608.9.2.3).
9. Individual water supplies: keeping the source out of reach of contamination (608.18)
An individual water supply must be located and constructed so as to be safeguarded against
contamination (IPC 2024, 608.18).
Well location. A potable ground water source or pump suction line may not be located closer to
potential sources of contamination than the distances Table 608.18.1 shows, and where the underlying
rock is limestone or fragmented shale the local or state health department must be consulted on the
well site. Those distances are minimum separations, and they must be increased in areas of creviced
rock or limestone, or where ground water moves from sources of contamination toward the well
(IPC 2024, 608.18.1).
TABLE 608.18.1 DISTANCE FROM CONTAMINATION TO PRIVATE WATER SUPPLIES AND PUMP SUCTION LINES
| Source of contamination | Distance (feet) |
|---|---|
| Barnyard | 100 |
| Farm silo | 25 |
| Pasture | 100 |
| Pumphouse floor drain of cast iron draining to ground surface | 2 |
| Seepage pits | 50 |
| Septic tank | 25 |
| Sewer | 10 |
| Subsurface disposal fields | 50 |
| Subsurface pits | 50 |
Elevation and depth. Well sites must be positively drained and sit at higher elevations than
potential sources of contamination (IPC 2024, 608.18.2). A private potable well supply may not be
developed from a water table less than 10 feet (3048 mm) below the ground surface (IPC 2024,
608.18.3).
Casings and covers. Each well must have a watertight casing extending to not less than 10 feet
(3048 mm) below the ground surface, with the casing extending not less than 6 inches (152 mm) above
the well platform, large enough to permit a separate drop pipe, and sealed at the bottom in an
impermeable stratum or extended several feet into the water-bearing stratum (IPC 2024, 608.18.4).
Drilled or driven well casings must be of steel or another approved material; where a drilled well
extends into rock, the casing must extend to and set firmly in the formation, and the annular space
between earth and casing must be filled with cement grout to not less than 10 feet (3048 mm) below
the ground surface, or to the rock surface where the casing is set to rock (IPC 2024, 608.18.5). Dug
or bored well casings must be watertight concrete, tile, or galvanized or corrugated metal pipe
extending to not less than 10 feet (3048 mm) below ground — and below the water table where the table
is deeper than 10 feet — surrounded by 6 inches (152 mm) of grout poured between the casing and the
ground and extending not less than 10 feet (3048 mm) below ground (IPC 2024, 608.18.6). A potable
water well must have an overlapping watertight cover at the top of the casing or pipe sleeve so that
contaminated water and other substances cannot enter through the annular opening; covers must extend
downward not less than 2 inches (51 mm) over the outside of the casing or wall, a dug well cover must
carry a pipe sleeve that lets the pump suction pipe, cylinder or jet body be withdrawn without
disturbing the cover, and where pump sections or discharge pipes pass through the side of the casing
the circle of contact must be watertight (IPC 2024, 608.18.7).
Drainage. Wells and springs must be constructed so that surface drainage is diverted away from them
(IPC 2024, 608.18.8).
10. What the inspector reads on the drawing and in the field
Put together, the area answers five questions in a fixed order:
device, or other approved means or method (IPC 2024, 608.7).
from the definitions the table's footnotes point to (IPC 2024, Table 608.1).
column of the table, and the same distinction in Sections 608.16 and 608.17, rule out devices that
only hold against one of the two (IPC 2024, Table 608.1).
the installation rules add the height of the critical level (IPC 2024, 608.14.5), the clearance
from a flood level rim (IPC 2024, 608.16.4), the prohibition on freezing locations (IPC 2024,
608.15.2), and the requirement that the relief discharge be able to take the device's published
maximum flow (IPC 2024, 608.15.2.1).
Identification, signage, purple piping and repeat intervals are the answer (IPC 2024, 608.9).
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free