Subject guide

Plan Reading

Subject guide — a code subject several of the state exam outlines declare.

Plan Reading

Reference text for the plan reading area. This text is not a chapter of the code: reading a plumbing

plan is a competence, and it is written here from the printed provisions that govern what the

document of a plumbing project must carry and what the figures drawn on it mean. Every rule below is

written from the printed line of the 2024 International Plumbing Code (IPC 2024) that carries it, and

each rule names the section it comes from. Where the printed line does not state a value, no value is

stated here; where a sizing table is printed under a number, the table is reproduced under that

number with the values read from the print. The text says what it does: it reads a plan through the

printed dispositions, and it does not add a method of drafting or a rule of any school that the code

read for this document does not print.

1. The document a plumbing plan belongs to

The printed code does not speak of a plan in the abstract; it speaks of the permit application and of

the construction documents filed with it. Work that the code regulates — to erect, install, enlarge,

alter, repair, remove, convert or replace any plumbing system — is not started, and no such work is

caused to be performed, before an application has been made to the code official and the required

permit obtained (IPC 2024, 105.1). A printed exception list removes a short set of work from the

permit requirement: the stopping of leaks in drains, water, soil, waste or vent pipe, with the

qualification that a concealed trap, drainpipe, water, soil, waste or vent pipe that has become

defective and must be removed and replaced with new material is treated as new work and requires a

permit and an inspection; the clearing of stoppages and the repair of leaks in pipes, valves or

fixtures; and the removal and reinstallation of water closets, provided such repairs do not involve

or require the replacement or rearrangement of valves, pipes or fixtures. Exemption from the permit

does not authorize work that violates the code (IPC 2024, 105.2).

Each application for a permit, with the required fee, is filed on the form the code official

furnishes and carries a general description of the proposed work and of its location, is signed by

the owner or the owner's authorized agent, and indicates the proposed occupancy of all parts of the

building and of that part of the site or lot not covered by the building or structure, with any other

information the code official requires (IPC 2024, 105.3). Before the permit is issued, the code

official is authorized to inspect and evaluate the systems, equipment, buildings, devices, premises

and spaces or areas to be used (IPC 2024, 105.3.1). An application is treated as abandoned 180 days

after filing unless it has been pursued in good faith or a permit has been issued, and the code

official may grant extensions of not more than 180 days each, on a written request showing

justifiable cause (IPC 2024, 105.3.2). The application is made by the person or agent who is to

install all or part of the plumbing system, that applicant meeting the qualifications established by

statute, rules, ordinance or resolution, and the full name and address of the applicant are stated in

the application (IPC 2024, 105.4).

The application and the construction documents filed with it are reviewed by the code official, and

where the proposed work is found to conform to the code and to the applicable laws and ordinances,

and the fees of Section 108.1 have been paid, the permit is issued (IPC 2024, 105.5). Where the code

official issues a permit for work for which construction documents are required, those documents are

endorsed in writing and stamped "APPROVED"; approved construction documents are not changed, modified

or altered without the authorization of the code official, and the work is done in accordance with

them. The code official may issue a permit for part of a plumbing system before the whole set of

documents has been submitted, on adequate information and detailed statements that comply with the

code, and the holder of such a permit proceeds at his or her own risk, without assurance that the

permit for the entire system will be granted (IPC 2024, 105.5.1).

A permit, or an approval of construction documents, is not a permit for or an approval of a violation

of the code or of any ordinance of the jurisdiction, and a permit purporting to give authority to

violate or cancel the code is not valid; issuing a permit on the basis of documents does not stop the

code official from later requiring errors in those documents to be corrected, or from preventing

building operations carried on under them where they violate the code (IPC 2024, 105.5.2). A permit

expires if the work authorized is not started within 180 days from its date, or if the work is

suspended or abandoned for a period of 180 days at any time after it was started; before the work can

be recommenced a new permit is obtained, at one-half the fee of a new permit, provided the original

documents are unchanged and the suspension or abandonment has not exceeded one year

(IPC 2024, 105.5.3). An unexpired permit may be extended for a period not exceeding 180 days where

there is reasonable cause, not more than once, on the same half-fee basis

(IPC 2024, 105.5.4). A permit issued in error, or on the basis of incorrect, inaccurate or incomplete

information, or in violation of any ordinance, regulation or provision of the code, may be suspended

or revoked (IPC 2024, 105.5.5). The permit, or a copy of it, is kept on the site of the work until

the project is completed (IPC 2024, 105.5.7).

2. What the construction documents must show

Construction documents, engineering calculations, diagrams and other such data are submitted in two

or more sets, or in a digital format where the code official allows it, with each application for a

permit. Where state law requires it, the code official requires those documents, computations and

specifications to be prepared and designed by a registered design professional. The printed

requirements on the drawing itself are these: the construction documents are drawn to scale, they are

of sufficient clarity to indicate the location, the nature and the extent of the work proposed, and

they show in detail that the work conforms to the provisions of the code. For buildings more than two

stories in height, the construction documents additionally indicate where penetrations will be made

for pipes, fittings and components, and indicate the materials and methods for maintaining the

required structural safety, fire-resistance rating and fireblocking (IPC 2024, 106.1).

The exception printed with that rule allows the code official to waive the submission of construction

documents, calculations or other data where the nature of the work applied for makes the review of

those documents unnecessary to determine compliance (IPC 2024, 106.1 and Exception).

One set of approved construction documents is retained by the code official for not less than

180 days from the date of completion of the permitted work, or as state or local laws require; one

set is returned to the applicant, and that returned set is kept on the site of the building or work

at all times while the work authorized by the permit is in progress (IPC 2024, 106.2).

3. Reading the drawing at the three printed inspection stages

Construction or work for which a permit is required is subject to inspection by the code official,

and that construction or work remains visible and able to be accessed for inspection purposes until

approved; it is the duty of the permit applicant to keep the work in that state. Approval following

an inspection is not an approval of a violation of the code (IPC 2024, 111.1).

The code prints three stages, each with its own scope, and a plan is read against them:

Underground inspection — made after the trenches or ditches are excavated and bedded and the

piping is installed, and before any backfill is put in place.

Rough-in inspection — made after the roof, framing, fireblocking, firestopping, draftstopping

and bracing are in place and all sanitary, storm and water distribution piping is roughed-in, and

prior to the installation of wall or ceiling membranes.

Final inspection — made after the building is complete, all plumbing fixtures are in place and

properly connected, and the structure is ready for occupancy.

(IPC 2024, 111.2)

The holder of the permit, or an authorized agent, notifies the code official when the work is ready

for inspection and provides access and the means for the inspections the code requires

(IPC 2024, 111.2.2). Work is not done beyond the point indicated in each successive inspection

without first obtaining the approval of the code official; the code official indicates the portion of

the construction that is satisfactory as completed or notifies the permit holder where it fails to

comply, and any portion that does not comply is corrected and is not covered or concealed until the

code official authorizes it (IPC 2024, 111.2.3).

For an alternative engineered design, the registered design professional or designated inspector

periodically inspects and observes the installation to determine that it is in accordance with the

approved construction documents, discrepancies are brought to the immediate attention of the plumbing

contractor for correction, and records are kept of all inspections (IPC 2024, 111.3.1); a final

report in writing certifies that the installation conforms to the approved construction documents,

and a notice of approval is not issued until that written certification has been submitted

(IPC 2024, 111.3.2). The notice of approval itself is issued by the code official after the

prescribed tests and inspections indicate that the work complies in all respects with the code

(IPC 2024, 107.1), the permit holder making the applicable tests prescribed in Section 312 and giving

reasonable advance notice when the work is ready for them (IPC 2024, 312.1), and the plumbing work

and systems being tested as Section 312 requires, with the tests made by the permit holder and

observed by the code official (IPC 2024, 111.4).

4. The drainage figures a plan carries

Drainage fixture unit values designate the relative load weight of the different kinds of fixtures

and are used in estimating the total load carried by a soil or waste pipe, in connection with the

sizing tables for soil, waste and vent pipes in which the permissible load is given in fixture units

(IPC 2024, 709.1 and Table 709.1).

The maximum number of drainage fixture units that may be connected to a given size of building sewer,

building drain or horizontal branch of the building drain is determined from the sizing table for

buildings drains and sewers, and the maximum number connected to a given size of horizontal branch or

vertical soil or waste stack is determined from the sizing table for horizontal fixture branches and

stacks (IPC 2024, 710.1 and Table 710.1(1) and Table 710.1(2)).

A horizontal drainage pipe is drawn at a uniform slope, and the printed minimum slopes are these

(IPC 2024, 704.1 and Table 704.1):

Size (inches)Minimum slope (inch per foot)
2 1/2 or less1/4
3 to 61/8
8 or larger1/16

Footnote a of that table sends the slope of piping draining to a grease interceptor back to the text

of the section, which requires not less than 1/4 inch per foot (2 percent slope) upstream of a grease

interceptor; and for SI: 1 inch = 25.4 mm, 1 inch per foot = 83.33 mm/m (IPC 2024, 704.1 and

Table 704.1). The control devices and the connections that follow from the slope are also read off

the drawing: fixture units establish the load, the load fixes the size, the size fixes the slope, and

the sizing tables of Section 710.1 give the permissible fixture-unit load for that size

(IPC 2024, 709.1, 710.1 and 704.1).

The size of the drainage piping is not reduced in the direction of flow; a 4-inch by 3-inch water

closet flange, a water closet bend fitting with a 4-inch inlet and a 3-inch outlet whose 4-inch leg

is upright and below the flange, and an offset closet flange are not treated as a reduction

(IPC 2024, 704.2). Horizontal branches connect to the bases of stacks at a point not less than

10 times the diameter of the drainage stack downstream from the stack, and connect to horizontal

stack offsets at a point not less than 10 times the diameter of the drainage stack downstream from

the upper stack (IPC 2024, 704.3). Drainage piping installed for future fixtures terminates with an

approved cap or plug, which is what the drawing shows for that rough-in (IPC 2024, 704.4).

Cleanout locations are drawn from the printed intervals and geometries: horizontal drainage pipes in

buildings have cleanouts at intervals of not more than 100 feet (30 480 mm), and building drains also

at not more than 100 feet, except that manholes used in place of cleanouts are at not more than

400 feet (122 m), the interval being measured from the cleanout or manhole opening along the

developed length of the piping to the next drainage fitting that provides access for cleaning, to the

end of the horizontal drain or to the end of the building drain (IPC 2024, 708.1.1). The junction of

the building drain and the building sewer is served by a cleanout located at the junction or within

10 feet (3048 mm) of the developed length of piping upstream of it (IPC 2024, 708.1.3). A change of

horizontal direction greater than 45 degrees (0.79 rad) in a horizontal drainage pipe, a building

drain or a building sewer carries a cleanout at that change, and where more than one such change

occurs within 40 feet (12 192 mm) of developed length, the cleanout installed for the first change

serves all the changes within that length (IPC 2024, 708.1.4). Cleanouts are the same size as the

piping they serve, except that cleanouts for piping larger than 4 inches (102 mm) need not be larger

than 4 inches (102 mm) (IPC 2024, 708.1.5). Clearance is drawn too: not less than 18 inches (457 mm)

from the face of the opening for cleanouts of 6-inch (153 mm) and smaller piping, and not less than

36 inches (914 mm) for cleanouts of 8-inch (203 mm) and larger piping, in both cases perpendicular to

the face of the opening and measured to any obstruction (IPC 2024, 708.1.10).

5. The vent geometry a plan carries

The minimum diameter of a stack vent or a vent stack is read from the developed length and the total

drainage fixture units connected to it in the sizing table for stack vents and vent stacks, and the

diameter is in no case less than one-half the diameter of the drain served or less than 1 1/4 inches

(32 mm) (IPC 2024, 906.1 and Table 906.1). The developed length that goes into that reading is

measured from the farthest point of vent connection to the drainage system to the point of connection

to the vent stack, the stack vent or the termination outside of the building (IPC 2024, 906.3).

The protecting vent of each fixture trap is located so that the slope and the developed length in the

fixture drain from the trap weir to the vent fitting are within the printed limits, which are read

from the table of maximum distance of fixture trap from vent (IPC 2024, 909.1 and Table 909.1):

Size of trap (inches)Slope (inch per foot)Distance from trap (feet)
1 1/41/45
1 1/21/46
21/48
31/812
41/816

Where a plan shows a sidewall vent terminal, the dimensions it carries come from the printed

clearances: 10 feet (3048 mm) or more from the lot line, and 10 feet (3048 mm) or more above the

highest adjacent grade where that grade lies within 10 feet (3048 mm) of the terminal horizontally,

with no termination under the overhang of a structure that has soffit vents, and protection against

birds and rodents entering or blocking the opening (IPC 2024, 903.1.4). No open vent terminal is drawn

directly below a door, an openable window or any other air intake of that building or of a

neighbouring one, and it stays outside 10 feet (3048 mm) horizontally of such an opening unless it

rises 3 feet (914 mm) or more above the top of that opening (IPC 2024, 903.5). Vent and branch vent

pipes are graded and connected so as to drain back to the drainage pipe by gravity (IPC 2024, 905.2),

every dry vent connecting to a

horizontal drain connects above the centerline of that drain (IPC 2024, 905.3), and every dry vent

rises vertically to not less than 6 inches (152 mm) above the flood level rim of the highest trap or

trapped fixture vented (IPC 2024, 905.4). Where the print read for this document carries no number on

a line — the height above the roof for an unprotected roof extension is printed as a bracketed

placeholder rather than as a figure — the drawing cannot take a value from that line, and none is

stated here (IPC 2024, 903.1.1).

6. The water supply figures a plan carries

The water distribution system is designed, and the pipe sizes are selected, so that under peak demand

the capacity at each fixture supply pipe outlet is not less than the printed value for that outlet;

where a fixture or appliance is not listed, the minimum flow rate and flow pressure come from the

manufacturer's installation instructions (IPC 2024, 604.3 and Table 604.3).

The maximum flow rates and water consumption for plumbing fixtures and fixture fittings are read from

the printed table, with the printed exceptions for blowout design water closets, vegetable sprays,

clinical sinks, service sinks and emergency showers (IPC 2024, 604.4 and Table 604.4).

Hot water and cold water manifolds installed with gridded or parallel-connected individual

distribution lines to each fixture or fitting are sized from the table of manifold sizing, in which

the total gallons per minute is the demand of all outlets supplied; the table reads a maximum demand

against a nominal size at a stated velocity (IPC 2024, 604.10.1 and Table 604.10.1). Where the street

water main pressures fluctuate, the building distribution system is designed for the minimum

available pressure (IPC 2024, 604.6); where the pressure from the street main or other source is not

enough to give the flow pressures at fixture outlets required by the table of design criteria, a

booster system conforming to Section 606.5 is installed (IPC 2024, 604.7); and where the pressure

within a building exceeds 80 psi (552 kPa) static, an approved water pressure-reducing valve

conforming to ASSE 1003 or CSA B356 with strainer is installed, to reduce the pressure in the

building water distribution piping to not more than 80 psi (552 kPa) static (IPC 2024, 604.8).

For the hot water side, the developed length of the hot or tempered water piping, measured from the

source of hot water to the fixtures that require hot or tempered water, is not more than 50 feet

(15 240 mm), with recirculating system piping and heat-traced piping counting as sources

(IPC 2024, 607.2).

7. The storm figures a plan carries

The size of vertical conductors and leaders, of building storm drains and building storm sewers, and

of any horizontal branches of such drains or sewers, is based on the 100-year hourly rainfall rate of

the geographic area as mapped in the figures published with Section 1106.1, or on other rainfall

rates determined from approved local weather data (IPC 2024, 1106.1).

Storm drain piping is sized on the flow rate through the roof drain, that flow rate being converted

from the rainfall rate by Equation 11-1 — the rainfall intensity in inches per hour multiplied by

the roof area in square feet, multiplied by 0.0104 — and then checked against the roof drain

manufacturer's published flow rate for the model and size selected; the flow rate in storm drain

piping does not exceed the printed values of Table 1106.2, which are read against the pipe size for a

vertical drain and for a horizontal drain at a slope of 1/16, 1/8, 1/4 or 1/2 inch per foot

(IPC 2024, 1106.2, 1106.2.1 and Table 1106.2). Vertical leaders are sized on the flow rate from

horizontal gutters or the maximum flow rate through the roof drains, and the flow rate through them

does not exceed the printed values of Table 1106.3, which pairs a leader size with its capacity in

gallons per minute (IPC 2024, 1106.3 and Table 1106.3). Horizontal gutters are sized on the flow rate

from the roof surface, and the flow rate in them does not exceed the printed values of Table 1106.6,

which reads a capacity against the gutter dimensions and the gutter slope (IPC 2024, 1106.6 and

Table 1106.6).

Two geometry rules change the areas and the openings drawn on the plan: one-half of the area of any

vertical wall that diverts rainwater onto the roof is added to the projected roof area, and that

combined area is what enters the calculation of the required size of the vertical conductors, the

leaders and the horizontal storm drainage piping (IPC 2024, 1106.4); and a scupper opening is not

less than 4 inches (102 mm) in height, with a width equal to or greater than the circumference of a

roof drain sized for the same roof area (IPC 2024, 1106.5).

Secondary (emergency) roof drains or scuppers are drawn where the roof perimeter construction extends

above the roof in a manner that would entrap water if the primary drains allow a buildup

(IPC 2024, 1108.1), their discharge end point is separate from the primary system, above grade, at a

location normally observed by the building occupants or by maintenance personnel (IPC 2024, 1108.2),

and they are sized in accordance with Section 1106 on the rainfall rate for which the primary system

is sized, with the flow through the primary system not counted (IPC 2024, 1108.3). Subsoil drains are

drawn at not less than 4 inches (102 mm) in diameter, from open-jointed, horizontally split or

perforated pipe, protected by an accessibly located backwater valve where the building is subject to

backwater (IPC 2024, 1111.1), and a sump pit is drawn at not less than 18 inches (457 mm) in

diameter and not less than 24 inches (610 mm) in depth, located so that all drainage flows into it by

gravity (IPC 2024, 1113.1.2).

8. The units the printed figures arrive in

The sizing figures a plan carries are printed with their units, and the same units are what a reader

takes off the drawing: pipe and trap diameters in inches with millimetre equivalents, slopes in inch

per foot with a millimetre-per-metre equivalent (IPC 2024, Table 704.1 and Table 909.1), capacities in

gallons per minute with a litre-per-minute equivalent (IPC 2024, Table 604.3, Table 1106.2,

Table 1106.3 and Table 1106.6), loads in drainage fixture units (IPC 2024, 709.1 and Table 709.1),

lengths in feet with millimetre equivalents (IPC 2024, 607.2, 708.1.1 and 909.1), pressures in psi

with kilopascal equivalents (IPC 2024, 604.8 and 504.5), and temperatures in degrees Fahrenheit with

degree Celsius equivalents (IPC 2024, 501.2, 501.6 and 607.1.2). The conversions printed with the

tables for SI are part of the reading: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute =

3.785 L/m, 1 inch per foot = 83.3 mm/m (IPC 2024, Table 1106.2, Table 1106.3 and Table 1106.6).

Where a printed table is a grid, the drawing carries the conditions of the row and column, not a

single number: the sizing tables of the code are read at the intersection of those conditions

(IPC 2024, Table 710.1(1), Table 710.1(2), Table 1106.2 and Table 1106.3).

9. What the print read for this text does not carry

The word "isometric" is not printed anywhere in the corpus read for this document: the code's

instrument of communication with the code official is the permit application and the construction

documents of Sections 105 and 106, and the printed rule about what the drawing must make visible is

that construction documents are drawn to scale and are of sufficient clarity to indicate the

location, nature and extent of the work proposed and to show in detail that the work conforms

(IPC 2024, 106.1). No projection convention, no drafting method and no rule of a trade school is

taken from this code, because it prints none. What the code does print, and what a reader of a plan

therefore finds in it, is the pair of things this text has set out: the document rules of Sections 105

and 106, and the printed dispositions whose figures a plan carries — fixture units and loads

(IPC 2024, 709.1 and 710.1), sizes (IPC 2024, 710.1 and 604.3), slopes (IPC 2024, 704.1),

developed lengths (IPC 2024, 607.2, 906.3 and 909.1), clearances (IPC 2024, 903.1.4, 903.5, 708.1.10

and 1106.5), rainfall rates and capacities (IPC 2024, 1106.1, 1106.2 and 1106.3), and the inspection

stages at which each part of the drawn work becomes visible (IPC 2024, 111.2).

10. What the approved drawing binds

The approved construction documents are not a description of intent: the work is done in accordance

with them (IPC 2024, 105.5.1), a returned set is kept on the site while the work is in progress

(IPC 2024, 106.2), the permit or its copy is kept on the site until the project is completed

(IPC 2024, 105.5.7), the work remains visible and able to be accessed for inspection until approved

(IPC 2024, 111.1), and no portion not in compliance is covered or concealed until the code official

authorizes it (IPC 2024, 111.2.3). A drawing whose figures are read off the printed tables is what

the code official reviews against the code, and the same tables are what the installer works to; the

notice of approval follows the tests and inspections, and those tests are the permit holder's to make

and the code official's to observe (IPC 2024, 107.1, 111.4 and 312.1).

Ready to test this chapter?

Practice with exam-aligned questions and timed simulations.

Start Practicing Free