Storm Drainage
Subject guide — a code subject several of the state exam outlines declare.
Storm Drainage
Reference text for the storm drainage area. Every rule below is written from the printed line of the
2024 International Plumbing Code (IPC 2024) that carries it, and each rule names the section it comes
from. Where the printed line does not state a value, no value is stated here; where a sizing table is
printed under a number, the table is reproduced under that number with the values read from the print.
The whole of Chapter 11 of the code is read for this text, together with the sections it refers to.
1. General
The chapter governs the materials, design, construction and installation of storm drainage
(IPC 2024, 1101.1). Rainwater falling on roofs, and storm water from paved areas, yards, courts and
courtyards, must drain to an approved place of disposal; for one- and two-family dwellings, and where
the code official approves it, such water is permitted to discharge onto flat areas such as streets or
lawns as long as the flow is directed away from the building (IPC 2024, 1101.2). The purpose stated by
the code for the whole chapter: rainfall onto buildings must be removed and directed to a location
that can accommodate storm water, and the chapter fixes the design rainfall event for the geographic
area and the sizing methods for piping and gutter systems, together with the piping materials and the
subsoil drainage rules (IPC 2024, Chapter 11, About this chapter).
Storm water must not be drained into a sewer intended for sewage only (IPC 2024, 1101.3). That
prohibition is the mirror of the rule printed for sanitary drainage: where the public sewer is a
combined system carrying both sanitary sewage and storm water, the sanitary sewer is connected
independently to that public sewer (IPC 2024, 703.6), and the storm sewer is likewise connected
independently to it (IPC 2024, 1109.1).
The conductors and the building storm drain are tested in accordance with Section 312
(IPC 2024, 1101.4). The size of a drainage pipe in the storm system must not be reduced in the
direction of flow (IPC 2024, 1101.5). Connections and changes of direction in the storm drainage
system must be made with approved drainage-type fittings in accordance with Table 706.3, and those
fittings must not obstruct or retard the flow in the system (IPC 2024, 1101.6).
Roof design carries a structural rule: roofs must be designed for the maximum possible depth of water
that will pond on them, as determined by the relative levels of the roof deck and of the overflow
weirs, scuppers, edges or serviceable drains, combined with the deflected structural elements. In
fixing that maximum depth, all primary roof drainage means are assumed to be blocked, and the depth
must include the height of water required above the inlet of the secondary roof drainage means for
that secondary means to carry the design rainfall rate required by Section 1106 (IPC 2024, 1101.7).
Cleanouts must be installed in the storm drainage system and must comply with the provisions of the
code for sanitary drainage pipe cleanouts; the exception printed there is the subsurface drainage
system (IPC 2024, 1101.8 and Exception). Storm drainage systems must be provided with backwater
valves as required for sanitary drainage systems in accordance with Section 714 (IPC 2024, 1101.9).
2. Materials
The materials and methods used to construct and install storm drainage systems must comply with this
section and with the applicable provisions of Chapter 7 (IPC 2024, 1102.1).
Inside storm drainage conductors installed above ground conform to one of the standards listed in
Table 702.1 (IPC 2024, 1102.2). Underground building storm drain pipe conforms to one of the standards
listed in Table 702.2 (IPC 2024, 1102.3). Building storm sewer pipe conforms to one of the standards
listed in Table 1102.4 (IPC 2024, 1102.4).
TABLE 1102.4 BUILDING STORM SEWER PIPE
| Material | Standard |
|---|---|
| Acrylonitrile butadiene styrene (ABS) plastic pipe in IPS diameters, including Schedule 40, DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or composite wall | ASTM D2661; ASTM F628; ASTM F1488; CSA B181.1; CSA B182.1 |
| Cast-iron pipe | ASTM A74; ASTM A888; CISPI 301 |
| Concrete pipe | ASTM C14; ASTM C76; CSA A257.1; CSA A257.2 |
| Copper or copper-alloy tubing (Type K, L, M or DWV) | ASTM B75; ASTM B88; ASTM B251; ASTM B306 |
| Polyethylene (PE) plastic pipe | ASTM F667; ASTM F2306/F2306M; ASTM F2648/F2648M; ASTM F2763; ASTM F2947/F2947M; CSA B182.8 |
| Polypropylene (PP) pipe | ASTM F2764; ASTM F2881; CSA B182.13 |
| Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR26, SDR35, SDR41, PS50 or PS100) in IPS diameters, including Schedule 40, DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or composite wall | ASTM D2665; ASTM D3034; ASTM F891; ASTM F1488; CSA B181.2; CSA B182.2; CSA B182.4 |
| Stainless steel drainage systems, Type 316L | ASME A112.3.1 |
| Vitrified clay pipe | ASTM C4; ASTM C700 |
Subsoil drains are open-jointed, horizontally split or perforated pipe conforming to one of the
standards listed in Table 1102.5 (IPC 2024, 1102.5).
TABLE 1102.5 SUBSOIL DRAIN PIPE
| Material | Standard |
|---|---|
| Cast-iron pipe | ASTM A74; ASTM A888; CISPI 301 |
| Polyethylene (PE) plastic pipe | ASTM F667; CSA B182.1; CSA B182.6; CSA B182.8 |
| Polyvinyl chloride (PVC) plastic pipe (type sewer pipe, SDR35, PS25, PS50 or PS100) | ASTM D2729; ASTM D3034; ASTM F891; CSA B182.2; CSA B182.4 |
| Stainless steel drainage systems, Type 316L | ASME A112.3.1 |
| Vitrified clay pipe | ASTM C4; ASTM C700 |
Roof drains conform to ASME A112.3.1 or ASME A112.6.4; roof drains other than siphonic roof drains
are tested and rated in accordance with ASME A112.6.4 or ASPE/IAPMO Z1034 (IPC 2024, 1102.6).
Pipe fittings must be approved for installation with the piping material installed and must conform
to the respective pipe standards or to one of the standards listed in Table 1102.7. The fittings must
not have ledges, shoulders or reductions capable of retarding or obstructing the flow in the piping,
and threaded drainage pipe fittings must be of the recessed drainage type (IPC 2024, 1102.7).
TABLE 1102.7 PIPE FITTINGS
| Material | Standard |
|---|---|
| Acrylonitrile butadiene styrene (ABS) plastic | ASTM D2661; ASTM D3311; CSA B181.1 |
| Cast iron | ASME B16.4; ASME B16.12; ASTM A74; ASTM A888; CISPI 301 |
| Coextruded composite ABS and drain DR-PS in PS35, PS50, PS100, PS140, PS200 | ASTM D2751 |
| Coextruded composite ABS DWV Schedule 40 IPS pipe (solid or cellular core) | ASTM D2661; ASTM D3311; ASTM F628 |
| Coextruded composite PVC DWV Schedule 40 IPS-DR, PS140, PS200 (solid or cellular core) | ASTM D2665; ASTM D3311; ASTM F891 |
| Coextruded composite PVC sewer and drain DR-PS in PS35, PS50, PS100, PS140, PS200 | ASTM D3034 |
| Copper or copper alloy | ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.23; ASME B16.26; ASME B16.29 |
| Gray iron and ductile iron | AWWA C110/A21.10 |
| Malleable iron | ASME B16.3 |
| Plastic, general | ASTM F409 |
| Polyethylene (PE) plastic pipe | ASTM F667/F667M; ASTM F2306/F2306M; ASTM F2763; ASTM F2947/F2947M |
| Polypropylene (PP) plastic pipe | ASTM F2764; ASTM F2881/F2881M |
| Polyvinyl chloride (PVC) plastic | ASTM D2665; ASTM D3311; ASTM F1866; ASTM F3202 |
| Stainless steel drainage systems, Type 316L | ASME A112.3.1 |
| Steel | ASME B16.9; ASME B16.11; ASME B16.28 |
3. Traps
Leaders and storm drains that connect to a combined sewer must be trapped. The trap is installed
either individually, on the storm water drain branch serving each conductor, or as a single trap in
the main storm drain immediately before its connection with the combined building sewer or with the
public sewer. Leaders and storm drains that connect to a building storm sewer are not required to be
trapped (IPC 2024, 1103.1). A storm water trap must be of the same material as the piping system it
is attached to (IPC 2024, 1103.2), and the trap for an individual conductor must be the same size as
the horizontal drain it is connected to (IPC 2024, 1103.3). A cleanout is installed on the building
side of the trap and is provided with access (IPC 2024, 1103.4).
4. Conductors and connections
Conductor pipes must not be used as soil, waste or vent pipes, and soil, waste or vent pipes must not
be used as conductors (IPC 2024, 1104.1). Floor drains must not be connected to a storm drain
(IPC 2024, 1104.2).
5. Roof drains
Roof drains are installed in accordance with the manufacturer's instructions, and the inside opening
of the roof drain must not be obstructed by the roofing membrane material (IPC 2024, 1105.1). The
published flow rate of the roof drain, based on the head of water above the drain, is the figure used
to size the storm drainage system in accordance with Section 1106; the flow rate used for sizing the
storm drainage piping is based on the maximum anticipated ponding at the roof drain
(IPC 2024, 1105.2).
6. Size of conductors, leaders and storm drains
6.1 Design rainfall
The size of vertical conductors and leaders, of building storm drains and building storm sewers, and
of any horizontal branches of such drains or sewers, is based on the 100-year hourly rainfall rate of
the geographic area as mapped in the figures published with the section, or on other rainfall rates
determined from approved local weather data (IPC 2024, 1106.1).
6.2 Storm drain piping
Vertical and horizontal storm drain piping is sized on the flow rate through the roof drain. That
flow rate is calculated in accordance with Section 1106.2.1 and is then checked against the roof
drain manufacturer's published flow rate for the specific model and size of the drain selected, to
verify that the drain will handle the anticipated flow. The flow rate in storm drain piping must not
exceed the values printed in Table 1106.2 (IPC 2024, 1106.2).
TABLE 1106.2 STORM DRAIN PIPE SIZING
| Pipe size (inches) | Capacity (gpm), vertical drain | Capacity (gpm), horizontal drain at 1/16 inch per foot | at 1/8 inch per foot | at 1/4 inch per foot | at 1/2 inch per foot |
|---|---|---|---|---|---|
| 2 | 34 | 15 | 22 | 31 | 44 |
| 3 | 87 | 39 | 55 | 79 | 111 |
| 4 | 180 | 81 | 115 | 163 | 231 |
| 5 | 311 | 117 | 165 | 234 | 331 |
| 6 | 538 | 243 | 344 | 487 | 689 |
| 8 | 1,117 | 505 | 714 | 1,010 | 1,429 |
| 10 | 2,050 | 927 | 1,311 | 1,855 | 2,623 |
| 12 | 3,272 | 1,480 | 2,093 | 2,960 | 4,187 |
| 15 | 5,543 | 2,508 | 3,546 | 5,016 | 7,093 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m
(IPC 2024, Table 1106.2).
6.3 Rainfall rate converted to a flow rate
The rainfall rate falling on a roof surface is converted to a gallon-per-minute flow rate by
Equation 11-1: the flow rate equals the rainfall intensity in inches per hour, multiplied by the roof
area in square feet, multiplied by 0.0104 (IPC 2024, 1106.2.1).
6.4 Vertical leaders
Vertical leaders are sized on the flow rate delivered from horizontal gutters or on the maximum flow
rate through the roof drains. The flow rate through vertical leaders must not exceed the values of
Table 1106.3 (IPC 2024, 1106.3).
TABLE 1106.3 VERTICAL LEADER SIZING
| Size of leader (inches) | Capacity (gpm) |
|---|---|
| 2 | 30 |
| 2 × 2 | 30 |
| 1 1/2 × 2 1/2 | 30 |
| 2 1/2 | 54 |
| 2 1/2 × 2 1/2 | 54 |
| 3 | 92 |
| 2 × 4 | 92 |
| 2 1/2 × 3 | 92 |
| 4 | 192 |
| 3 × 4 1/4 | 192 |
| 3 1/2 × 4 | 192 |
| 5 | 360 |
| 4 × 5 | 360 |
| 4 1/2 × 4 1/2 | 360 |
| 6 | 563 |
| 5 × 6 | 563 |
| 5 1/2 × 5 1/2 | 563 |
| 8 | 1208 |
| 6 × 8 | 1208 |
For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m (IPC 2024, Table 1106.3).
6.5 Vertical walls
When roof drains and storm drainage piping are sized, one-half of the area of any vertical wall that
diverts rainwater onto the roof is added to the projected roof area, and that combined area is the
area used in calculating the required size of the vertical conductors, the leaders and the horizontal
storm drainage piping (IPC 2024, 1106.4).
6.6 Parapet wall scuppers
Where scuppers serve as primary roof drainage, as secondary (emergency overflow) roof drainage, or as
both, their quantity, size, location and inlet elevation are chosen so that the depth of ponding
water on the roof does not exceed the maximum water depth for which the roof was designed as
determined by the International Building Code. Scupper openings are not less than 4 inches (102 mm)
in height and have a width equal to or greater than the circumference of a roof drain sized for the
same roof area. The flow through the primary system is not counted when the secondary scuppers are
located and sized (IPC 2024, 1106.5).
6.7 Roof gutters
Horizontal gutters are sized on the flow rate from the roof surface, and the flow rate in horizontal
gutters must not exceed the values of Table 1106.6 (IPC 2024, 1106.6).
TABLE 1106.6 HORIZONTAL GUTTER SIZING
| Gutter dimensions (inches) | Slope (inch per foot) | Capacity (gpm) |
|---|---|---|
| 1 1/2 × 2 1/2 | 1/4 | 26 |
| 1 1/2 × 2 1/2 | 1/2 | 40 |
| 4 | 1/8 | 39 |
| 2 1/4 × 3 | 1/4 | 55 |
| 2 1/4 × 3 | 1/2 | 87 |
| 5 | 1/8 | 74 |
| 4 × 2 1/2 | 1/4 | 106 |
| 3 × 3 1/2 | 1/2 | 156 |
| 6 | 1/8 | 110 |
| 3 × 5 | 1/4 | 157 |
| 3 × 5 | 1/2 | 225 |
| 8 | 1/16 | 172 |
| 8 | 1/8 | 247 |
| 4 1/2 × 6 | 1/4 | 348 |
| 4 1/2 × 6 | 1/2 | 494 |
| 10 | 1/16 | 331 |
| 10 | 1/8 | 472 |
| 5 × 8 | 1/4 | 651 |
| 4 × 10 | 1/2 | 1055 |
Footnote a of the table: dimensions are width by depth for rectangular shapes, and a single dimension
is the diameter of a semicircle. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute =
3.785 L/m, 1 inch per foot = 83.3 mm/m (IPC 2024, Table 1106.6).
7. Siphonic roof drainage systems
Siphonic roof drains and siphonic drainage systems are designed in accordance with ASME A112.6.9 and
ASPE 45 (IPC 2024, 1107.1).
8. Secondary (emergency) roof drains
Where roof drains are required, secondary (emergency overflow) roof drains or scuppers are provided
where the roof perimeter construction extends above the roof in a manner that would entrap water if
the primary drains allow a buildup of water for any reason. Where primary and secondary roof drains
are manufactured as a single assembly, the inlet and the outlet of each drain are independent
(IPC 2024, 1108.1).
The secondary roof drain system discharges at an end point separate from the primary system, above
grade, at a location normally observed by the building occupants or by maintenance personnel
(IPC 2024, 1108.2).
Secondary (emergency) roof drain systems are sized in accordance with Section 1106, on the rainfall
rate for which the primary system is sized. Scuppers are sized so that the depth of ponding water does
not exceed the depth for which the roof was designed as determined by Section 1101.7; a scupper has
an opening dimension of not less than 4 inches (102 mm) in height, and an opening width equal to the
circumference of the roof drain required for the area served. The flow through the primary system is
not counted when the secondary roof drain system is sized (IPC 2024, 1108.3).
The section on secondary roof drains carries no sizing table of its own in the print read for this
document; the sizing of secondary drains is by reference to Section 1106 (IPC 2024, 1108.3), and the
only sizing tables printed in Chapter 11 are Table 1106.2, Table 1106.3 and Table 1106.6
(IPC 2024, Table 1106.2, Table 1106.3, Table 1106.6).
9. Combined sanitary and storm public sewer
Where the public sewer is a combined system serving both sanitary sewage and storm water, the storm
sewer is connected independently to that public sewer (IPC 2024, 1109.1).
10. Controlled flow roof drain systems
Where the storm drainage system is engineered for controlled flow, the roof of the structure is
designed for the storage of water. The controlled flow roof drain system is an engineered system
under this section and under the design, submittal, approval, inspection and testing requirements of
Section 316.1, and it is designed on the required rainfall rate of Section 1106.1 (IPC 2024, 1110.1).
The control devices are installed so that the discharge rate of water per minute does not exceed the
values for continuous flow indicated in Section 1110.1 (IPC 2024, 1110.2). Runoff control is by those
control devices, and the control devices are protected by strainers (IPC 2024, 1110.3). The minimum
number of roof drains in such a roof is fixed: not fewer than two roof drains in roof areas of
10,000 square feet (929 m²) or less, and not fewer than four roof drains in roofs of more than
10,000 square feet (929 m²) (IPC 2024, 1110.4).
11. Subsoil drains
Subsoil drains are open-jointed, horizontally split or perforated pipe conforming to one of the
standards listed in Table 1102.5, and they are not less than 4 inches (102 mm) in diameter. Where the
building is subject to backwater, the subsoil drain is protected by a backwater valve located with
access. Subsoil drains discharge to a trapped area drain, to a sump, to a dry well or to an approved
location above ground. A subsoil sump is not required to have a gastight cover or a vent, and the sump
and the pumping system comply with Section 1113.1 (IPC 2024, 1111.1).
12. Building subdrains
Building subdrains located below the level of the public sewer discharge into a sump or a receiving
tank whose contents are lifted automatically and discharged into the drainage system as required for
building sumps; the sump and the pumping equipment comply with Section 1113.1 (IPC 2024, 1112.1).
13. Sumps and pumping systems
The sump pump, the pit and the discharge piping conform to Sections 1113.1.1 through 1113.1.4
(IPC 2024, 1113.1).
The sump pump is of a capacity and a head appropriate to the anticipated use requirements
(IPC 2024, 1113.1.1). The sump pit is not less than 18 inches (457 mm) in diameter and not less than
24 inches (610 mm) in depth, unless otherwise approved; it is provided with access and is located so
that all drainage flows into the pit by gravity. The pit is constructed of tile, steel, plastic, cast
iron, concrete or another approved material, with a removable cover adequate to support the
anticipated loads in the area of use, and the pit floor is solid and provides permanent support for
the pump (IPC 2024, 1113.1.2). Electrical service outlets, where they are required, meet the
requirements of NFPA 70 (IPC 2024, 1113.1.3).
The discharge piping meets the requirements of Section 1102.2, 1102.3 or 1102.4 and includes a gate
valve and a full flow check valve; the pipe and the fittings are the same size as, or larger than,
the pump discharge tapping (IPC 2024, 1113.1.4). The exception printed with that rule: in one- and
two-family dwellings only a check valve is required, located on the discharge piping from the pump or
the ejector (IPC 2024, 1113.1.4 and Exception).
14. Where the rules of the chapter meet the other chapters
Storm drainage borrows from the rest of the code by printed reference, and those references fix what
the storm installer shares with the sanitary installer: the tests of Section 312 (IPC 2024, 1101.4),
the drainage-type fittings and changes of direction of Table 706.3 (IPC 2024, 1101.6), the pipe
cleanout provisions of Chapter 7 through Section 1101.8 (IPC 2024, 1101.8), the backwater valves of
Section 714 (IPC 2024, 1101.9), the materials of Chapter 7 through Section 1102.1 (IPC 2024, 1102.1),
and the above-ground conductor materials of Table 702.1 and the underground building drain materials
of Table 702.2 (IPC 2024, 1102.2 and 1102.3). The combination of storm and sanitary flow in one
building drain does not merge the two systems: each is connected independently to a combined public
sewer (IPC 2024, 703.6 and 1109.1).
Ready to test this chapter?
Practice with exam-aligned questions and timed simulations.
Start Practicing Free